Home / Hollard / Determination 975018
Determination 975018
Claim denied for cracking said to be caused by excluded earth movement rather than earthquake
Summary
Complainants claimed for cracking to their home after an earthquake and the insurer denied it as excluded earth movement. AFCA found the western and rear cracking was covered, the eastern cracking was not, and ordered a scope of works and cash settlement with 10% uplift.
The insurer bore the onus of proving the earth movement exclusion and failed to show the earthquake was not the proximate cause of the more significant western and rear cracking.
Issues
- Claim denial primary · upheld“The insurer is liable to repair the damage consisting of cracking to the western side and rear corner of the property”
- Inadequate claim investigation secondary · unclear“Insurer's engineer did not effectively respond to the differential footings explanation; alternative causes not sufficient for all damage”
Subjects and remedies
home or building damagenatural disasterpay claim
Related
Text of the determination
Determination
Case number 975018
Financial firm The Hollard Insurance Company Pty Ltd
Determination | Case number: 975018 Page 1 of 7
Case number: 975018 12 December 2023
1 Determination overview
1.1 Complaint
The complainants have claimed under their home insurance policy for damage they say was
caused by an earthquake event on 21 September 2021.
The financial firm (the insurer) has denied the claim as they say the damage was not caused
by the earthquake and was instead caused by unrelated earth movement over time which is
excluded under the policy.
1.2 Issues and key findings
Is the insurer entitled to deny the claim?
No, whilst the cracking on the eastern side of the home was likely caused by earth movement
excluded under the policy, the more significant cracking to the western side and rear of the
building was most likely caused by the earthquake. The insurer is liable to repair the damage
consisting of cracking to the western side and rear corner of the property (detailed later in this
determination as the covered cracking).
Why is the outcome fair?
The insurer has limited its policy cover so damage caused by earth movements other than
earthquake are not covered. The insurer bears the proof of establishing the limitation is
applicable.
T he complainant‟s engineer has put convincing arguments as to why an earthquake event of
the intensity involved did cause a significant portion, though not all, of the cracking to the
home. They also effectively called in to question whether the insurer‟s engineer‟s alternative
list of causes would have been sufficient to cause all of the damage.
1.3 Determination
This determination is substantially in favour of the complainants. Within 14 days of
notification of the complainant‟s acceptance of this determination the insurer must:
arrange for a builder/engineer to attend, assess and prepare a scope of works (SOW)
required to repair the covered cracking;
on receipt of the SOW provide a copy to the complainant; and
then cash settle the claim based on the SOW and quote obtained including a 10% uplift for
transfer of risk and contingencies.
Determination | Case number: 975018 Page 2 of 7
2 Reasons for determination
2.1 Is the insurer entitled to deny the claim?
No, whilst the cracking on the eastern side of the home was likely caused by earth movement
excluded under the policy, the more significant cracking to the western side and rear of the
building was most likely caused by the earthquake. The insurer is liable to repair the damage
consisting of cracking to the western side and rear corner of the property (detailed later in this
determination as the covered cracking).
Policy covers accidental loss and damage and not otherwise excluded
The initial onus is on the complainant to establish on the balance of probabilities (that is more
likely than not) that the loss or damage falls within the terms of the policy. This is known as a
valid (or prima facie) claim.
Once the complainant has established a valid claim, the onus shifts onto the insurer to
establish, on balance, the application of a policy exclusion or that it is otherwise entitled to
deny the claim under the policy.
Insurer must show the proximate cause of the damage is excluded
The complainant‟s policy provides cover for accidental da mage. Both parties accept that there
has been damage and that it has been accidental. I am satisfied that the complainants have
established a valid claim under the policy. The onus therefore shifts to the insurer to show
that it is entitled to deny the claim.
The insurer refers to exclusions for:
Settling, shrinkage or any movement of earth; and
Rust, corrosion, gradual deterioration, depreciation, wear or tear.
There is an exception to the exclusion regarding earth movement, where the damage
occurred within 72 hours of, and as a result of, an earthquake.
To deny the claim, the insurer must show that the proximate cause of the damage falls within
the exclusion clause it is relying upon.
The evidence from both sides is that the damage resulted from earth movement. To be
successful the insurer needs to establish that the proximate cause of that movement was
something other than the earthquake. This is a question of fact depending on the
circumstances. The proximate cause is not necessarily the first, or last or sole cause of the
loss. It is the effective, dominant or operative cause of the loss.
The circumstances of the claim
At the time of the claim the complainants‟ home was approximately 4 years old, the build
having been completed sometime in 2017. It is of double story brick veneer construction, with
basement walls of 300mm thick, filled block concrete blocks, and a first and second floor of
timber frame construction with internal plasterboards and external brick veneer and a
concrete slab floor. There is also an alfresco area with a double brick wall. All external walls
are rendered.
