Home / Chubb / Determination 952432
Determination 952432
Insurer declined claim for collapsed retaining wall relying on exclusions and s54 ICA
Summary
A company's retaining wall collapsed after extreme rain and the insurer declined that part of the claim, citing inadequate drainage, exclusions and s54 ICA. AFCA found for the complainant and required the insurer to accept and assess the claim under the policy, with a cash settlement option based on a quote plus 15% contingencies.
Heavy rain and inadequate drainage were interdependent proximate causes, and the insurer did not discharge its onus of proving any exclusion or s54(2) ICA breach.
Issues
- Claim denial primary · upheld“The insurer has not established that an exclusion applies that would entitle it to decline the claim.”
- Inadequate claim investigation secondary · upheld“Insurer's engineer conclusions on 2015 repair based on desktop photo review; AFCA not persuaded wall was repaired or rebuilt”
- Product terms interpretation secondary · upheld“exclusions for wear and tear, latent defect, faulty workmanship, design error did not apply; 'making good' wording misread by insurer”
Subjects and remedies
broker or intermediaryhome or building damagenatural disastersmall businesspay claimrepair or rectify
Related
Text of the determination
Determination
Case number 952432
Financial firm Chubb Insurance Australia Limited
Determination | Case number: 952432 Page 1 of 9
Case number: 952432 21 February 2024
1 Determination overview
1.1 Complaint
The complainant holds an Industrial Special Risks insurance policy (policy) with the financial
firm (insurer). The policy includes cover for material loss or damage to real and personal
property. The complainant lodged a claim on the policy after a retaining wall collapsed
following heavy rain on or around 26 - 27 February 2022.
The insurer denied liability for the collapsed wall but accepted the claim for damage to the
complainant’s building damaged by the collapse, including removal of debris to allow repair of
building. The insurer says the wall collapsed due to a build up of hydrostatic pressure caused
by inadequate drainage and relied on exclusions in the policy and on section 54 of the
Insurance Contracts Act 1984 (ICA).
The complainant says the insurer should accept the claim for the collapsed wall (damage) as
the damage is not excluded by the policy.
The complainant company is represented by the broker, CC. For simplicity, I will refer to the
complainant and broker collectively as ‘the complainant’.
1.2 Issues and key findings
Is the insurer entitled to decline the claim?
No. While inadequate drainage contributed to the wall’s collapse, the extreme rainfall was
also causative of loss. The available information establishes on the balance of proba bilities
damage occurred due to a combination of inadequate drainage and heavy rainfall. As the
collapse was unforeseen and unexpected, the complainant has established a valid claim
under the policy. The insurer has not established that an exclusion applies that would entitle
it to decline the claim.
Why is the outcome fair?
The outcome is fair because the insurer has not shown that an exclusion applies, or that it is
otherwise entitled to decline the claim. Therefore, it is fair that the insurer covers the damage
in accordance with the policy terms and conditions.
1.3 Determination
The determination is in favour of the complainant. If the complainant accepts this
determination, the insurer is required to accept the claim and assess it in accordance with the
policy’s terms and conditions.
If the insurer elects to pay the complainant a cash settlement for the claim, it must obtain a
quote for the necessary repairs, based on the reasonable current cost payable by a consumer
such as the complainant. It must pay the complainant the quoted amount plus a 15%
contingencies uplift. The insurer’s liability is limited by the relevant policy sublimit.
Determination | Case number: 952432 Page 2 of 9
2 Reasons for determination
2.1 Is the insurer entitled to decline the claim?
No. While inadequate drainage contributed to the wall’s collapse, the extreme rainfall was
also causative of loss. The available information establishes on the balance of probabilities
damage occurred due to a combination of inadequate drainage and heavy rainfall. As the
collapse was unforeseen and unexpected, the complainant has established a valid claim
under the policy. The insurer has not shown an exclusion applies that would entitle it to
decline the claim.
Background to the current claim
The insured property consists of several large-scale steel framed warehouses located in an
industrial area. The majority of the property is paved with a relatively level concrete slab. The
land has a natural slope and has retaining walls on the southern boundary of the property
with an average height of 3250mm. A moderately sloping 6m width of lawn is located
between the south retaining wall and paved carpark of the neighbouring south property. This
determination concerns the retaining wall on the eastern portion of the southern property
boundary line behin d the building referred to by the parties as ‘the factory’ .
