Home / Allianz Australia / Determination 897869

Determination 897869

Insurer declined cover for first-floor floorboards damaged by water after a storm

FirmAllianz Australia
Decided2023-08-24
ProductGeneral Insurance · Home building and contents
OutcomeFor the firm
Amount awarded—
Non-financial loss—
Amount claimed$29,311
SourceAFCA PDF

Summary

The complainant claimed for storm-related water damage to first-floor floorboards, which the insurer declined. AFCA's supplementary determination found the insurer entitled to decline cover.

The complainant did not meet the onus of showing a storm damaged the floorboards, and the policy excludes water entering through openings not created by the storm, such as the defective flashing.

Issues

Subjects and remedies

home or building damagenatural disasterno remedy

Related

All Allianz Australia determinations · Find similar determinations

Text of the determination

Supplementary Determination Case number 897869 Financial firm Allianz Australia General Insurance Limited Supplementary Determination | Case number: 897869 Page 1 of 6 Case number: 897869 24 August 2023 1 Determination overview 1.1 Complaint The complainant lodged a claim on his home insurance policy with the financial firm (insurer) on or about 8 March 2022. He reported water damage following a severe storm on 27 February 2022. The insurer partially accepted the claim, including the ceiling on the ground floor living room / entryway and ceiling of the main bedroom. However, it declined cover for the rear alfresco ceiling, floorboards on the ground floor, and floorboards on the first-floor. AFCA issued a determination dated 18 May 2023. The complainant says that not all issues raised during the complaint have been dealt with by that determination. He says the determination does not address whether the insurer is entitled to decline cover for the floorboards on the first floor. The original determination is final regarding the matters determined. This supplementary determination will not deal with those matters already determined. It will only deal with the question of coverage of the floorboards on the first floor. 1.2 Issues and key findings Is the insurer entitled to decline cover for the first-floor floorboards? Yes. The information supports the insurer’s position that the damage to the first -floor floorboards is not covered under the policy. Why is the outcome fair? The outcome is fair because I do not consider the complainant has provided sufficient information to satisfy his onus that a storm event damaged the first-floor floorboards. Further, even if I was satisfied rainwater had entered the property, the policy excludes any damage from water entering the building through an opening, unless the opening was due to the storm. There is insufficient information to show a storm event caused the damage to the flashing, which is, on balance, the only possible entry point for water. This means any damage to the first-floor floorboards caused by rainwater entering the damaged flashing is excluded. It is fair for the insurer to decline cover for the first-floor floorboards. 1.3 Determination This supplementary determination is in favour of the insurer. The insurer is entitled to decline cover for the first-floor floorboards. Supplementary Determination | Case number: 897869 Page 2 of 6 2 Reasons for determination 2.1 Is the insurer entitled to decline cover for the first-floor floorboards? Yes. The information supports the insurer’s position tha t the damage to the first-floor floorboards is not covered under the policy. Insurer partially accepted claim It is accepted insurance law that the complainant carries the initial onus to establish, on the balance of probabilities (that is, more likely than not), a loss which is covered by the terms and conditions of the policy. Only if the complainant can do this, will the onus shift to the insurer to show, on balance, it is entitled to decline cover in line with the policy wording or otherwise. The policy is an ‘insured events’ policy. This means not all loss and damage is automatically covered. Rather, only loss or damage caused by one or more of the insured events, and not subject to exclusions, is covered. The product disclosure statement (PDS) outlines the insurer will cover loss or damage caused by storm, cyclone, rainwater, and run-off. This cover is subject to conditions and exclusions. This includes a specific exclusion for: rainwater, run-off, hail, wind or water that enters your buildings through an open door, window or other opening (this exclusion does not apply to openings made by the storm or cyclone, or, if you’ve selected the optional cover Accidental Damage and it is shown on your policy schedule). The insurer also refers to several general exclusions for inherent defects, and atmospheric and other climatic conditions. The insurer partially accepted the claim. However, it says the complainant has not established the storm event damaged the floorboards. The determination dated 18 May 2023 dealt with the rear alfresco ceiling, and floorboards on the ground floor. This supplementary determination only deals with whether the insurer is entitled to decline cover for the floorboards on the first floor. Complainant says damage to floorboards on first floor due to storm The complainant says:  the ceiling damage was accepted by the insurer  the ceiling on the ground floor is directly below the floorboard damage on the first floor  this shows the floorboard damage on the first floor should be approved and paid  the storm in February 2022 was the worst in history for his area and marked as a catastrophic event  prior to the storm there were no issues to the floorboards  during the complaint being at AFCA, he arranged repairs to the ground floor ceiling, and when lights were removed in the ceiling he found water damage/ water staining to the ceiling cavity Supplementary Determination | Case number: 897869 Page 3 of 6  there is photo evidence of storm related water damage to the floorboards on the first floor  floorboard installation defects are not applicable as evidence from the floorboard manufacturer and installation guidelines substantiate that the floorboards have been installed to standard  defects from outside roof flashings are not applicable as photo evidence shows water ingress from the flashings was not possible and the flashings are nowhere near the floorboard damage on the first floor  the ceiling damage was not paid on a goodwill basis, because the insurer’s building consultant found the damage to the ceiling was due to the storm. The complainant says the total cost of flooring repairs (ground floor and first floor) is $58,622. He says repairs to the floorboards on the first floor equate to $29,311. Reports do not show, on balance, a storm damaged the first-floor floorboards The insurer provided reports from its builder (MK). The report dated 22 April 2022 states: It is our professional