There was an earthquake event on 22 September 2021, the centre of which was located
some 120 kilometres from the complainant‟s property and 10 kilometres below the s urface. It
Determination | Case number: 975018 Page 3 of 7
measured 5.9 on the Richter Scale and the authorities estimated the impact in the area of
complainant‟s property at IV on the Modified Mercalli Sc ale (MMI). That scale is used to rate
the level of felt and measured impacts of an earthquake for a particular location.
The complainants‟ lodged their claim on 26 November 2021. There is both external and
internal cracking to the home building. In particular there are:
cracks at both ends of the west facing double brick alfresco wall which are 2-3mm wide at
the rear boundary and 1mm wide at the other end;
cracks to the west facing brick veneer façade at ground floor level;
some render cracking on the eastern wall of the house: and
minor interior cracks.
The expert evidence on causation
Both parties relied on engineer‟s reports on the issue of causation and the engineers provided
a number of follow up reports adding to their views or commenting on the views of the other
party‟s engineer. Both also had builder‟s reports and it was the builders who were the first to
attend the property.
The insurer‟s engineer concluded that the cracking was not caused by the earthquake They
relied on the MMI estimate of IV, which means light shaking which is not expected to cause
structural damage to buildings. They also did a floor level survey that found variation in the
slab floor level in the home of 32mm with a general pattern of relative settlement towards the
internal central region of the house.
They noted that the area has moderately reactive clay soils which could expand and contract
with changes in moisture content. They considered the location and pattern of the cracking
was consistent with damage caused by differential foundation movements due to reactive
soils combined with long term deflection of the supporting structure, i.e. the central settlement
of the slab. They also noted that there was evidence at the property of previous repairs of
cracks which suggested cracking had occurred prior to the earthquake. This was also
observed by the insurer‟s builder.
They considered that the damage had been caused by a combination of:
Long term differential footing movements associated with variation in moisture content of
the reactive clay soil;
Long term deflection of supporting structure (suspended slab and steel beams) within the
central region of the house;
Absence of articulation joints within brick walls;
Long term brick growth; and
Long term movement of cementious rendering and underlying brickwork due to different
thermal expansion rates.
The complainant provided evidence from their builder that after the earthquake some
patching of cracks had been done on a temporary basis on 23 November 2021 to prevent
further separation. The complainant‟s engineer said that long term movement of footings
should be ruled out as a cause as there had not been significant variation in soil moisture
content in recent years and that failed footings would produce vertical cracks rising from the
ground up which was not evident here.
They considered that settling of the slab in the centre of the house would not produce major
cracks in brick veneer walls because the bricks are supported by the basement walls and the
footings and are not supported by the floor joists. They argued that if central sagging were to
Determination | Case number: 975018 Page 4 of 7
blame there would be more cracks in the internal stud walls. In their view variat ion in floor
heights of 10-30mm were possible as variation from the building process rather than
subsequent movement.
They provided evidence that contrary to the insurer‟s engineer‟s report, there were articulation
joints in the walls. They considered brick growth would not be a significant force in the 4 years
the building had been in place. In relation to differential expansion rates of cement render
they were of the view that whilst it can cause cracks but not cracks of the size found on the
west façade of the house.
They state it is fairly common to get brick cracks in an earthquake of MMI IV. They also
explained that the fact that the west façade sat on two different footings of different depth, the
garage footing at the front and the shallower strip footing at the rear, it was more vulnerable
to cracking. They considered that the footings reacted differently to the shockwaves from the
earthquake and “like two ocean waves running into each other” this released forces upward
causing the crack in the brick veneer area above where the strip footings meet with the
basement wall. The complainant‟s engineer placed particular emphasis on this last point
relating to differential footings as explaining how an earthquake of the size involved could
cause the significant cracking at both ends of the western façade.
Assessment of evidence on causation and conclusions
I accept that the MMI rating of IV for an earthquake event would in the majority of cases mean
that there is unlikely to be structural damage caused to buildings. However I also
acknowledge that this can be impacted by many local factors. The i nsurer‟s engineer stated
that these factors, such as local geology and the structure of the building, can lead to
considerable variations in damage caused even within a single neighbourhood.
The issue of whether there was any pre-existing cracking is contested. The complainant
provided strong evidence that the builder who attended the property in November 2021 did
some temporary repairs. Counter to this the insurer‟s builder and engineer both considered
that some of that cracking and repairs looked older and that some of the repairs had opened
up by the time of the builder‟s visit to the property in December 2021 and the engineers in
February 2022. I accept that there was some pre-existing cracking. I accept the evidence
that some of the cracking looked ol der. I don‟t consider it likely that cracks caused by an
earthquake in September and patched in November would reopen so quickly.
Nevertheless, I don‟t accept that the sources of movement identified by the insurer‟s engineer
were sufficient to cause all of the cracking at the property and in particular the wider cracking
on the western façade. All of the potential causes they identified were long term, yet the
building was only 4 years old.
