Home / Allianz Australia / Determination 925425
Determination 925425
Denial of claim for lightning damage to underground electrical cables and conduit
Summary
The insurer declined a home insurance claim for lightning damage to underground electrical cables, saying there was no evidence of a lightning strike. AFCA found a close lightning strike likely caused the damage and required the insurer to settle the claim, covering like-for-like two-phase repairs, generator and detection costs and damaged equipment.
On the balance of probabilities, eyewitness and expert evidence showed a lightning strike very close to the premises caused the damage, which is covered and not excluded as wear and tear.
Issues
- Claim denial primary · upheld
“The insurer was not entitled to deny the claim on the information provided.”
- Claim amount dispute secondary · unclear
“Insurer not required to upgrade to three-phase; repair cost to be met like for like on a two-phase system once firm quote provided.”
- Inadequate claim investigation secondary · upheld
“Preferred complainant's experts over insurer's; LIAS reports do not provide accuracy within that range, strike could have been right next to the house.”
Subjects and remedies
home or building damagenatural disasterpay claimrepair or rectify
Text of the determination
Determination
Case number 925425
Financial firm Allianz Australia General Insurance Limited
Determination | Case number: 925425 Page 2 of 9
Case number: 925425 29 June 2023
1 Determination overview
1.1 Complaint
The complainant is represented by another party in this matter and reference to complainant
is a reference to both parties.
The complainant held a home and contents insurance policy with the financial firm (insurer).
The policy included cover for lightning. On 13 May 2022 the complainant lodged a claim for
lightning damage to his electrical cables.
The insurer denied the claim on the basis that they said there was no evidence of the
lightning strike or any insurable event under the policy.
This matter has been the subject of a preliminary view in favour of the insurer. The
complainant rejects this, and the matter has been referred for determination.
1.2 Issues and key findings
Was the insurer entitled to deny the claim?
On the information provided to me, on balance, I am satisfied as follows:
a lightning strike occurred very close to the complainant’s premises
it is likely that that lightning strike caused the damage to the electrical conduit
the tree root which had breached the cable is unlikely to have caused the damage
the carpenter working on the building noted a lightning strike in very close proximity to the
building
when he returned to the property the next day, the power was not operating
the policy provides coverage for lightning and storm but not from wear and tear and
gradual deterioration, which is excluded
The insurer was not entitled to deny the claim on the information provided. The insurer is to
settle the claim as set out in 2 hereof.
This determination is in favour of the complainant.
Why is the outcome fair?
Both parties have been given the opportunity to provide information in response to the claim.
In the circumstances I am satisfied the information provided by the complainant, on balance,
is sufficient to show that it is more likely than not that the damage to the conduit was caused
by lightning. In the circumstances it is fair that the insurer compensates the complainant.
1.3 Determination
This determination is in favour of the complainant. Upon acceptance of this determination the
insurer is to settle the claim as set out in clause 2 hereof.
Determination | Case number: 925425 Page 3 of 9
2 Reasons for determination
2.1 Was the insurer entitled to deny the claim?
Product disclosure statement (PDS)
The PDS provides as follows:
That storm and lightning are an insured event, but under general exclusions, excludes loss or
damage that is caused by or arising from:
Wear and tear, and environmental conditions
Wear and tear, gradual deterioration or fading,
rust, corrosion, oxidisation, mould, mildew or atmospheric conditions,
…
The insurer says it declined the claim, ‘ Based on the information provided, including lack of
visible evidence that the damage was the result of a lightning strike…’. The insurer states
further, ‘In this instance, the damage to the Complainant’s property w as not the result of an
insured event. ’
Expert reports
The insurer arranged for an assessor, (DM) to inspect the property on 17 May 2022.
DM stated:
the complainant says a lightning strike struck the chimney to the property on 8 May 2022
prior to lodging the claim, the insured engaged electrical contractor and service location
specialists who had dug multiple pits and a large trench
consumer mains were cut at multiple points by the electrical contractor
a carpenter working at the property was said to have seen lightning strike the brick
chimney
an inspection of the chimney showed no entry or exit points.
