Insurer declined cover for first-floor floorboards damaged by water after a storm
Summary
The complainant claimed for storm-related water damage to first-floor floorboards, which the insurer declined. AFCA's supplementary determination found the insurer entitled to decline cover.
The complainant did not meet the onus of showing a storm damaged the floorboards, and the policy excludes water entering through openings not created by the storm, such as the defective flashing.
Issues
- Claim denial primary · not upheld“It is fair for the insurer to decline cover for the first-floor floorboards.”
- Product terms interpretation secondary · not upheld“policy excludes any damage from water entering the building through an opening, unless the opening was due to the storm”
Subjects and remedies
home or building damagenatural disasterno remedy
Related
All Allianz Australia determinations · Find similar determinations
Text of the determination
Supplementary Determination
Case number 897869
Financial firm Allianz Australia General Insurance Limited
Supplementary Determination | Case number: 897869 Page 1 of 6
Case number: 897869 24 August 2023
1 Determination overview
1.1 Complaint
The complainant lodged a claim on his home insurance policy with the financial firm (insurer)
on or about 8 March 2022. He reported water damage following a severe storm on 27
February 2022.
The insurer partially accepted the claim, including the ceiling on the ground floor living room /
entryway and ceiling of the main bedroom. However, it declined cover for the rear alfresco
ceiling, floorboards on the ground floor, and floorboards on the first-floor.
AFCA issued a determination dated 18 May 2023. The complainant says that not all issues
raised during the complaint have been dealt with by that determination. He says the
determination does not address whether the insurer is entitled to decline cover for the
floorboards on the first floor.
The original determination is final regarding the matters determined. This supplementary
determination will not deal with those matters already determined. It will only deal with the
question of coverage of the floorboards on the first floor.
1.2 Issues and key findings
Is the insurer entitled to decline cover for the first-floor floorboards?
Yes. The information supports the insurer’s position that the damage to the first -floor
floorboards is not covered under the policy.
Why is the outcome fair?
The outcome is fair because I do not consider the complainant has provided sufficient
information to satisfy his onus that a storm event damaged the first-floor floorboards.
Further, even if I was satisfied rainwater had entered the property, the policy excludes any
damage from water entering the building through an opening, unless the opening was due to
the storm. There is insufficient information to show a storm event caused the damage to the
flashing, which is, on balance, the only possible entry point for water. This means any
damage to the first-floor floorboards caused by rainwater entering the damaged flashing is
excluded.
It is fair for the insurer to decline cover for the first-floor floorboards.
1.3 Determination
This supplementary determination is in favour of the insurer.
The insurer is entitled to decline cover for the first-floor floorboards.
Supplementary Determination | Case number: 897869 Page 2 of 6
2 Reasons for determination
2.1 Is the insurer entitled to decline cover for the first-floor
floorboards?
Yes. The information supports the insurer’s position tha t the damage to the first-floor
floorboards is not covered under the policy.
Insurer partially accepted claim
It is accepted insurance law that the complainant carries the initial onus to establish, on the
balance of probabilities (that is, more likely than not), a loss which is covered by the terms
and conditions of the policy.
Only if the complainant can do this, will the onus shift to the insurer to show, on balance, it is
entitled to decline cover in line with the policy wording or otherwise.
The policy is an ‘insured events’ policy. This means not all loss and damage is automatically
covered. Rather, only loss or damage caused by one or more of the insured events, and not
subject to exclusions, is covered.
The product disclosure statement (PDS) outlines the insurer will cover loss or damage
caused by storm, cyclone, rainwater, and run-off.
This cover is subject to conditions and exclusions. This includes a specific exclusion for:
rainwater, run-off, hail, wind or water that enters your buildings through an open
door, window or other opening (this exclusion does not apply to openings made
by the storm or cyclone, or, if you’ve selected the optional cover Accidental
Damage and it is shown on your policy schedule).
The insurer also refers to several general exclusions for inherent defects, and atmospheric
and other climatic conditions.
The insurer partially accepted the claim. However, it says the complainant has not
established the storm event damaged the floorboards. The determination dated 18 May 2023
dealt with the rear alfresco ceiling, and floorboards on the ground floor.
This supplementary determination only deals with whether the insurer is entitled to decline
cover for the floorboards on the first floor.
Complainant says damage to floorboards on first floor due to storm
The complainant says:
the ceiling damage was accepted by the insurer
the ceiling on the ground floor is directly below the floorboard damage on the first floor
this shows the floorboard damage on the first floor should be approved and paid
the storm in February 2022 was the worst in history for his area and marked as a
catastrophic event
prior to the storm there were no issues to the floorboards
during the complaint being at AFCA, he arranged repairs to the ground floor ceiling, and
when lights were removed in the ceiling he found water damage/ water staining to the
ceiling cavity
Supplementary Determination | Case number: 897869 Page 3 of 6
there is photo evidence of storm related water damage to the floorboards on the first floor
floorboard installation defects are not applicable as evidence from the floorboard
manufacturer and installation guidelines substantiate that the floorboards have been
installed to standard
defects from outside roof flashings are not applicable as photo evidence shows water
ingress from the flashings was not possible and the flashings are nowhere near the
floorboard damage on the first floor
the ceiling damage was not paid on a goodwill basis, because the insurer’s building
consultant found the damage to the ceiling was due to the storm.