Until 2015, the relevant retaining wall was a concrete crib wall. Following a storm in 2015
part of the crib wall collapsed and part of the crib wall bowed. The complainant says, and the
insurer does not dispute, that a 12m section collapsed at the western end of the wall and was
replaced in 2015 by the complainant with a concrete panel and post wall (panel wall). The
parties dispute what damage and work occurred beyond this.
Circumstances of the 2022 loss and claim
Following heavy rain on 26 - 27 February 2022 the concrete crib retaining wall was damaged
and a large section collapsed. This was discovered on Monday 28 February 2022, and the
complainant lodged a claim with the insurer. The damaged wall (disputed wall) was to the
east of the panel wall built in 2015. The collapse of the disputed wall damaged approximately
12m of the factory’s sheet metal wall. The insurer has accepted the claim for the damage to
the factory structure but not the retaining wall.
The insurer says it is not required to pay the damage because it falls within the policy’s
exclusion clauses. It says the proximate cause of the damage was not storm but a build up of
hydrostatic pressure caused by an absence of granular fill and drainage. It says the wall was
repaired or rebuilt as a crib wall after the 2015 event.
Policy covers material loss or damage subject to terms and conditions
The full details of the policy coverage, conditions, limitations, and exclusions are contained
within the Policy Wording (PW). There is no dispute the insurer sent the PW to the
complainant. Therefore, the insurer is entitled to rely upon the terms of the policy.
The policy covers material loss or damage to all real and personal property (except as
specifically excluded) belonging to the complainant during the period of cover. I accept the
presence of material damage to the retaining wall during the period of insurance was
unintentional and unexpected and is therefore a claimable loss. The onus therefore transfers
to the insurer to show why it is not liable for the claimed damage.
Determination | Case number: 952432 Page 3 of 9
.
The insurer relies on exclusions to deny the claim
The insurer says it is not required to cover the damage as it relies on paragraph (4) of the
Perils Exclusions in the policy which relevantly states the insurer will not be liable under
Section 1 (material damage) in respect of:
4. Physical loss, destruction or damage occasioned by or happening through
(a) … a latent defect
(b) wear and tear, fading, scratching or marring, gradual deterioration or
developing flaws, normal upkeep or making good
(c) error or omission in design, plan or specification or failure of design
(d) normal settling, seepage, shrinkage or expansion in buildings or foundations,
walls, pavements, roads and other structural improvements, creeping, heaving
and vibration
(e) faulty materials or faulty workmanship
…
The insurer also relies on:
Condition 11 (applicable to all sections):
11. Precautions To Prevent Loss
The Insured shall take all reasonable precautions to prevent loss, destruction or damage
to the property insured by this Policy. (insurer’s emphasis)
Insurer and complainant rely on expert reports
Following the 2022 collapse of the disputed wall, the insurer engaged engineer, EC, to
determine the cause of the collapse. EC inspected the damage on 5 April 2022. EC’s first
report (EC1) is dated 21 April 2022. EC1 says:
the failure occurred to 12 metres of the concrete crib wall
the crib wall sustained failure by overturning
the remaining section of crib wall had a gradient greater than the 4:1 incline required in
concrete crib wall construction and also appeared to be overturning
no damage was apparent to the panel wall
the soil behind both retaining (crib and panel) walls is clay-based earth
no free-draining granular material could be observed in the soil behind the crib wall which
is required as a component of the drainage construction
the cause of the wall failure was build-up of hydrostatic pressure at the rear of the wall due
to ineffective drainage
the damage to the crib wall was not consistent with damage caused during the recent
heavy rainfall event or by another single event but was attributed to ineffective drainage
over a long time.
The complainant engaged engineers, AS, to determine the cause of the crib wall collapse.
AS inspected the damage on 14 March 2022 and 20 May 2022. AS’s first report ( AS1) is
dated 26 May 2022. AS1 says:
the crib wall is 50 to 60 years old
Determination | Case number: 952432 Page 4 of 9
Bureau of Meteorology (BOM) data for the area shows rainfall of 68mm on Friday 25
February 2022; 224mm on Saturday 26 February 2022; and 193mm on Sunday 27
February 2022 (AS has attached that BOM data to AS1)
there is no Australian Standard that prescribes drainage to be installed with a retaining wall
and, even if there was, EC would be comparing current standards with a structure
designed and constructed at least 50 years ago
e ven if a 100mm ag pipe and granular material was installed as per EC1’s section drawing,
the wall would have been subjected to the same hydrostatic pressure as a retaining wall
without drainage
the collapse of the retaining wall is a direct consequence of the extreme rain event that
occurred during the weekend of 26 February 2022.
