Home / Suncorp Group / Determination 979538

Determination 979538

Denial of storm water ingress damage claim relying on gradual deterioration, disrepair and defects exclusions

FirmSuncorp Group
Decided2024-03-18
ProductGeneral Insurance · Home building and contents
OutcomeFor the complainant
Amount awarded—
Non-financial loss$1,500
Amount claimed$282,028
SourceAFCA PDF

Summary

The insurer denied a storm water ingress claim as caused by gradual deterioration and construction defects. AFCA found the claim was covered except for repositioning the weepholes, and ordered repair or cash settlement, expert cost reimbursement up to $5,000 and $1,500 non-financial loss.

The complainant established a storm loss and the insurer did not prove the exclusions applied, as he did not know and should not reasonably have known of the weephole defect.

Issues

Subjects and remedies

home or building damagenatural disasterpay claimpay compensationpay interestpay non financial loss

Related

All Suncorp Group determinations · Find similar determinations

Text of the determination

Determination Case number 979538 Financial firm AAI Limited Determination | Case number: 979538 Page 2 of 9 Case number: 979538 14 March 2024 1 Determination overview 1.1 Complaint Since 2014, the complainant has held home building and contents insurance with the financial firm (insurer). On 22 March 2022, he lodged a claim for water ingress damage he said was attributable to recent storm activity. The insurer has denied the claim. It says that the damage was not caused by a single insured event. Rather, the damage was the result of gradual deterioration, construction defects, and the home’s condition. The policy excludes damage from those causes. The complainant maintains that the damage was the result of extreme levels of wind-driven rain. He wants the insurer to accept the claim and is dissatisfied with its claim handling. 1.2 Issues and key findings Is the insurer entitled to deny the entire claim? No. The balcony wall weepholes were incorrectly positioned, enabling wind driven rain in the severe storm to enter the home. It has not been shown the complainant knew or should have known about the issue with the weepholes, that the home was in disrepair, or that there was gradual deterioration. The insurer is required to accept the resultant water damage and reimburse the complainant’s expert costs . It is not liable for repositioning of the weepholes. Is non-financial loss compensation payable? Yes. The insurer acknowledges it did not properly consider the complainant’s expert reports until he lodged his complaint with AFCA. Further, the insurer did not adequately address his (correct) concerns about how the construction defects exclusion had been applied. These matters caused him stress and inconvenience. The insurer is to pay him $1,500. Why is the outcome fair? The complainant has established a claimable loss under the policy terms and the insurer has not shown the resultant water damage is excluded. It is therefore fair that the insurer covers the cost t o repair the resultant damage. The insurer’s claim handling has unreasonably caused the complainant stress and inconvenience, so it is fair that he receives compensation. 1.3 Determination This determination is in favour of the complainant. If the complainant provides it with written notice he accepts this determination, the insurer is required to:  cover the cost to repair the resultant internal water damage pursuant to the policy terms and conditions. The process to do so is set out in section 2.1 of this determination,  reimburse the complainant’s proven expert costs, up to a $5,000 maximum, and  within 21 days of receiving the notice, pay the complainant $1,500 in non-financial loss compensation. Determination | Case number: 979538 Page 3 of 9 2 Reasons for determination 2.1 Is the insurer entitled to deny the entire claim? No. The balcony wall weepholes were incorrectly positioned, enabling wind driven rain in the severe storm to enter the home. It has not been shown the complainant knew or should have known about the issue with the weepholes, that the home was in disrepair, or that there was gradual deterioration. The insurer is required to accept the resultant water damage and reimburse the complainant’s expert costs. It is not liable for repositioning of the weepholes. Complainant must show a claimable loss under the policy The complainant is required to show, on the balance of probabilities (that it is more likely than not), that he suffered a claimable loss under the policy. This means he must show the loss was caused by a risk for which he is insured. Subject to the terms and conditions set out in the product disclosure statement (PDS), the complainant’s policy covers damage to his home caused by an insured event during the period of insurance. The insured events are the specific incidents listed in th e PDS. ‘Incident’ is defined as: a single event, accident or occurrence which you did not intend or expect to happen. A series of incidents attributable to one source of originating cause is deemed to be the one incident. One of the specified insured event s is ‘Storm’. On 22 March 2022, the complainant notified the insurer that he had been away overseas. On returning home, he found extensive water ingress damage. The complainant attributes the damage to wind driven rain, noting the very high levels of rainfall in February and March 2022. Once the complainant proves the existence of a claimable loss, the insurer is liable for the loss unless it shows an exclusion or limiting condition applies. The insurer has the onus of proving on the balance of probabilities the application of the exclusion or condition. Insurer has denied the claim