Claim declined for awning collapse on grounds of wear and tear and gradual deterioration
Text of the determination
Determination
Case number 910961
Financial firm Allianz Australia Insurance Limited
Determination | Case number: 730453 Page 1 of 11
Case number: 910961 18 May 2023
1 Determination overview
1.1 Complaint
The complainants ’ hold a home building and contents insurance policy (policy) with the
financial firm (insurer). On or about 17 April 2022, a claim was lodged for damage to the
insured building and contents due to the collapse of an awning installed above the upstairs
timber balcony.
The insurer has declined the claim. The insurer says the collapse of the awning is due long
term gradual deterioration and a loss of bond/tension of the mortar between the masonry
bricks over an extended period. Loss or damage in such circumstances is excluded under the
policy.
1.2 Issues and key findings
Is the insurer’s assessment of its liability under the claim fair ?
No. The panel is satisfied it is more likely that a significant portion of the damage claimed is
accidental damage, which is covered under the policy. The panel considers it would be unfair
to allow the insurer to exclude the damaged awning from cover. However, the panel accepts
the insurer is entitled to decline cover for the damaged piers located under the balcony. The
insurer is to settle the claim as provided in section 2.1 of this determination.
Are the complainants entitled to non-financial loss compensation (NFL)?
Yes. The insurer’s overall management of the claim has caused the complainants to
experience undue levels of stress, inconvenience and delays. The insurer is to pay the
complainant $3,000 in NFL in line with the AFCA Rules.
Why is the outcome fair?
Based on the available information, it is fair to accept a claim under the accidental damage
benefit exists. The insurer has not shown it is entitled to decline indemnity for all the damage
subject of the claim. The panel considers it would not be fair in the circumstances for the
damaged awning to be excluded from cover. However, it is reasonable for the insurer to
decline cover for the damage to the pier(s), which has not been shown to be caused by the
event.
1.3 Determination
This determination is in favour of the complainants. The insurer is to accept and settle the
claim as set out in section 2.1 of this determination.
The insurer is to pay the complainants $3,000 in NFL in line with the AFCA Rules.
Determination | Case number: 730453 Page 2 of 11
2 Reasons for determination
2.1 Is the insurer’s assessment of its liability fair?
No. The available information shows the insured property has suffered accidental loss or
damage, which triggers cover under the policy. The insurer has not shown it is more likely the
damage to the awning, wall, balcony and contents is due to circumstances excluded under
the policy.
The complainants purchased the insurer’s premium insurance product
The insurer provided the complainants with the relevant policy documentation including the
product disclosure statement (PDS) and certificate of insurance (COI). Therefore, the panel
accepts it is fair to consider the complainant having regard to the policy provisions.
The complainants purchased the insurer’s premium cover at a higher cost, which in addition
to providing cover for loss or damage due to the listed insured events, also covers accidental
loss or damage to the insured property. Cover under these benefits is subject to the
conditions, limitations and exclusions specified in the PDS.
The policy defines ‘accident’ and ‘accidental loss or damage’ as:
accident an event that happens by chance and is not expected in the normal
course of events.
accidental loss or damage loss or damage caused by an accident.
Complainants need to show the loss or damage triggers cover under the policy
The complainants are first required to show, it is more likely than not, that the loss or damage
claimed triggers cover under the policy. Only if the complainants can do this, will the duty shift
to the insurer to show, on balance, it is entitled to decline cover in line with the policy wording
or otherwise.
The available information shows the awning, installed to a masonry veneer wall, collapsed on
17 April 2022 resulting in damage to the insured property. There is no dispute that this event
was sudden and unexpected, which the panel accepts meets the policy definition for
accidental loss or damage, and which triggers cover under the policy.
Therefore, the onus rests with the insurer to show, on balance, an entitlement to decline the
claim in line with the policy provisions or otherwise. The panel notes the parties ’ differing
positions on whether it may be ‘Storm’ (wind) damage, which is discussed later in the
determination.