After EC1 and AS1 were prepared, the insurer provided the report and scope of works (SOW)
prepared by engineer, CR, dated 12 June 2015, to EC and the complainant. CR ’s report
responds to enquiries by a (different) insurer regarding the 2015 crib wall collapse and
subsequent insurance claim. That report contains photos, including of the collapsed and
bowed wall, and says:
12m of the crib wall collapsed
approximately 5m of the crib wall ‘is observed to be ‘bowing’ outwards from the retained
soil adjacent to the collapsed section of the wall’
the collapsed sect ion of the wall has exposed the retained soil which reveals no ‘free
draining granular fill’ or ‘geotextile fabric’
no surface drainage infrastructure was observed to be installed at the top of the retaining
wall
the collapse occurred during a one-off extreme rainfall event
the proximate cause of the damage to the crib wall was inadequate drainage behind the
retaining wall which has allowed an excessive build-up of hydrostatic pressures
overloading the structure
the crib wall should comply with Australian Standard AS4678 but does not
there is little evidence the collapse occurred over the long term
the remaining length of the retaining wall appears to be inclined into the retained earth as it
was constructed
CR’s opinion is that rebuilding the wall in part is not possible and complete deconstruction
of the wall is required.
The insurer has provided EC’s second report (EC2 ) dated 29 June 2022. EC2 commented on
AS1 and also provided comment on CR ’s report relating to the 2015 collapsed of part of the
crib wall, together with their earlier inspection and findings. EC2 says:
the CR report shows a large section of the crib wall collapsed in an identical fashion to the
most recent collapse
the wall was replaced in 2015 making it far less than 50 years old and should have been
reconstructed in accordance with AS4678 (2002) back in 2015
the CR report concluded that the retaining wall collapsed in 2015 due to hydrostatic
pressure caused by absence of drainage medium. The 2022 collapse was from the same
cause, as set out in EC1
the CR report stated that the wall could not be partially repaired and that the entire wall
needed to be replaced with a new wall in accordance with AS4678 – Earth Retaining
Structures
a crib wall that conforms with the Concrib installation manual 2024 and AS4678 (relevant
standards) is free-draining and would not have been affected by hydrostatic pressure,
causing the collapse
Determination | Case number: 952432 Page 5 of 9
the relevant standards were in place in 2015, and were included in the CR report, when
the works on the crib wall were undertaken
the CR report required the replacement wall to feature drainage as per the relevant
standards. This was due to the wall failing in 2015 because of lack of drainage and
consequential hydrostatic pressure
the replacement or repaired wall did not have drainage or meet the relevant standards.
That left the wall susceptible to another failure
it is likely that AS was not told about the 2015 collapse and therefore their conclusion
relied on incorrect assumptions about the age of the wall, construction and compliance
requirements. The incorrect assumptions led to an incorrect conclusion.
The complainant provided an email from AS dated 4 July 2022 ( AS2) addressing issues
raised by EC. To the extent that new information was provided, AS2 says:
the overturning/collapse was a consequence of the elevated hydrostatic pressure on the
back of the crib wall due to the extreme rain event. The resulting horizontal forces
exceeded the resistance capacity of the crib wall
AS1 commented on the crib wall only, therefore the statement that the wall is 50 years old
is correct
AS did not see and was unaware of the CR report when it prepared AS1.
The insurer has provided EC’s third report (EC3 ) dated 28 October 2023. To the extent that
new information was provided, EC3 attaches marked 2015, 2021 and 2022 aerial photos of
the property identifying the various sections of retaining walls. It says:
the photos show the section of crib wall to the east of the panel wall was repaired and
‘appears to have been reinstated still containing unsuitable material for drainage…’
the photos show a section of panel wall was built extending to the western side the factory
after the post 2015 panel wall construction
the shown discrepancies suggest an ongoing issue with the wall and past repair attempts
‘[e]ven if the retaining wall was constructed 50 years ago, it was constructed specifically to
prevent collapse due to excessive rainfall – particularly in the case of a crib wall…any
collapse requires the determination of the specific defect that led to the collapse. ’
it included an aerial diagram which marks a section at the eastern end of the wall
‘unrepaired bowed crib wall’ and marks the middle section as ‘repaired bowed crib wall’
the ‘section of bowed crib wall beside (east of) [the panel wall] was repaired, however it
appears to have been reinstated still containing unsuitable material for drainage causing
the collapse to simply occur beside the newly installed panel wall’
relies on photo 4 of EC3 which shows gaps in the retained soil above the collapsed wall
and marks a small section of the eastern most part of the wall ‘the undamaged crib wall’
effective reinstatement was not conducted to the full length of the damaged area.