The insurer agreed to defer assessing the claim until the complainant provided repair quotes. After the quotes were provided in late August 2022, the insurer engaged builder RP. Following an inspection of the home on 5 October 2022, RP confirmed there was water damage to walls, floorboards and ceilings upstairs, and to walls and ceilings downstairs. The insurer’s engineer, JH , inspected the home on 30 November 2022. JH reported that:  the damp proof course (DPC) at the bottom of weepholes, or flashing serving as a DPC, must not be less than: > 150mm above the adjacent ground level, or > 75mm above the finished surface level of adjacent paved or concreted areas that slope away from the wall  the weep holes in the upper floor balconies were effectively at the same level as the external ground. This would allow surface water to flow into the wall cavity, and would be the main cause of the water ingress into the upper floor rooms Determination | Case number: 979538 Page 4 of 9  t he balconies’ slope was almost flat, resulting in inefficient water drainage. This would result in seepage through the concrete walls, and was the cause of the water staining and flaking paint affecting the ground floor  the claimed damage was therefore not due to a single event. JH has provided a supplementary report dated 30 August 2023, in which it responded to the complainant’s expert reports. JH:  acknowledged the comment by engineer NE that the weepholes were appropriately spaced, but maintained that their height above the external surface level did not comply with code requirements  said ‘r egardless of the slope of the balconies, wind driven rain could have easily entered through the weep holes’  noted that NE had relied on Bureau of Meteorology (BOM) rainfall data for February 2023, but the claim was lodged in March 2022  further, the BOM data NE relied on was derived from the Sydney weather station, despite there being stations much closer to the home  rejected NE’s contention 45.8mm in 24 hours was a 1 i n 100 years rain event, and said 280mm was required to qualify as a 1 in 100 years event  submitted that the highest daily rainfall recorded by closest available BOM weather station in the month before the claim was lodged was 103mm on 23 February 2022. Tha t would equate to a 1 in 2 years event  indicated the 2019 Building Code required that water from a 1 in 20 years event be disposed of in a way that will not cause damage. That event would involve 208mm  concluded ‘the dwelling should have been able to cope with the rainfall without damage occurring to any elements. Thus, the available evidence indicates other causation factors are at play. In this case, it is the non-compliant weep holes that have resulted in water ingress and damage’. The insurer says the complainant has not established that the damage claimed was caused by a single storm event. Instead, the damage is due to excluded causes given that the PDS confirms the policy does not cover damage to, caused by, connected with or arising from:  any part of the insured building not being in good condition (examples are provided, including roof leaks, blocked gutters, holes in walls, and other instances of disrepair)  wear, tear and gradual deterioration. The insurer also relies on the ‘Defects’ exclusion in t he PDS, which precludes cover for: • loss or damage caused by, connected with or ar ising from, or liability caused by, connected with or arising from inherent defects, faulty design, structural defects, structural fault or faulty/poor workmanship (e.g. structural posts, beams or load bearing walls have been removed without taking into account structural engineering requirements), if you knew or should have reasonably known about it (e.g. because the defect or fault was able to be observed by you or because it was identified in a pre-purchase building inspection report); • any loss or damage to the part of the building with an inherent defect, faulty design, structural defect or faulty/poor workmanship, whether or not you knew or should reasonably have known about it. Complainant says claim should be accepted The complainant disagrees with the insurer’s claim denial. Determination | Case number: 979538 Page 5 of 9 The complainant says in 2013, he hired a builder to demolish the existing house on the property and build the home. He moved into the home in 2014. He says before doing so, he inspected the home with the builder, and it appeared to be perfect. He denies being aware of any defects before the events the subject of the claim. On 29 July 2022, builder BI provided a repair quote to the complainant, totalling $282,028.20. The quote included photos of the damage, one of which was captioned ‘TOP FLOOR – Internal damage adjacent to the balcony sliding door, due to non- compliant cavity flashing’. The complainant relies on BI’s report dated 13 January 2023. BI says it inspected the home on multiple occasions from 1 April 2022 to 21 December 2022. According to BI:  the home is in good condition, with the roof, gutters, façade, balcony floor and drainage points all adequately draining water  the water ingress damage likely occurred during a rain event in March 2022. During its inspections, including during heavy rainfall, no further water ingress occurred. This suggests the ingress was due to a single, extraordinary event  due to the water ingress, the wooden floorboards have swollen, causing them to raise, buckle, and separate from the subfloor. Mould has appeared and spread. Paint has started to bubble due to dampness from the ingress. The bubbling has increased over time. On 4 September 2023, the complainant provided a further report in which BI confirmed its view that the damage was caused by a one-off storm