The report by DM also included photos of the premises including the exposed conduit
It was arranged for an electrical company (EE) to inspect the property and they provided a
report dated 17 May 2022 as follows:
Determination | Case number: 925425 Page 4 of 9
The insurer provided an Australian lightning incident archive search (LIAS). The first LIAS
document states that the closest stroke was 1.9 kilometres away which occurred on 7 May
2022 at 16:19:20 (UTC). The second LIAS search showed further information which appears
to show the closest stroke of 48.6 kilometres on 8 May 2022 at 21:08:54 (UTC) and a third
LIAS report shows that between 9 May 2022 and 10 May 2022 there were no close strokes .
The complainant obtained reports in support of their claim from a weather service, (MW) who
provided a report in response to a request from the complainant. The report stated as follows:
As mentioned in our phone conversation, it is important for an assessor to
understand the following performance/error measurements of the TOA Systems
owned lightning detection network in Australia, and in turn how to interpret the
LIAS reports.
The stated detection accuracy of the TOA System’s lightning detection network in
Australia (of which [MW] is the exclusive reseller of the resultant lightning
information), is as follows:
Cloud to ground lightning strikes have a detection accuracy of >98%, meaning 1-2
lightning strikes out of a 100 are not captured.
The stated location accuracy for cloud to ground lightning strikes is 300 metres,
using a Root Mean Square Error (RMSE) method. This does not mean that
lightning detected at distance of greater than 300 metres can be ruled out as a
cause of damage, and potentially some strikes will be misplaced by approximately
1-2km
There is also a misclassification rate of cloud to cloud lightning as cloud to ground
lightning (and vice versa of around 3-4%), which means a closely located cloud to
cloud event could have actually struck the ground or infrastructure.
Based on the information you have provided, in particularly the file labelled E
1.LIAS Report PDF and the BOM Confirmation report are supportive of lightning
occurring at the central lat/long on 7th May 2022, particularly if there were
eyewitness reports that align with the time that the closest strikes were occurring
in the 7th May 2022 LIAS report ( E 1.LIAS Report PDF). This archived BOM
radar loop from 7th May 2022 is also supportive of extensive convective (i.e.
heavy showers or thunderstorms) activity over Upper Broofiled, Queensland
during the afternoon and evening hours -
https://theweatherchaser.com/radar/IDR664/2022-05-07-00/2022-05-07-
23/Australia%2FBrisbane
Conversely, if there was no lightning detected on the day, no BOM report of
thunderstorms, and no evidence of convective activity on the radar, this would be
clearer evidence that lightning was not the cause of damage. E.g. the LIAS report
for the 9th May 2022, labelled E.3.LIAS Report PDF, is not support of lightning on
the day.
Determination | Case number: 925425 Page 5 of 9
The complainant obtained a report from electricians, (BH) who provided a report dated
9/5/2022.
…
The report from the Locate and Detection Specialists, (LA)
LA provided a job docket dated 9 May 2022 which stated as follows:
The complainant obtained a report from (AN), who commented on the report by BH and
stated:
My qualifications are:
1. Cert III cable jointer up to 33 kV plastic and paper lead
2. Cert III linesman
3. Cert III electrical.
Our company specialises in underground and overhead reticulation for low voltage and high
voltage installations. We concur with the fault review section of the BH report. Both the report
and photographs are consistent with a lightning strike. I have investigated and would like to
add the following:
(a) The fault happened underground
(b) The fault is at the top of a hill
Determination | Case number: 925425 Page 6 of 9
(c) The fault route link was approximately 180 metres from point of supply (POS)
(transformer fuses)
(d) The cable appears to be 4x16mm 1Cu (common size of this type of
installation)
(e) The transformer fuses were blown and replaced by the supply authority.
Given the distance from the fault to the POS it is unlikely that the fault current alone would be
sufficient to blow the transformer low voltage fuses. In my professional opinion, this gives
further weight to the case that the underground mains were hit by lightning which would blow
the low voltage fuses at the POS.
AN responded to the report by (EE) in a report dated 10 February which was an expansion on
a previous report.
The complainant says that the commencement of repairing the line and assessing the
damage to the electrical conduit was known to the insurer.
The complainant also has provided a witness statement by (DC) who stated as follows:
As mentioned, as we were packing up for work last Saturday (7th) there was a
huge lightning strike that looked like it hit the chimney of their house. When we
came back Sunday for work there was no power.
Insurer is not entitled to deny the claim
On the information provided, on balance, I am satisfied that there was a lightning strike very
close to the house on 7 May 2022. I have looked at the LIAS reports that have been provided
by the insurer. I note that according to those reports the nearest lightning strike is 1.2
kilometres from the premises.