Consultants have provided conflicting opinions regarding the damage
The insurer appointed bu ilding consultants ‘G’ to investigate the cause and extent of the
damage. G attended the site on 21 April 2022 and says the damage had not been caused by
any event but rather appeared to be a failure of the masonry wall to which the awning had
been connected.
Engineering consultants ‘IE’ attended the insured property on 26 June 2022 to complete their
assessment. IE ’s report dated 12 July 2022, says in part:
Determination | Case number: 730453 Page 3 of 11
the awning was installed in around 2012
the complainant told IE the awning was not extended at the time of loss
the maximum wind speeds on the date of loss of loss (recorded at the three closest
weather stations) were 69km/hr, 37km/hr and 56km/hr
the collapse of the awning and masonry veneer was due to loss of bond capacity of the
mortar between bricks caused by:
- normal degradation of the mortar joints
- fatigue failure due to the vibration of the operable wall motor and fluctuation of
rotational moments on the connection due to varying wind forces on the unit when
the canopy is extended
this type of event is a sudden failure and provides no warning. Wind speeds were not
excessive, however given the existing long-term loss of mortar bond/tension, this may
have been the final contributing factor for the collapse
there was no evidence of damage to the main dwellings primary timber framed structure.
Some moisture related rotting to the timber bearers supporting the balcony was noted.
The complainants raised various concerns regarding the consultants’ reports. These included
the fact IE says the awning was not in use at the time of loss, which it was. Also, that it seems
IE has only presented a theory regarding failure of the mortar and gradual deterioration with
no supporting information.
IE responded to the concerns in a report dated 20 December 2022. IE says it is very
confident that the collapse was due to long-term deterioration of the mortar bond within the
wall under the weight of the awning. The tensile mortar capacity can be disturbed or be
reduced to zero due to degradation and wear and tear over time. IE reports that once the
mortar bond strength is reduced to zero, the parapet and awning’s stability is reliant on the
dead weight of the bricks, which proved insufficient to prevent the loss.
The complainants contacted the awning’s manufacturer ‘M’ a nd appointed its authorised
awning installation specialists ‘BB’ to investigate the cause and extent of the damage. BB
attended on 30 January 2023, and noted the collapsed awning was attached to two courses
of brickwork (the bricks being large and of solid construction). BB says the awning had been
adequately installed and that when adequately installed the awning does not cause
deterioration or weakening of mortar bonds.
BB says it did not observe any sign of mortar or other deterioration. In BB’s opinion the
awning did not collapse because of deterioration or weakening of mortar bonds over time. BB
says wind speeds over 37km/hr posed a significant risk to complainants’ awning, which is a
wind resistance class 2 awning. BB notes the maximum wind speeds recorded at the three
closest weather stations on date of loss were almost double what the awning could withstand.
In BB’s opinion , wind gusts caused the sudden uplift of wind from under the awning causing
the bricks to buckle under pressure and collapse.
M has sent an email to the complainant dated 31 January 2023, advising the awning should
be used between 28km/hr to 37km/hr wind speeds. Further, that the wind speeds recorded on
the day could have contributed to the awning being dislodged from the wall. The
manufacturer did not attend the insured property or inspect the canopy or damaged area.
Damage to piers under the balcony
The complainants say the impact and weight of the collapsed awning including approximately
30 bricks has caused damage to pier one located under the balcony. The complainants rely
on information from BB as well as engineering consultants ‘K’ in seeking cover for t he cost to
repair the pier.
Determination | Case number: 730453 Page 4 of 11
BB says the dry weight of the awning is approximately 80kg and at the time of collapse it was
secured to four bricks, each weighing 16kg each (144kg). Further, approximately 30
additional bricks fell at the same time as the awning. Given this, the total weight of the items
that collapsed onto the balcony (pier) below was approximately 624kg.
K did not attend the insured property but has provided its view on the information received
from the complainants in its report dated 17 March 2023. Regarding force of impact, K notes
the above provided weight of awning and additional bricks which fell around 2.8m. In K’s
calculations, the total load of 624kg may have had a dynamic factor of 5.1, which means that
the 624kg load falling from the 2.8m height may have had an equivalent static mass of 5.1 x
624kg = 3,182kg.