event. The complainant has also provided a report dated 3 February 2023 by PB, builder. PB said:  it had inspected the home in March 2022 after the water damage was sustained  through laser and level testing, it determined the balcony had the correct falls to waste drainage points  it had been back to the home on several occasions since March 2022, when there has been Southerly wind driven rain. There has been no further water ingress  it inspected other areas where water could ingress as a result of ‘ building failure ’ , including the roof and its drainage points. They were all in a satisfactory condition  the interior damage was the result of record rainfall in March 2022, which according to BOM data (link included) was up by 380% compared to the March average  the flaking paint JH observed when it inspected the home in December 2022, would have been the result of the moisture content since the March 2022 water ingress. PB also prepared a report dated 2 September 2023, which indicates that PB had undertaken repairs. PB said the home’s location made it vulnerable to the elements, and its south - western exposure meant rain would be driven towards it by wind. On 10 March 2023, engineer NE inspected the home. NE reported that:  a survey moisture meter showed a high moisture reading in the upper level walls that had bubbling paint and water staining  the balcony was likely waterproofed with a liquid applied membrane with a screed to falls and tiles  the balcony had appropriate falls to direct water to drainage points  the applicable Australian Standard provides that where flashings are incorporated in masonry, weepholes are to be provided in the masonry immediately above the flashing at centres not exceeding 1200mm. That had been achieved  at the reported time the water ingress occurred, 45.8mm of rainfall fell in 24 hours, constituting a 1 in 100 years rain event  ‘the cause of the internal water ingress is due to excessive wi nd driven rain which has allowed moisture to penetrate internally.’ Determination | Case number: 979538 Page 6 of 9 NE provided a second report, dated 18 August 2023. NE provided BOM data for the weather station closest to the home. It noted that 76mm fell on 23 February 2022, and 157mm on 8 March 2022. NE said the latter represented a 1 in 100 years event. NE maintained its conclusion that the water ingress was due to wind driven rain in the storm. Insurer is not entitled to deny the entire claim Based on the exchanged information, the panel is not satisfied that the insurer is entitled to deny the internal water damage to the home. The panel is satisfied that the complainant has established a claimable loss. The BOM data provided shows there was significant storm activity in early March 2022, culminating in 157mm of rainfall on 8 March 2022. The panel is satisfied the storm activity was a single incident or a series of incidents attributable to the prevailing atmospheric conditions. The panel acknowledges there are conflicting references to what amounts to a 1 in 100 years rainfall event etc, and that the rainfall data from different weather stations varies. However, it is notable that the BOM has confirmed that the 157mm recorded on 8 March 2022 at the closest station to the home was the highest March da ily rainfall ever recorded at the station. The southern side of the home is wind exposed. The insurer has not factored in the effect of wind driving the rain towards the home. BI and PB both stated that no further water ingress occurred, despite subsequent storms with wind driven rain. That supports the position the water ingress was due to a single, severe storm event, with wind driven rain entering the home through the balcony weepholes. The panel is not satisfied the insurer can exclude the resultant internal damage because:  there is no persuasive evidence the home was in a state of disrepair, or that the internal damage was due to gradual deterioration  the insurer’s engine er has stated: > ‘ regardless of the slope of the balconies, wind driven rain could have easily entered through the weep holes’ , and > ‘ it is the non - compliant weep holes that have resulted in water ingress and damage’  accordingly, the building condition and the gradual deterioration exclusions do not apply  the first part of the defects exclusion concerns resultant damage from a defect. It requires that the insured knew or should reasonably have known about the defect  the complainant has consistently denied being aware that the weepholes were incorrectly position/defective until the internal water damage was identified in March 202.  there is no information that suggests his denial should be doubted or not accepted  there is no reasonable basis to conclude the complainant should have reasonably been aware that the weepholes were defective. None of the experts have stated that a reasonable home owner in his position should have been aware of the defect. There are no documents (such as a pre-purchase report) that should have put him on notice  the 2019 Building Code referred to by JH does not apply as the home was built in 2014. The second part of the defects exclusion relates to the defective item itself. It applies regardless of whether the insured person knew or should reasonably have known about the defect. Accordingly, the insurer is entitled to exclude the cost of repositioning the weepholes. How the claim is to be settled If the complainant accepts this determination, the insurer is required to cover the cost to repair the resultant internal water damage pursuant to the policy terms and conditions. Determination | Case number: 979538 Page 7 of 9 To the extent the complainant has attended to the internal damage repairs already:  he must provide a copy