Home / IAG / Determination 857819
Determination 857819
Claim denial for earthquake cracking damage to bathroom and external bathroom wall
Summary
The complainant claimed earthquake damage to his bathroom and external bathroom wall, which the insurer denied as caused by long-term settlement. AFCA decided the bathroom and external wall damage was caused by the earthquake and must be accepted, with the insurer entitled to deny other damage.
The complainant met the onus of showing a prima facie earthquake claim, and the insurer did not show that any policy exclusion applied to the bathroom and external wall damage.
Issues
- Claim denial primary · upheld“The insurer is not entitled to deny the claim in full and must accept the internal bathroom damage and external bathroom wall damage.”
- Inadequate claim investigation secondary · unclear“ME is silent on if there are any specific characteristics of the internal bathroom and external bathroom wall cracks indicating whether they are pre-existing or not.”
Subjects and remedies
home or building damagenatural disasterpay claimreassess claim
Related
Text of the determination
Determination
Case number 857819
Financial firm Insurance Manufacturers of Australia Pty Ltd
Case number: 857819 10 August 2022
Determination | Case number: 857819 Page 2 of 9
1 Determination overview
1.1 Complaint
On 24 September 2021 the complainant lodged a claim with the financial firm (insurer) for
cracking damage to his property. The complainant says there are cracks in the bathroom and
to the external brickwork outside the bathroom. He says these are new cracks and were
caused by an earthquake on 22 September 2021.
The insurer assessed the damage and denied the claim. The insurer says the claimed
damage was not caused by the earthquake. It says it was not caused by a single event and
was instead caused by long term settlement and ground movement which is excluded by the
policy.
The complainant accepts there was some cracking damage to the property prior to the
earthquake.
1.2 Issues and key findings
Is the insurer entitled to deny the claim?
Partially. The insurer is not entitled to deny the claim in full and must accept the internal
bathroom damage and external bathroom wall damage. The insurer is entitled to deny the
other damage to the property.
Why is the outcome fair?
The outcome is fair because the available information shows it is more likely the damage to
the bathroom and the external bathroom wall was caused by the earthquake than by an
excluded cause. Therefore, the complainant has met his onus to show this damage was
caused by the earthquake and the insurer has not met its onus to show it is entitled to deny
the claim. In such circumstances, it would be unfair for the insurer to be able to deny the
claim for this damage.
The remaining damage to the property was most likely not caused by the earthquake and
therefore it is fair for the insurer to be entitled to deny the claim for this damage.
1.3 Determination
This determination is substantially in favour of the complainant.
The insurer is required to accept the claim for the damage to the bathroom and the external
bathroom wall. The insurer is required to settle this damage as per the policy terms by either
arranging the repairs or cash settling. If the insurer chooses to cash settle the claim the
settlement is required to be calculated in accordance with this determination.
The insurer is entitled to deny any damage to the property other than the damage to the
bathroom and the external bathroom wall.
Determination | Case number: 857819 Page 3 of 9
2 Reasons for determination
2.1 Is the insurer entitled to deny the claim?
Partially. The insurer is not entitled to deny the claim in full and must accept the internal
bathroom damage and external bathroom wall damage. The insurer is entitled to deny the
other damage to the property.
Complainant must show a prima facie claim
The onus is on the complainant to show, on the balance of probabilities, a claim within the
terms of the policy. This is commonly called a prima facie claim. Once shown the onus
transfers to the insurer to show, on the balance of probabilities, it is entitled to:
rely on a condition or an exclusion contained within the policy to refuse the claim
otherwise deny the claim.
The complainant’s policy provides cover for loss or damage caused by an earthquake.
There is no dispute there was an earthquake on 22 September 2021.
Complainant says earthquake caused bathroom and external wall damage
The complainant accepts there was some cracking to the property prior to the earthquake.
However, he says the claimed damage to the bathroom (internally and to the external wall)
was not there prior to the earthquake. He says this damage was caused by the earthquake.