The complainant says the total cost of flooring repairs (ground floor and first floor) is $58,622.
He says repairs to the floorboards on the first floor equate to $29,311.
Reports do not show, on balance, a storm damaged the first-floor floorboards
The insurer provided reports from its builder (MK). The report dated 22 April 2022 states:
It is our professional opinion that the cause of the damage to the first-floor master
bedroom is the result of the water ingress from the backing up of rainwater to the
back edge of the concrete roof tile to the metal valley iron roof flashing from the
observed heavy rainfall and storm activity on 27 February 2022.
Our Assessor has advised the Insured that it is recommended by our office that
they contact a roofing contractor to attend the property to alleviate the risk of
water ingress through the metal valley iron roof flashing above the master
bedroom...
…
Furthermore, it is our professional opinion that the cause of the damage to the
ground floor open plan entryway, living room and hallway is the result of water
ingress through the observed gaps openings to the apron flashing to the side
elevation. This is not a storm created opening for an insurable event.
The insurer provided a further response from MK dated 5 October 2022, which states it is
unable to provide comment on damage to the first-floor flooring as this area was not
inspected and or damage was not advised to this area at the time of assessment. It stated it
would need to reattend the property to determine the extent and cause of damage.
The insurer says the complainant would not allow MK to reattend to inspect the first-floor
flooring. However, it says it is the same location as the ground floor ceiling, which it says was
damaged due to defective flashing.
The complainant provided several responses from repairers addressing the damage to the
first-floor floorboards, including an invoice from his repairer (SK). The invoice states: ‘the
timbers have been expanded by the humidity and the heavy rain ’.
SK provided a further response dated 20 September 2022, which states the floorboards have
been damaged ‘mainly due to excessive moisture level that exceeds normal weather
conditions’. SK states normal levels of humidity are generally not enough to cause the entire
floor to buckle up, so it:
Supplementary Determination | Case number: 897869 Page 4 of 6
strongly suspects that the heavy amount of rain probably has leaked into the
supporting beam, joists, or the particle boards underneath the current engineered
boards, and caused the abnormal level of moisture
The complainant provided a response from another repairer (TA) dated 20 September 2022,
which states: ‘on the first level of the house the floating boards were recently exposed to high
levels of water or high levels of moisture (this can be caused by water ingress when heavy
weat her conditions)’ .
The complainant also arranged a roofer (SR) to repair the roof. SR commented that its
‘educated guess’ is that hail damaged the tiles in the last few years.
Whilst the complainant provided several opinions from repairers, these did not provide a
persuasive view on the cause of the damage to the first-floor floorboards. For example, SK
states that rain ‘probably’ leaked into the home but does not provide any further details
regarding the entry point or how this damage occurred. TA’s and SR’s responses are brief
and do not provide further explanation for how a storm event caused the damage to the first-
floor floorboards.
MK does not specifically comment on the first-floor flooring. However, I consider the report
provides a persuasive opinion on the only entry point for water, being defective flashing. The
report is detailed and includes photos in support. The complainant has not provided
persuasive information to show there was any other entry point. The report from SR is not
persuasive on this point as there is no detailed explanation for how water entered the
property and no photos to support.
I do not consider the complainant has provided persuasive information to show a storm event
caused the damage to the first-floor floorboards. Whilst it is possible rainwater entered the
property during the storm event, there is insufficient information to show this storm event
caused the damage claimed. The information also shows any rainwater would have entered
the property through defective flashing.
Fair for the insurer to decline the claim
The insurer says it partially accepted the claim for the ceilings on a goodwill basis, not
because it was covered by the policy. It says acceptance of a portion of a claim, which does
not fall within the scope of cover under the policy, does not oblige the insurer to accept the
entire claim.
I acknowledge the complainant’s submissions addressing the insurer’s partial acceptance of
the claim and his belief this shows the storm damaged the floorboards above the damaged
ceiling. I agree the information provided does not clearly state the insurer only partially
accepted the claim on a goodwill basis. However, I do not accept this means the insurer is
obliged to accept the damage to the first-floor floorboards. The onus is still on the
complainant to show all damage claimed is from an insured event.
I do not consider the complainant has provided sufficient information to satisfy his onus that a
storm event damaged the first-floor floorboards.
Further, the policy excludes any damage from water entering the building through an opening ,
unless the opening was due to the storm. There is insufficient information to show a storm
event caused the damage to the flashing. Rather, the information from MK indicates this
damage was already present. This means any damage to the first-floor floorboards caused by
rainwater entering the damaged flashing is excluded.
Supplementary Determination | Case number: 897869 Page 5 of 6
It is fair for the insurer to decline cover for the first-floor floorboards.
Supplementary Determination | Case number: 897869 Page 6 of 6
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.