I also have looked at the report from MW which shows that some lightning strikes are not
captured, albeit about two per cent but also that lightning strikes can be misplaced by one to
two kilometres.
I have taken into account the eyewitness and although the statement says that the lightning
struck the chimney, I am satisfied that lightning did not strike the chimney, as has been borne
out by the expert reports. However, I am satisfied that there was a lightning strike very close
Determination | Case number: 925425 Page 7 of 9
to the premises as the carpenters were packing up their equipment. Their mistake as to what
was actually struck, does not preclude, on balance, from accepting they experienced a very
close strike. Whilst it has not been stated that there was power to the premises at that time, I
am satisfied that it is likely there was and that when the carpenters returned the next day they
discovered that the power was out.
The report by EE contained in an email dated 28 February 2023 states as follows:
In regards to their report, given lightning takes the path of least resistance I find it
very unlikely that the entry point would be where indicated in their report. Also
given that the closest lightning strike recorded was 1.9 kilometres away this
confirms my conclusion that the damage to the cabling was not caused by
lightning.
The complainants have provided an answer to the report of MK. The complainant has
provided responses. In those responses it has been pointed out that the insurer gave the
client approval to excavate and hire generators just prior to sending MK out to view the
premises. I am satisfied that there was a view formed by the insurer’s experts that there was
not a lightning strike within 1.2km of the premises. However, I am satisfied that it would be
possible for this to have occurred without it being accurately placed on the LIAS report. I also
refer to the LA report of 9 May 2022 which contains photos indicating exactly where they say
that there was a loss signal within a metre of the house and when it was dug up it confirmed
there had been a complete blow up of cable and conduit.
Given all the information that has been provided, I am now satisfied that it is likely that there
was a lightning strike very close to the premises considering all the information and the
eyewitness report. Whilst the insurer has consistently stated that the closest lightning strike
was only within 1.2 kilometres, I am satisfied that the reports do not provide an accuracy
within that range and it is more than possible that the strike was very close to or right next to
the house. I do take note of the carpenter’s report in relation to that as they were there at the
time.
In the circumstances I am satisfied that the tree roots did not cause the damage to the
conduit and note that the conduit when breached would still have wires which were insulated
within it. Nothing has been provided that shows that they would not have continued to provide
the insulation required. I also have considered the experts from the complainant who I am
more satisfied and more convinced by than the experts provided by the insurer.
The insurer is to meet the claim under the terms and conditions of the policy.
How is the matter to be completed?
The insurer is to settle the matter under the terms and conditions of the policy. The report
from MK dated 18 May 2022 has rejected the quote provided by MP of $81,950 on the basis
that it includes upgrading the consumer mains from two-phase to three-phase power which is
not required. There was also dispute about KA quotation for $38,261.89.
MK however, did find the invoice from HP in the sum of $2,596 for connection of a generator
fair and reasonable along with the detection service amount of $1,386. There was a
provisional estimate by MK of $46,200 GST inclusive to replace consumer mains and
reinstate power to the property including builder margins. It was noted however, that once
power was reinstated further testing of appliances and internal electrical to the main dwelling
is required.
Determination | Case number: 925425 Page 8 of 9
In view of the fact that the repairs have been completed the complainant is to provide proof of
the payment of all bills and the insurer is to pay the HP and detection service costs in the sum
of $2,596 and $1,386.
In relation to the replacement of consumer mains and reinstatement of power, I note that the
$46,200 is only a provisional estimate.
The insurer is not required to upgrade the system to three-phase power. The complainant is
to provide a firm quote from the installer for the difference between the installation of the
three-phase power and the two-phase power.
The insurer is to meet the cost of the repairs for a two-phase system on a like for like basis.
The complainant is also to provide details of any damaged equipment which was because of
the lightning strike. The complainant is to provide the cost of any damaged equipment
together with proof of payment.
Payments by insurer
The insurer is to pay:
-$2,596
-$1,386
-The cost of repairs to a two-phase system as set out above
- The replacement of any damaged equipment as set out above.
All sums are to be paid within 14 days of acceptance of this determination or within 14 days of
the complainant providing the required information.
Determination | Case number: 925425 Page 9 of 9
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.