Insurer’s builder says bathroom and external wall cracks are not pre -existing
The insurer arranged for a builder (JO) to assess the damage and provide a report (see 3.2
below). JO says:
there are damages to the bathroom and to the external bathroom wall
the earthquake may have caused the damages
there were no other signs of pre-existing damages to the claimed areas
given the lack of debris in the external cracking it appears it has not occurred over a long
period of time.
JO is clear the bathroom and external wall cracks are not pre-existing.
JO’s comments in its report are consistent with the complainant’s position the internal
bathroom damage and external bathroom wall damage was not pre-existing and was caused
by the earthquake.
JO recommended marking the claim as ‘UNSURE’. However, this was not because JO was
unsure of the cause instead, it was because an engineer was required to assess if there was
any structural damage.
Insurer’s engi neer says damage is caused by long-term factors
The insurer appointed an engineer (ME) to assess the damage and provide a report (see 3.2
below). ME says:
there are patterns of settlement towards southeast and northwest corners of the house
typical of damage caused by long-term differential footing movements in reactive
foundation soils
the long-term differential footing movement was caused by:
Determination | Case number: 857819 Page 4 of 9
> long-term tree root drying due to trees located close to the house
> normal seasonal and climatic effects, increased by the nearby trees
> poor site drainage due to lack of impermeable paving around the full perimeter of the
house
the likely Modified Mercalli (MM) intensity would be MM IV (light)
at MM IV the earthquake will be felt, doors and windows will be disturbed, and walls will
make a cracking sound
the observed damage to the house is ‘non - structural’ and no structural damage was
observed
the earthquake did not cause the observed damage and it was instead caused by several
long-term factors.
Relevantly, while ME says the earthquake did not cause the observed damage this view is
primarily reached based on the floor level survey and overall patterns of damage. ME is silent
on if there are any specific characteristics of the internal bathroom and external bathroom wall
cracks indicating whether they are pre-existing or not.
Trees likely caused movement to north west and south east of the property
The floor level survey completed by ME shows a datum (fixed starting point) located
approximately in the middle of the property.
The floor level survey shows the north west and south east corners of the property have
dropped relative to the datum. It also shows the property is relatively level from the north east
corner through the middle of the property to the south west corner.
The available information shows there are trees to the north west and south east of the
property.
I am satisfied, on balance, the floor level survey supports ME’s opinion the trees have
contributed to the movement in the north west and south east corners of the property.
Other causes suggested by ME are not persuasive
I am not persuaded by either of the other two possible causes of the movement suggested by
ME.
No information has been provided by ME to explain what the seasonal and climatic effects
referred to are. It is unclear if ME is suggesting the climate has been wetter or dryer than
usual. This is relevant because, as ME says, ‘ an increase in moisture content causes [highly
reactive clay] soil to swe ll and a decrease in moisture content causes the soil to shrink’. It is
therefore important to know if ME is suggesting the climate has been wetter or dryer than
usual as this will impact the direction of any foundation movement caused by seasonal and
climatic effects.
No information (including photographs) have been provided of the paving around the property
to show it is impermeable. This cause also appears to contradict one of the other main
causes suggested by ME (the drying effect of trees). Poor drainage would likely result in a
higher moisture content in the soil. Based on ME’s statements about highly reactive clay soil
this would then swell. This is in direct opposition to the effect trees would have. It is also
unclear where ME says this effect has occurred.
Determination | Case number: 857819 Page 5 of 9
Modified Mercalli intensity scale is useful but not the only relevant factor
The MM intensity scale is useful to estimate the expected effect of an earthquake at a
location however, it does not consider the specifics of the subject building.
While an MM of IV indicates a lower likelihood of damage, property specific information such
as that provided by the complainant, JO, and ME is a key component in determining if a
property suffered earthquake damage.