K notes from the photos that the awning did not fall vertically but at an angle, which it says
would produce a vertical component of the impact force as well as a horizontal component. K
notes the awning struck the deck approximately 1m – 1.2m away from the wall. Calculation of
possible scenarios indicate more than 90% of the impact force is determined to have acted
vertically, but between approximately 25% to 40% of the impact force will have acted
horizontally.
K says the horizontal force for the impact would primarily be in the direction of the joists, away
from the house. This would have the effect of the joists pulling on the split face blockwork
masonry piers, which would result in the top of the piers trying to pull away from the house.
Given the cracking is wider at the top of the pier, this indicates it has been pulled away from
the wall at the top by a force. The mortar is weaker than the masonry and so cracking along
the mortar line would be expected and in K’s opinion , the force of the impact caused the
damage.
The insurer disputes the damage to the pier is due to the awning collapse event and says the
movement damage to piers under the balcony existed before the event. The insurer relies on
the information from IE and says this damage is not covered under the claim. The available
information shows IE had attended the insured property under a previous claim on 8 April
2022 relating to building movement concerns and water under the home. The panel notes the
area under the balcony was assessed and photos were taken at the time.
IE notes the photos taken before and after the canopy’s collapse, shows no appreciable
difference in cracking between the second pier and external wall. Photos of the first pier,
subject of this complaint, were not taken at the time. IE says regarding the cracking to pier
one, it is more likely due to differential footing movement along with insufficient shear keying
of the pier to the main masonry veneer wall. This being consistent with the existing damage
noted to adjacent pier two on 8 April 2022.
IE refers to the fact there is clear evidence of movement and associated cracking damage to
the piers which pre-exists the awning collapse. In response to the query as to why it is only
the first two piers affected by cracking, IE says it cannot provide a concluded opinion. It may
be the case that the other piers had a better initial mortar bond to the exterior wall face. The
fact that the other piers are not as high as the first and second pier may have affected their
better performance. It says what is clear from the photos is there existed cracking between
the second pier and wall face prior to the event.
Insurer has not persuasively shown it can exclude all the damage
The panel has carefully considered all the information from the parties. The panel is not
satisfied the insurer’s assessment of its liability under the claim is consistent with the
information or fair in the circumstances.
Determination | Case number: 730453 Page 5 of 11
When considering claims/complaints of this nature, it is first necessary to establish the
proximate cause for the loss or damage claimed. In considering the proximate or effective
causes, it is necessary to consider the facts of the situation alongside the terms of the
relevant policy. The proximate cause is not the first, or the last, or the sole cause of the loss
but the effective or dominant cause of the loss. It is a question of fact to be considered in
each case.
The panel notes the insurer’s reliance on wear and tear and gradual deterioration of the
mortar between the brickwork as the basis for its decision to decline cover for the collapsed
awning and resultant damage. However, the panel is of the view the insurer has not provided
reasonably persuasive supporting information to establish wear and tear and gradual
deterioration is the dominant cause for the damage.
The panel notes both G and IE refer to wear and tear and gradual deterioration of the mortar
between the brickworks, however, the panel is of the opinion that:
neither of the consultants have provided any compelling information to establish this such
as but not limited to:
- any information regarding the materials (bricks and mortar etc.) that
establishes, on balance, they were deteriorated and/or not constructed in line
with the manufacturers’ recommendations or accepted industry practices
- that the materials had exceeded their expected service periods or exhibited
evidence of wear and tear or deterioration
- that identifies indicators of deterioration to the materials or that such indicators
were consistent with known consequences of a long-term deterioration
process
there is reference to and one photo of smooth mortar in place from where the brickwork
separated (where the awning was installed). The insurer says this proves bond failure and
therefore deterioration. However, there is nothing to say the presence of such smooth
mortar at the point of separation would not have been the same had the dominant cause
for the separation been any other event such as earthquake, storm, impact etc
there is no information or assertion by the consultants or the insurer that there are any
other areas of mortar deterioration or failure of the masonry brickwork near or anywhere
around the insured property, other than the location of the awning’s installation.