The insurer has provided EC’s fourth report (EC4 ) dated 4 January 2024. EC4 says:
‘a section of the crib wall at which collapse occurred [in 2015] was not installed with a
concrete panel retaining wall further down the wall but was put back together as a crib
wall. This was the section that incurred collapse in 2022.’
the diagram in EC3 (from 2022 aerial view) shows the area of panel wall installed following
the 2015 collapse. The 2022 collapse has occurred immediately beside this panel wall
location
Photo 1 in EC3 ‘shows that the concrete panel wall did not previously extend down t he
side of the factory, it used to end at a location beside the carport’
‘Photo 3 (also from the 2015 report) shows that the wall had collapse d and bowed for a
greater distance down the side of the factory.’
‘photograph 2 in the 2015 [CR] report indicates the extent to which the collapse occurred. ’
Determination | Case number: 952432 Page 6 of 9
‘Given that the new concrete panel wall was not installed in front of this collapsed location
it is evident that the damaged crib wall was put back together at this location following the
2015 collapse’.
Rebuild/repair after 2015 event
The parties disagree about whether the disputed wall was repaired or rebuilt after 2015.
The insurer says the complainant rebuilt or repaired part of the disputed wall after the 2015
event. It says that not all the 2015 collapsed wall was replaced by the panel wall and that
some of the collapsed wall and some of the bowed wall (to the east of the panel wall) was
replaced and/or repaired as a crib wall. It relies on EC’s reports including EC3 ’s aerial
diagram which marks a section at the eastern end of the disputed wall: ‘the unrepaired bowed
crib wall’ and marks the western section: ‘the repaired bowed crib wall’.
However, the complainant says that it did not receive a copy of the CR report or SOW prior to
the current claim. The complainant says it did not do any repairs or rebuilding to the disputed
wall after the 2015 event. The complainant’ s marked aerial diagram provided on 27 October
2023 marks a section at the eastern end of the disputed wall: ‘8m undamaged crib wall 60
years old’ and marks the western section: ‘approx 15m collapsed crib wall after 2022 rain
event 60 years old’.
I accept that the available information does not show the CR report or SOW was provided to
the complainant.
I am not persuaded by the insurer ’s version that repairs and/or rebuilding work was done to
the disputed wall after the 2015 collapse. That is because:
EC1 does not identify the disputed wall as being repaired or rebuilt in full or part
CR says that 12m of wall collapsed in 2015. The complainant says, and the insurer does
not dispute, that the 12m panel wall was built at the location of the collapsed crib wall.
This indicates that all of the 2015 collapsed wall was replaced by the panel wall. It is noted
that the insurer’s submission of 27 October 2023 say ‘the collapsed part of the retaining
wall was rebuilt as a steel post and concrete panel wall’ and that ‘the 5 metres of the
retaining wall was observed by [CR] to have been bowing outwards. We further
understand that this section that was bowing out was not rebuilt and is noted as being
adjacent to the panel wall’
the photos provided do not show any new wall built or repaired (beyond the 12m panel
wall)
the photos do not show that the 2015 collapsed wall extended beyond where the new
panel wall was installed
it appears from EC3 and EC4 that EC reached this conclusion based on a desktop review
of photos rather than its own independent inspection. In particular, EC provides no expert
analysis of the date of materials or construction that points to post 2015 repair of the crib
wall
I am not satisfied that the photos relied upon by EC support its conclusion. That is
because the various perspectives from which the photos referred to by the insurer are
taken cannot reliably line up the collapsed wall with external markers to determine the
extent to which it was replaced by the panel wall
Photo 2 of CR’s report showing the extent of the 2015 collapse is consistent with the
complainant’s version . It appears to show that the 2015 collapse did not extend beyond
where the panel wall stands.
Determination | Case number: 952432 Page 7 of 9
What is the proximate cause of the damage to the disputed wall?