The MM intensity scale is useful, but it is not the only relevant factor to consider. I am not
satisfied a low MM intensity is sufficient to rule out earthquake damage on its own.
Earthquake caused the bathroom and external wall damage
For the reasons set out above, I am satisfied there is differential foundation movement to the
north west and south east corners of the property. I am satisfied, on balance, the drying effect
of trees caused this movement.
The available information, particularly the floor level survey, does not support there being
differential movement within the bathroom. I acknowledge there is a 6mm rise in floor level in
the middle of the bathroom. However, this is a relatively small rise and the floor may have
been constructed this way, the rise may be present to allow for the drainage of water, or for
some other reason.
I am satisfied the available information, on balance, shows the internal damage to the
bathroom and the damage to the external bathroom wall was not caused by differential
movement of the foundations.
Insurer has not shown exclusions apply to bathroom and external wall damage
The insurer has relied on multiple exclusions to deny the claim in addition to saying the
damage was not caused by the earthquake. The exclusions relied on by the insurer relate to:
gradual deterioration and wear and tear
atmospheric conditions or extreme temperature
tree roots
settling, shrinkage or expansion in buildings, foundations, walls, or pavements
claims arising from incidents outside the policy period
faulty design or workmanship.
I am not satisfied any of the exclusions relied on by the insurer apply to entitle it to deny the
internal damage to the bathroom and the damage to the external bathroom wall. I am
satisfied the insurer can deny all other damage to the property because I am not satisfied it
was caused by the earthquake.
An earthquake is not gradual deterioration or wear and tear, an atmospheric condition or
extreme temperature, or tree roots therefore the exclusions relating to these causes do not
apply.
The available information does not show the claimed damage to the bathroom and external
wall was caused by settling, shrinkage or expansion. Typically, an earthquake causes
shaking, this is not settling, shrinkage or expansion.
The earthquake occurred during the policy period. Neither JO or ME refer to any faulty design
or workmanship. Therefore, these exclusions do not apply.
Determination | Case number: 857819 Page 6 of 9
Insurer is required to settle as per policy terms
The insurer is required to accept the claim for the internal damage to the bathroom and the
damage to the external bathroom wall and settle as per the policy terms.
The policy gives the insurer the choice in how to settle the claim (arrange repairs or cash
settle).
The current scope of works (SOW) provided by JO says:
Please note: [JO] recommend partial cash settlement as we are unable to warrant
works to the bathroom. If [JO] were to provide a warrantable outcome, we would
need to complete a whole bathroom scope as we cannot confirm if the cracking
has affected the waterproof membrane.
Based on this I am not satisfied the current SOW is complete nor that the quote provided by
JO is actionable.
Therefore, the insurer is required to obtain an updated SOW.
If the insurer choses to cash settle the claim, the insurer is required to obtain an actionable
quote based on the updated SOW upon which to base the cash settlement.
The insurer is also required to add 20% to the actionable quote to allow for any variations to
the repairs, the loss of the lifetime guarantee on the repairs provided by the insurer, and the
inconvenience to the complainant of having to arrange his own repairs.
2.2 Why is the outcome fair?
The outcome is fair because the available information shows it is more likely the damage to
the bathroom and the external bathroom wall was caused by the earthquake than by an
excluded cause. Therefore, the complainant has met his onus to show this damage was
caused by the earthquake and the insurer has not met its onus to show it is entitled to deny
the claim. In such circumstances, it would be unfair for the insurer to be able to deny the
claim for this damage.
The remaining damage to the property was most likely not caused by the earthquake and
therefore it is fair for the insurer to be entitled to deny the claim for this damage.