Long term differential footing movements caused by variation in soil moisture content can
generate movement and cause cracking. But a table provided by the insurer‟s engineer put
those movements where the soil is moderately reactive as having a timeframe of greater than
20 years and less than 40 years. The engineer noted that that is for normal variations in
moisture content and that it can be quicker where those variations are abnormal. The
engineer provided a range of possible reasons for abnormal variation in soil moisture content,
but only provided arguments for variation caused by the drying effects of tree roots in the
vicinity. They stated that there were numerous trees and shrubs in close proximity to the
building. This claim does not appear to be supported by the aerial and other photos of the
property which show relatively modest tree cover, particularly in comparison to other houses
in the area.
Determination | Case number: 975018 Page 5 of 7
I prefer the evidence of the complainants‟ engineer that the impact of „long term brick growth‟
is unlikely to be significant in a 4 year old building. Similarly, I agree with them that „long term
movement‟ in cementous render and brickwork would not be sufficient, in such a young
building, to contribute significantly to the creation of such wide cracks as appear in the
western façade.
The floor survey done by the insu rer‟s engineer provided useful evidence. It found variation of
30mm with it being generally lower in the centre of the house. This might support the
argument that the house was impacted by earth movement from non-earthquake sources.
The complainant‟s engin eer considered 30mm of variation might be within normal range
whilst the insurer pointed to building standards that it should be no more than 20mm.
I am persuaded by the arguments of the complainant‟s engineer that the external walls the
subject of cracking are supported by the footings. If earth movement generated sagging of the
central part of the house had caused the major cracking in the western façade, there would
also be cracking in the internal walls closer to the site of the sagging. There are no such
cracks reported.
Finally, in relation to the absence of articulation joints as a possible contributor to the
damage, the two engineers now agree that there are articulation joints but that they have
been rendered over. The insured‟s engineer states th at the rendering over of them can
restrict their intended function and lead to cracking in the render. This appears true in the
present case as there are render cracks reported at their locations in the structure.
T he complainant‟s engineer has provided an explanation, being the differential footings under
the two ends of the western side of the house, about how the earthquake forces involved
could cause the significant cracking in the that façade. The insurer‟s engineer did not
effectively respond to that explanation other than by asserting that if braced to standards a
building should not be impacted by an earthquake event of the intensity involved.
Whilst as noted I accept there was some pre-existing cracking from other causes, I consider it
more likely that the more significant cracks have been caused by the earthquake and thus the
insurer is liable for the repair of those cracks.
Settlement of the cracking damage
As the two parties have taken absolute positions, that either all the damage was caused by
the earthquake or none was, there is a lack of evidence addressing each of the cracks
separately. This creates challenges when seeking to delineate which cracks are more likely
generated by the earthquake and which by excluded sources of earth movement. In
undertaking that task I have remained conscious that the burden of proof is on the insurer to
establish the exclusion
The complainant‟s case is convincing as regards the western façade of the house and the
alfresco wall. This extends to damage associated with separation of the range hood in the
alfresco, the vertical cracking to the wall at the southwest corner (Photographs 5 and 6 in the
insurer‟s engineer‟s report dated 3 March 20 22) and the cracking to the southern side of the
basement (photograph 15, 16, 17 and 18 of that same report). I am satisfied that the insurer
is liable for the repairing of all of that cracking (the covered cracking).
No information is available on the cost of those repairs. It is fair in the circumstances that
within 14 days of notification of the complainant‟s acceptance of this determination the
insurer:
Determination | Case number: 975018 Page 6 of 7
arrange for a builder/engineer to attend, assess and prepare a scope of works (SOW)
required to repair the covered cracking;
on receipt of the SOW provide a copy to the complainant; and
the insurer can then cash settle the claim based on the SOW and quote obtained including
a 10% uplift for transfer of risk and contingencies.
I consider the cracking on the eastern side of the house, which is more hairline cracking to
the render and does show signs of prior repairs to be more consistent with the longer term
causes identified by the insurer‟s engineer, noting also that no argumen t was made about
differential footings on that eastern side. I am satisfied the insurer is not liable for this
damage.
2.2 Why is the outcome fair?
The insurer has limited its policy cover so damage caused by earth movements other than
earthquake are not covered. It has effectively communicated that limitation in the policy
documents provided to the complainant.
Both parties have had the opportunity to put their case and the views of their experts and to
consider and respond to the arguments and evidence, including expert evidence, put by the
other.
The insurer‟s engineer‟s case principally relies in the relatively low MMI rating of the event‟s
impact in the area of the property and puts forward other potential causes of cracking all of
which are long term but which if applicable would exclude the damage from cover.
The complainant‟s engineer has put convincing arguments as to why an earthquake event of
the intensity involved could cause a significant portion, though not all, of the cracking to the
home. They also effectively called in to question whether the insurer‟s engineer‟s alternative
list of causes would have been sufficient to cause all of the damage in the circumstances
involved including the relatively low age of the house. On balance the insurer has not satisfied
the burden of proof on it to prove the application of the exclusion to the covered cracking.
Determination | Case number: 975018 Page 7 of 7
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.