Without compelling information to the contrary, the panel is satisfied it is reasonable to accept
the single difference between the area of damage and other areas of similar construction, is
installation of the awning. The insurer does not raise any concerns with the installation of the
awning and given the information from BB, the panel accepts the awning was adequately
installed. The panel notes IE’s reference to the mech anics of the awning failure and says:
Put simply, the brickwork above the canopy’s connections to the wall had
insufficient weight and mortar bond to resist the forces imposed on the wall
through the bolts that connected the canopy to the wall.
The panel accepts this supports the presence (installation) of the awning and forces the
installation imposed on the wall is what separates the failed brickwork location from all other
areas of the insured building. Further, that had the installation been lower with more rows of
brickwork above, it is likely the damage/collapse of the awning would not have occurred as
the wall would have been able to bear the weight and forces imposed by the awning
installation.
Determination | Case number: 730453 Page 6 of 11
The panel notes reference by IE to the possibility of insufficient weight of bricks and mortar
bond but is not of the opinion this equates to wear and tear or gradual deterioration. Given
this, put simply, it is not unreasonable to accept it is not gradual deterioration or wear and tear
but the installation of the awning that resulted in the failure. As noted above, there has been
no reference to or reliance upon defective installation as a basis to decline the claim nor has
this been established in light of BB’s information.
The panel notes IE concedes that, with respect to the claimed loss of mortar bond and
resultant reduction in resistance capacity of the wall over time, it has no objective proof that
this is the case. Further, in its reports IE acknowledges and refers to other potential causes
such as use of the canopy and wind loads and acknowledges the failure will have been
sudden and unexpected.
The panel notes IE’s original assessment and therefore opinions were based on the incorrect
assumption that the awning was not in use at the time of the loss. IE reported this was based
on advice from the complainants. However, this has been shown to be inaccurate with the
complainants never advising of such and photos from shortly after the incident showing the
awning was in use at the time of the loss. The p anel also notes that IE’s re sponses to these
concerns raised about its original report were not from the consultant who completed the
assessment and report, as he had left the employment of the company.
The exclusion provisions say the policy excludes loss or damage that is predominantly
caused by or arises from wear and tear, gradual deterioration or fading. The panel is satisfied
it is fair to accept this to mean the insurer bears the onus to show it is more likely that wear
and tear and gradual deterioration are the dominant or effective cause of the awning collapse.
However, for the reasons discussed above, the panel is not satisfied the insurer has been
successful in showing wear and tear and gradual deterioration are the dominant causes for
the collapsed awning event.
Not enough information to show the damage is due to a storm
The panel has considered the parties position on whether the collapse of the awning is due to
the insured event storm. It is not in dispute that three weather stations closest to the insured
property have recorded maximum wind speeds that exceed what the awning manufacturer
says the awning is capable of weathering. However, other than this, there is no clear or
compelling information linking the awning damage to a wind event other than reference to a
possibility that this is the case.
There is no information showing any wind damage to the awning itself with the failure being
the wall where it was installed. The information shows the complainants and their guests were
playing cricket during the day and the balcony was in use for entertaining guests at the time
the awning collapsed. There is no persuasive witness information from those present to
indicate a sudden high wind gust or the impact this may or may not have had on the awning
at the time. There is no information to show the maximum recorded wind speeds occurred at
or near the time of damage.
The panel accepts the information shows awnings are susceptible to wind and depending on
the kind of awning, their capacity to operate in winds varies. Further, that it is possible that the
wind may have contributed to the damage, however, the panel is not satisfied it has been
shown that wind was the dominant or likely cause for the awning collapse. The panel is
satisfied the more likely cause and associated policy benefit to consider is accidental loss or
damage.