Determination | Case number: 857819 Page 7 of 9
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
3.2 Relevant expert reports
Builder (JO)
CAUSE OF DAM AGE
During our inspection of the property we noted damages to the bathroom and to
the external bathroom wall. There was a section of cornice along one wall and
tiles around the bath hob that had separated from the wall, there was a small
crack in the wall above the doorway as well as cracking to a large section of the
mortar along the external brickwork. It appears these damages may have been
caused due to the recent earthquake event in Victoria. We noted no other signs of
pre-existing damages to the claimed areas and given the lack of debris in the
external cracking it appears it has not occurred over a long period of time.
Determination | Case number: 857819 Page 8 of 9
Due to the circumstances surrounding this claim we are marking it "UNSURE" as
the damages appear to have been caused due to the recent earthquake event
however given that damages to the external brickwork have been noted we
recommend an engineer attend the property and assess the extent of any
structural damages.
Engineer (ME)
3.2 External
Stepped diagonal cracking to brick wall at northern side of the house
3.3 Internal
Diagonal crack above doorway at eastern side of Dining
Cracking at junction of bathtub and wall at eastern side of Bathroom
Gap between cornice and wall at eastern side of Bathroom
Cracking to tile joint of Bathroom floor
4.0 Floor Level Survey Results
4.1 …
An arbitrary datum was selected at the central region of the house
and is denoted '0Dat' on the contour map.
The floor levels vary from +6rnm to -26mm relative to the arbitrary
zero, giving a total variance in levels across the entire floor of 32mm.
There are relative patterns of settlement towards southeast and
northwest corners of the house.
5.0 Discussion
5.1 …
5.2 … The subject site is located approximately 140 km from the epicentre of
the earthquake.
5.3 An isoseismal map … shows the Modified Mercalli (MM) values
experienced in zones around the epicentre of the earthquake on 22
September 2021 …
5.4 Based on the isoseismal map, likely intensity at the subject site would be
MMIV during the earthquake event … This intensity is described as
follows:
" MM IV - Light Shaking Felt indoors by many, outdoors by few during
the day. At night, some awakened. Dishes, windows, doors disturbed;
walls make cracking sound. Sensation like heavy truck striking building.
Standing motor cars rocked noticeably."
5.5 Based on [ME]'s visual observation of the damage throughout the house,
it is [ME]'s opinion that the damage is not attributable to the earthquake
event. This statement is made for the following reasons:
1) The location and the pattern of cracking observed throughout the
subject house is typical of damage caused by long term differential
Determination | Case number: 857819 Page 9 of 9
footing movements in reactive foundation soils … [ME] expects
highly reactive CLAY foundation soil … at the subject site … An
increase in moisture content causes [highly reactive clay] soil to
swell and a decrease in moisture content causes the soil to shrink.
In this case, the floor level survey indicates patterns of relative
settlement towards southeast and northwest corners of the house,
which are in general direction towards trees that are located in
close proximity to the house. Therefore, it is [ME]'s opinion that the
damage has occurred due to long term footing movements
associated with differential variations in the moisture contents of
the reactive foundation soils due to combination of the following
factors:
o Long term tree root drying due to numerous trees located in
close proximity to the subject house.
o Normal seasonal and climatic effects, amplified by the nearby
trees.
o Poor site drainage characteristics due to lack of impermeable
paving around the full perimeter of the house.
2) The MM scale suggests that slight to moderate damage in well-built
ordinary structures commences with intensity MMVII ("Damage
negligible in buildings of good design and construction,: slight to
moderate in well-built ordinary structures; considerable damage in
poorly built or badly designed structures; some chimneys broken").
Therefore. an earthquake intensity of MMIV would not be expected
to cause any structural distress.
6.0 Conclusion
6.1 The observed damage to the house is considered to be ‘non - structural’
damage only and no structural damage was observed.
6.2 Based on the available evidence, and within a reasonable degree of
engineering probability, it is [ME]'s opinion that the earthquake Event did
not cause, nor contribute to, the observed damage to the subject
building.
6.3 It is [ME]'s opinion that the observed damage throughout the house has
been caused by several long term contributing factors as discussed in
paragraph 5.5 of this report.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.