Claim declined for ensuite damage caused by missing puddle flange; resultant ceiling damage accepted
Text of the determination
Determination
Case number 840614
Financial firm XL Insurance Company Se
Determination | Case number: 840614 Page 1 of 8
Case number: 840614 22 February 2022
1 Determination overview
1.1 Complaint
The complainant is a beneficiary under a residential strata policy held with the financial firm
(insurer). He lodged a claim for damage to his ensuite and downstairs ceiling. He says the
waterproofing in the ensuite was compromised, resulting in a leak through the floor and into
the ceiling.
The insurer says the damage is due to a gradual release of water and liquid over time due to:
faulty workmanship
a construction flaw, and
failure to comply with Australian Building Standards with the installation of a puddle flange.
The complainant says the property was built in line with the relevant building codes. He also
says the leak was not gradual. He wants the insurer to accept the claim.
1.2 Issues and key findings
Is the insurer entitled to decline the claim?
The insurer is entitled to decline cover for the damage to the bathroom. However, the insurer
has accepted resultant damage to the ceiling in line with its assessor‟s quote. It is fair for the
insurer to limit its liability to the resultant damage to the ceiling.
Why is the outcome fair?
The information provided shows, on balance, the damage is due to a defect and/or defective
workmanship. As this cause of damage is excluded, it would not be fair to require the insurer
to accept cover for the bathroom. It is fair for the insurer to limit its liability for the resultant
damage accepted under the claim.
1.3 Determination
This determination is in favour of the insurer.
Other than the resultant damage to the ceiling, the insurer is not required to accept the claim.
Determination | Case number: 840614 Page 2 of 8
2 Reasons for determination
2.1 Is the insurer entitled to decline the claim?
The insurer is entitled to decline cover for the damage to the bathroom. However, the insurer
has accepted resultant damage to the ceiling in line with its assessor‟s quote. It is fai r for the
insurer to limit its liability to the resultant damage to the ceiling.
Policy covers accidental loss or damage, subject to exclusions
The initial onus is with the complainant to establish the loss is covered by the policy. This is
known as a valid (or prima facie ) claim.
Once the complainant has established a valid claim, the onus shifts to the insurer to establish,
on balance, the application of a policy exclusion or that it is otherwise entitled to decline the
claim under the policy.
The policy covers accidental loss or damage to the property. The product disclosure
statement (PDS) defines loss or damage as:
direct physical loss of, destruction of, or damage to property from any sudden and
accidental cause not otherwise excluded by this Policy.
Relevant sections of the PDS are included in section 3.2 of this determination.
Information shows cause of damage was lack of puddle flange to shower
The complainant provided a report from his plumber, B, dated 21 September 2021, which
states:
I performed a pressure test to the shower and found no leaks.
I visually inspected the shower base and found the grout, tiles and silicon to be
sound.
I removed the shower grate and inspected the waste outlet. I found that there
wasn‟t a puddle flange installed to connect the pvc pipe shower waste to the
flooring.
I ran water down the waste and found it to be leaking immediately. It appears that
the 50mm pvc wastepipe is simply penetrating the floor and then waterproofed
down into it. The movement in the pipe has caused the waterproofing at this point
to crack and come away, allowing water through.
I believe a property of this age should have had a puddle flange installed originally
to satisfy plumbing and waterproofing codes.
The insurer appointed an assessor (CC) t o attend the property. CC‟s report dated 8 October
2021 states:
The sighted damage to the ground floor ceiling is a result of a missing puddle
flange to the upstairs ensuite shower recess.
The plumber has confirmed that a puddle flange should have been installed as
per building codes at the time of construction.
Determination | Case number: 840614 Page 3 of 8
Owners repairs - To replace the puddle flange to the ensuite area, the ensuite
area has to be dismantled to ensure adequate waterproofing as per building
codes.
CC provided a further email, which states:
A puddle flange is used during construction to create a waterproof seal around a
pipe which passes through concrete. In this case, a puddle flange was not
installed so when general movement has occurred the waterproofing has been
disturbed, causing cracks, which is allowing the water to leak at this point. If a
puddle flange had been installed, this would encase the pipe, and create an extra
barrier around the pipe preventing this leak from occurring.
Based on the expert reports provided, I am satisfied the cause of damage was a leak from the
shower recess due to the lack of a puddle flange.
Complainant wants the insurer to accept the damage to his bathroom
The complainant says:
B noted the waterproofing was compromised and said new builds have puddle flanges
which would have stopped the leak as a backup
the insurer‟s assessor agreed the waterproofing had been compromised and also agreed a
puddle flange would have acted as a backup
neither his plumber nor the assessor suggested it was a slow leak, in fact both suggested
it was an immediate compromise of the waterproofing and not gradual
he does not consider a puddle flange was required under the building code when the
property was built
either way, he should still be covered under the policy because i t was „an immediate issue
and not a gradual leak‟
he also says it would be considered a building defect rather than faulty workmanship,
which means it should be covered.