Where damage that is the subject of an insurance claim may have more than one cause, it is
necessary to determine the proximate cause of the damage. Proximate cause is the
dominant, efficient or operative cause of a loss. It is not required to be last in time or the sole
cause. It is a question of fact that depends on the circumstances of each case and an
evaluation of the evidence.
Based on the available information, I am satisfied the wall collapsed because of a build-up of
hydrostatic pressure behind the wall and that this had two interdependent proximate causes.
They were the heavy rain that fell on the weekend of 26 February 2022, together with
inadequate drainage behind the crib wall. I am satisfied the information shows that neither of
these causes, on their own, would have caused the February 2022 collapse, but rather, t hese
combined elements caused the wall to collapse.
Insurer is not entitled to rely on exclusion clauses
While I accept that an equal proximate cause of the damage to the wall was lack of drainage
leading to a build up of hydrostatic pressure, that does not, of itself, mean that the policy does
not cover the damage. Rather, the insurer bears the onus of showing that an exclusion or
other limiting factor applies that entitles it to deny the claim. I am not satisfied the insurer has
discharged that onus. That is because:
the exclusions for wear and tear, gradual deterioration and developing flaws relate to
diminution, decay or damage that is ongoing or sustained over a period of time. The
available information, including the 2015 event (which happened during an extreme rain
event), does not support a finding that the collapse was the result of ongoing or sustained
diminution, damage or other ongoing issue. While hydrostatic pressure may build up over
time, the information does not show the wall had gradually deteriorated or developed a
flaw over a sustained period. The information does not show that, but for the extreme rain
event, the damage would have occurred
the insurer has argued that the ‘policy does not provide cover due to developing flaws due
to a failure to attend to making good ’ . It is correct that the policy excludes damage caused
by developing flaws irrespective of how they occurred. However, the section does not say
the policy ‘ does not cover developing flaws due to a failure to attend to making good ’. In
fact, t he section does not refer to ‘failure to make good’ or ‘ failure to attend to making
good ’ . Rather, it says ‘it does not cover…loss…occasioned by or happening
through… making good ’ . The available information does not show that any damage was
occasioned by or happened through making good
the insurer has not shown the damage was caused by faulty workmanship. As stated
above, I am satisfied the collapsed wall was built 50 to 60 years ago and was not repaired
or rebuilt in 2015. The available information does not show the wall was not built as it was
designed or that faulty workmanship occurred in its construction
while the insurer argues the damage was caused by error or omission in design, plan or
specification or failure of design, the available information does not show the design and/or
specifications were considered erroneous or insufficient at the time the wall was designed
and/or built
the insurer has not shown that the wall collapsed due to a ‘ latent ’ defect. The Macquarie
Dictionary says the term means a fault or imperfection that is ‘present, but not visible or
apparent’. The insurer has said that the wall was defective due to lack of drainage in its
construction. I am not persuaded by this as the available information does not show that it
was defective judged by accepted building practices at the time it was built. The Australian
Standard relied upon by the insurer was not in place when the wall was built. The insurer
Determination | Case number: 952432 Page 8 of 9
has not shown any Australian Standard or manufacturer’s crib wall manual was available
and industry standard at that time
The insurer has said the complainant did not comply with the policy term to take all
reasonable precautions to prevent the loss or damage. It says it is therefore entitled to
refuse to pay the claim in accordance with s.54 (2) of the ICA. It says the complainant did
this by not rebuilding the wall in accordance with CR’s 2015 recommendation to demolish
and rebuild the wall, by rebuilding or repairing the wall in breach of Australian Standards,
and by having inadequate drainage behind the wall. However, the available evidence
does not show that the complainant received CR’s report therefore I am not satisfied the
complainant knew of its recommendations. As stated above, the insurer has not shown the
disputed wall was repaired or rebuilt. Also, the circumstances of the 2015 collapse could
reasonably have led the complainant to believe that damage was solely due to the extreme
weather event. Accordingly, I am not satisfied the complainant failed to comply with this
term of the contract and s.54 (2) of the ICA is not invoked.
2.2 Why is the outcome fair?
The outcome is fair because the insurer has not shown that exclusions apply, or that it is
otherwise entitled to decline the claim. Therefore, it is fair that the insurer covers the damage
in accordance with the policy terms and conditions.
Determination | Case number: 952432 Page 9 of 9
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.