opinion that the cause of the damage to the first-floor master bedroom is the result of the water ingress from the backing up of rainwater to the back edge of the concrete roof tile to the metal valley iron roof flashing from the observed heavy rainfall and storm activity on 27 February 2022. Our Assessor has advised the Insured that it is recommended by our office that they contact a roofing contractor to attend the property to alleviate the risk of water ingress through the metal valley iron roof flashing above the master bedroom... … Furthermore, it is our professional opinion that the cause of the damage to the ground floor open plan entryway, living room and hallway is the result of water ingress through the observed gaps openings to the apron flashing to the side elevation. This is not a storm created opening for an insurable event. The insurer provided a further response from MK dated 5 October 2022, which states it is unable to provide comment on damage to the first-floor flooring as this area was not inspected and or damage was not advised to this area at the time of assessment. It stated it would need to reattend the property to determine the extent and cause of damage. The insurer says the complainant would not allow MK to reattend to inspect the first-floor flooring. However, it says it is the same location as the ground floor ceiling, which it says was damaged due to defective flashing. The complainant provided several responses from repairers addressing the damage to the first-floor floorboards, including an invoice from his repairer (SK). The invoice states: ‘the timbers have been expanded by the humidity and the heavy rain ’. SK provided a further response dated 20 September 2022, which states the floorboards have been damaged ‘mainly due to excessive moisture level that exceeds normal weather conditions’. SK states normal levels of humidity are generally not enough to cause the entire floor to buckle up, so it: Supplementary Determination | Case number: 897869 Page 4 of 6 strongly suspects that the heavy amount of rain probably has leaked into the supporting beam, joists, or the particle boards underneath the current engineered boards, and caused the abnormal level of moisture The complainant provided a response from another repairer (TA) dated 20 September 2022, which states: ‘on the first level of the house the floating boards were recently exposed to high levels of water or high levels of moisture (this can be caused by water ingress when heavy weat her conditions)’ . The complainant also arranged a roofer (SR) to repair the roof. SR commented that its ‘educated guess’ is that hail damaged the tiles in the last few years. Whilst the complainant provided several opinions from repairers, these did not provide a persuasive view on the cause of the damage to the first-floor floorboards. For example, SK states that rain ‘probably’ leaked into the home but does not provide any further details regarding the entry point or how this damage occurred. TA’s and SR’s responses are brief and do not provide further explanation for how a storm event caused the damage to the first- floor floorboards. MK does not specifically comment on the first-floor flooring. However, I consider the report provides a persuasive opinion on the only entry point for water, being defective flashing. The report is detailed and includes photos in support. The complainant has not provided persuasive information to show there was any other entry point. The report from SR is not persuasive on this point as there is no detailed explanation for how water entered the property and no photos to support. I do not consider the complainant has provided persuasive information to show a storm event caused the damage to the first-floor floorboards. Whilst it is possible rainwater entered the property during the storm event, there is insufficient information to show this storm event caused the damage claimed. The information also shows any rainwater would have entered the property through defective flashing. Fair for the insurer to decline the claim The insurer says it partially accepted the claim for the ceilings on a goodwill basis, not because it was covered by the policy. It says acceptance of a portion of a claim, which does not fall within the scope of cover under the policy, does not oblige the insurer to accept the entire claim. I acknowledge the complainant’s submissions addressing the insurer’s partial acceptance of the claim and his belief this shows the storm damaged the floorboards above the damaged ceiling. I agree the information provided does not clearly state the insurer only partially accepted the claim on a goodwill basis. However, I do not accept this means the insurer is obliged to accept the damage to the first-floor floorboards. The onus is still on the complainant to show all damage claimed is from an insured event. I do not consider the complainant has provided sufficient information to satisfy his onus that a storm event damaged the first-floor floorboards. Further, the policy excludes any damage from water entering the building through an opening , unless the opening was due to the storm. There is insufficient information to show a storm event caused the damage to the flashing. Rather, the information from MK indicates this damage was already present. This means any damage to the first-floor floorboards caused by rainwater entering the damaged flashing is excluded. Supplementary Determination | Case number: 897869 Page 5 of 6 It is fair for the insurer to decline cover for the first-floor floorboards. Supplementary Determination | Case number: 897869 Page 6 of 6 3 Supporting information 3.1 The AFCA process AFCA’s approach is based on fairness AFCA has determined this complaint based on what is fair in all the circumstances, having regard to:  the legal principles  applicable industry codes or guidance  good industry practice  previous decisions of AFCA or its predecessor schemes (which are not binding). The respective parties have completed a full exchange of the relevant information, and each party has had the opportunity to address any issues raised. We have reviewed and considered all of the information the parties have provided. While the parties have raised a number of issues in their submissions, we have restricted this determination to the issues that are relevant to the outcome. We assess complaints on available information and circumstances AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to require third parties to give evidence. When we assess complaints, we consider:  available documents  the recollections of the parties  all relevant circumstances. We give more weight to documents created at the time the events occurred. If there are no relevant documents, we will decide what most likely occurred based on the available information. If there are conflicting recollections and these are evenly weighted, we may find that a claim cannot be established.