Determination | Case number: 730453 Page 7 of 11
Damage to pier one not covered under the claim
With respect to the damage to pier one, the panel is not satisfied this has been shown to be
due to the collapsed awning event. The panel notes the information from BB regarding the
weight of the awning and bricks as well as K’s opinions based on BB’s information . However,
the panel finds the information from IE, which completed two physical assessments of the
damage, to be more compelling.
The information from IE confirms concerns with building movement and damage to pier two
under the balcony existed before the awning collapsed. The panel notes the complainants’
view that given the absence of a photo of pier one, it is reasonable to accept there was no
damage to pier one on 8 April 2022. However, the panel is not of the same opinion and it is
not unusual for consultants to take a photo of an area to support is findings of an area as a
whole.
The damage to pier one and pier two are reasonably consistent and in the absence of
compelling information to the contrary, the panel is satisfied it is more likely the damage to
pier one also existed before the awning collapse event. Therefore, it would be unfair to
require the insurer to cover the cost to repair the claimed damage to the pier under the claim.
It is fair for the awning to be covered under the accidental damage benefit
The insurer says the damaged awning is not covered under the policy. This is because cover
under the optional accidental loss or damage benefit is subject to all the specific exclusions
that apply to each of the listed insured events, including storm. Cover under the event storm
specifically excludes cover for fabric awnings, unless professionally installed and less than
five years old. The insurer says, given the awning is over five years old, the specific exclusion
under storm applies to exclude the awning from cover.
The panel has reviewed the PDS and notes that the optional accidental loss or damage
benefit is subject to its own specific exclusions, which do not make any reference to awnings.
The panel notes in line with the PDS, cover under the optional accidental loss or damage
benefit:
is only possible if the loss or damage is not due to one of the listed insured events
is subject to all the specific exclusions that apply to the optional benefit
is subject to all the specific exclusions that apply to each of the listed insured events
is subject to all the general exclusions that apply to the policy.
The panel is satisfied that the accidental loss or damage cover is an optional benefit available
with the insurer’s premium insurance product and for which the complainants were required to
pay a higher premium. The panel believes it is reasonable to accept that in offering an
‘ optional benefit’ for a higher premium, the intention is for this optional benefit to provide a
wider scope of cover than that available under its standard contract of insurance.
The panel accepts it is not unusual that each insured event is subject to several specific
exclusions, including specific exclusions that apply to an optional benefit such as accidental
loss or damage. The panel also accepts it is standard practice for a contract of insurance to
include general exclusion provisions that apply to all sections of the contract. However, the
panel is not satisfied it is fair in the circumstances to then also apply all the specific insured
events’ exclusion s to the optional benefit, the purpose of which is to increase the level of
cover available under the contract.
The panel finds it concerning that the policy on the one hand says the optional benefit is only
available where the loss or damage is not due to one or more of the listed insured events i.e.
Determination | Case number: 730453 Page 8 of 11
is due to circumstances not covered under an insured event. But then the policy also seeks to
exclude under the optional benefit all the circumstances not covered (specific exclusions)
under the insured events in addition to the broad ranging general exclusions that also limit
cover under the optional benefit. Simply put, if the insurer’s position is to be accepted, the
optional accidental loss or damage benefit:
does not assist where loss or damage is caused by an insured event
does not assist where loss or damage is excluded by an insured event
does not assist where one or more of its own specified exclusions apply; and
does not assist where a general exclusion provision applies.
Given the above, the panel is concerned about the fairness, reasonableness and authenticity
in selling a product that is said to offer a higher level of cover (optional benefits) at a higher
premium, only to then attempt to minimize the benefit so significantly that it barely provides
any benefit at all. The panel is the opinion the insurer’s position is at the very least unfair and
at worst, selling the illusion of higher cover for a higher premium is deceptive and misleading.
Accordingly, the panel is not satisfied it would be fair to allow the insurer to decline cover for
the damaged awning in the circumstances.