of the relevant scopes of work, quotes and invoices to the insurer  within 21 days of receiving the abovementioned documents, the insurer must complete a desktop assessment of whether any of the items are not claim related  within seven days of completing the desktop assessment, the insurer is to: > provide to the complaint the desktop assessment, together with detailed written reasons for the items (if any) it has not accepted as being claim related > pay the complainant the amount it has assessed as covered, plus interest pursuant to section 57 of the Insurance Contracts Act, 1984 (Cth) from the date the complainant proves each item was paid, until the date it reimburses him. To the extent the complainant has not attended to the internal damage repairs already, the insurer may choose to attend to repairs, or to pay a cash settlement for them. if it elects to pay a cash settlement, it must do so based on a current quote for the retail cost of the repairs payable by a consumer and pay the quoted amount plus a 15% contingencies uplift. The complainant retains the right to lodge a further complaint if he is dissatisfied with the amount the insurer pays for the repairs or the adequacy of its repair work. Insurer is to reimburse complainant’s expert costs The AFCA Rules enable AFCA to require an insurer to contribute to the professional costs incurred by the complainant. These costs are, however, usually capped at a total of $5,000, unless special circumstances apply. When considering whether to require an insurer to make a costs contribution, AFCA considers matters such as the complexity of the complaint and whether the complainant needed to incur costs to understand or establish their claim. The reports the complainant obtained from BI, PB and NE have assisted him in establishing an entitlement to coverage for the claim. Upon receiving from the complainant proof of payment for those reports, the insurer is to reimburse him up to $5,000 of the proven costs. 2.2 Is non-financial loss compensation payable? Yes. The insurer a cknowledges it did not properly consider the complainant’s expert reports until after he lodged his complaint with AFCA. Further, the insurer did not adequately address his (correct) concerns about how the construction defects exclusion had been applied. These matters caused him stress and inconvenience. The insurer is to pay him $1,500. AFCA can award compensation for poor claim handling Under the AFCA Rules, we may award compensation (capped at $5,400) for non-financial loss where a complainant has suffered an unusual degree or extent of physical inconvenience, time taken to resolve the situation or interference with their expectation of enjoyment or peace of mind. Insurer has caused stress and inconvenience The complainant says the insurer’s poor claim h andling has caused him considerable stress, frustration and inconvenience. He says that he went to considerable time and effort in obtaining expert reports, only for them to be ignored. He also refers to detailed emails he sent to the insurer about the defects exclusion, to which he never received an adequate response. Determination | Case number: 979538 Page 8 of 9 The insurer acknowledges it did not consider the complainant’s expert reports until after it had lodged its notice of response with AFCA. It is also apparent that the insurer did not address his concerns about how the defects exclusion had been applied. Those concerns were valid. Had the insurer taken them into account, the claim may have resolved at an earlier time. The panel is satisfied it is reasonable to require the insurer to pay $1,500 in compensation. 2.3 Why is the outcome fair? The complainant has established a claimable loss under the policy terms and the insurer has not shown the resultant water damage is excluded. It is therefore fair that the insurer covers the cost to repair the resu ltant damage. The insurer’s claim handling has unreasonably caused the complainant stress and inconvenience, so it is fair that he receives compensation. Determination | Case number: 979538 Page 9 of 9 3 Supporting information 3.1 The AFCA process AFCA’s approach is based on fairness AFCA has determined this complaint based on what is fair in all the circumstances, having regard to:  the legal principles  applicable industry codes or guidance  good industry practice  previous decisions of AFCA or its predecessor schemes (which are not binding). The respective parties have completed a full exchange of the relevant information, and each party has had the opportunity to address any issues raised. We have reviewed and considered all the information the parties have provided. While the parties have raised several issues in their submissions, we have restricted this determination to the issues that are relevant to the outcome. A panel determined this matter Due to the nature of this complaint, we referred it to a panel for determination. The panel includes:  an ombudsman  a member with significant experience in consumer and small business advocacy  a member with extensive experience in the insurance industry. We assess complaints on available information and circumstances AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to require third parties to give evidence. When we assess complaints, we consider:  available documents  the recollections of the parties  all relevant circumstances. We give more weight to documents created at the time the events occurred. If there are no relevant documents, we will decide what most likely occurred based on the available information. If there are conflicting recollections and these are evenly weighted, we may find that a claim cannot be established.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.