Insurer is to accept and settle the claim in the following manner
In line with the matters discussed above, the panel is satisfied that it is fair that the insurer
covers the complainant for the damaged awning ($9,174.79), damaged contents ($5,600) and
the cost to repair the resultant damage to the insured property including the timber hand rail,
timber cladding, masonry cladding, box gutter, exterior wall lights etc. The insurer is not
required to cover the cost to repair the piers under the balcony.
The panel has reviewed quotes from the complainants. However, these include repairs not
covered under the policy and do not provide adequate information to assess whether they are
fair and reasonable. Accordingly, at its discretion, the insurer can:
authorise and manage the repairs to the insured building and installation of a new awning,
or alternatively
within 21 days of receiving notice of the complainants’ acceptance of this determination,
cash settle the complainants under the claim based on an actionable quote from a suitably
qualified consultant covering the cost to repair the insured building and installation of the
awning (but not the awning which is to be cash settled for $9,174.79)
In the instance the insurer elects to cash settle the claim, the insurer is to increase the final
cash settlement by a further 15% to allow for contingencies and the transfer of risk associated
with arranging the works to the complainants.
2.2 Are the complainants entitled to NFL?
Yes. The insurer is to pay the complainants $3,000 in NFL in line with the AFCA Rules.
AFCA Rules allow for and award of NFL
The Rules (Rule D 3.3) allow for an award of up to $5,400 for non-financial loss
compensation, if the insurer caused the complainants to suffer an unusual degree or extent of
inconvenience, delay or interference. AFCA takes a conservative approach when considering
any award of compensation.
Insurer is to pay the complainants $3,000
Determination | Case number: 730453 Page 9 of 11
In this instance and considering AF CA’s approach to compensation, the panel accepts the
insurer’s overall management of the claim was not been to a level expected of a professional
organisation. The panel accepts this has caused the complainants to experience
unreasonable levels of stress, anxiety, inconvenience and delays.
In particular, with respect to the insurer’s management of and app roach taken regarding the
required make safe works. The insurer did not complete the make safe works, despite the
information showing G invoiced the insurer for make safe works. IE had also made
recommendations to the insurer setting out much needed make safe works at the insured
property.
The panel acknowledges the insurer’s position that there is no requirement or obligation on it
to arrange make safe works under the policy. Rather, the policy places the responsibility on
the complainants to arrange works to mitigate further loss and to maintain the insured
property. This may be so, however, the panel accepts it is more common than not (accepted
industry practice) that the insurer will arrange the necessary and immediate make safe works.
Further, the panel notes the insurer did not clearly advise the complainants of its intention not
to arrange the make safe works. Rather, it appears the insurer kept assuring the
complainants the works would be or had been completed, which in the panel’s view inhibited
the complainant from making the required arrangements.
It is also concerning G has invoiced the insurer for works which were obviously not
completed. Further, that, on balance, the insurer failed to share with the complainants the
recommendations from IE regarding needed make safe works. This supports concerns of
poor communication by the insurer over the course of the claim and which contributed to the
unreasonable levels of stress and anxiety experienced by the complainants.
The panel is of the opinion, i t is fair and consistent with AFCA’s approach to an award of NFL,
that the insurer pays the complainants $3,000. This is to be paid within 14 days of the insurer
receiving notice of the complainants’ acceptance of this determination.
Determination | Case number: 730453 Page 10 of 11
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all the information the parties have provided.
While the parties have raised several issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
A panel determined this matter
Due to the nature of this complaint, we referred it to a panel for determination. The panel
includes:
an ombudsman
a member with significant experience in consumer advocacy
a member with extensive experience as an industry representative.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
3.2 AFCA Rules
D.3.3 An AFCA Decision Maker may decide that the Financial Firm is to compensate
the Complainant for non-financial loss:
Determination | Case number: 730453 Page 11 of 11
a) for a complaint relating to an individu al’s privacy rights - injury has occurred to
the Complainant’s feelings or humiliation has been suffered by the Complainant;
or
b) for other complaints – an unusual degree or extent of physical inconvenience,
time taken to resolve the situation or interfe rence with the Complainant’s
expectation of enjoyment or peace of mind has occurred.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.