The complainant also raised concerns with the insurer‟s reliance on the building codes
supplied. He says Australian Standard (AS) 3740 part 5.12.2 does not state all wet areas
„must‟ have the drainage flange. He says the bathroom was constructed in accordance with
this AS and the puddle flange at the time the property was constructed in 2007 was optional.
The insurer says the cause of damage is excluded
The insurer provided copies of the relevant building codes. This included Australian Standard
(AS) 3740 – Waterproofing of wet areas within residential buildings. This came into effect in
200 4, prior to the construction of the complainant‟s property . The AS states:
5.12 MEMBRANE TO DRAINAGE CONNECTION
…
5.12.2 Other floors
For membrane drainage connections in other floors, any one of the following shall
apply:
(a) The drainage riser shall be fixed to the floor substrate and the waterproofing
membrane terminated a minimum of 20 mm into the riser.
Determination | Case number: 840614 Page 4 of 8
(b) A drainage flange shall be installed with the waterproofing membrane
terminated at/in the drainage flange to provide a waterproof connection (see
Figure 5.10).
NOTE: Drainage flanges may be set into the floor or fixed to the top surface of the
floor substrate or tile bed.
(c) Where a prefabricated shower tray is used, provision shall be made to drain
the tile bed and provide a waterproof connection to the drain.
The insurer also provided reports from its building consultant (M). Relevant sections are
included in section 3.3 of this determination. The insurer says the reports show why the lack
of a puddle flange to the floor waste fixture of the bathroom is a failure to comply with the
Building Code of Australia 2004 (BCA) and AS 3740 at the time of construction.
The insurer says there is nothing to suggest the drain was fixed to the substrate. It says B‟s
report states it appears the waste pipe is simply penetrating the floor and that the movement
in the pipe has caused the waterproofing to crack and come away.
The insurer says the failure to install a puddle flange at the time of the build is the result of
faulty workmanship and/or a construction flaw/defect which is specifically excluded from cover
under the policy. It says this failure to install a puddle flange directly caused the loss, as had it
been installed it would have prevented leakage.
The insurer declined the claim to the bathroom. However, it agreed to accept resultant
damage to the ceiling. Based on CC‟s report, it stated once the complainant arranged
maintenance works to the bathroom, it would authorise reinstatement works as quoted for
$1,659.90.
Information shows cause of damage is a defect and/or defective workmanship
I have considered the complainant‟s submissions. He says photographs show the pipe is
clearly fixed to the floor base. He provided his opinion on why he considers the construction
of the bathroom complied with relevant building codes when constructed.
However, having reviewed all the available information, I am persuaded by M‟s reports.
These reports are logical and supported by the available information. The information
indicates the shower was not constructed in accordance with the relevant building codes. M
refers to B‟s findings that the pipe had moved, which indicates it was not fixed to the subst rate
as required.
The complainant has not provided any persuasive evidence to challenge these findings. The
photograph the complainant provided is not persuasive.
I am satisfied the lack of a puddle flange constitutes a defect and/or defective workmanship
under the policy.
The policy covers damage from any sudden and accidental cause. However, even if I was
satisfied the complainant had established a valid claim for accidental damage, the available
cover is subject to any applicable exclusions. I am satisfied the cause of damage is excluded
in this instance. This means it is fair for the insurer to decline cover for the repairs to the
bathroom.
The insurer appears to have accepted the resultant damage to the ceiling in line with CC‟s
report. I consider this to be fair in the circumstances. I accept the insurer is not liable to
Determination | Case number: 840614 Page 5 of 8
conduct repairs to the ceiling until the complainant has undertaken the maintenance works
required.
Determination | Case number: 840614 Page 6 of 8
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
3.2 Relevant sections of the PDS:
1) We will not pay for Loss or Damage:
…
c) caused by moths, termites or other insects, vermin, mice, rats, rust or
oxidisation, mildew mould, contamination or pollution, wet or dry rot, corrosion,
gradual corrosion or deterioration, change in colour, dampness of atmosphere or
other variations in temperature, evaporation, disease, inherent vice or latent
defect, loss of weight, change in texture or finish or pecking, biting, chewing or
scratching by birds or animals;
d) caused by Wear, Tear, fading, concrete or brick cancer, gradual deterioration
or developing flaws;
…
n) due to normal settling, creeping, heaving, seepage, shrinkage, or expansion in
Buildings, foundations / footings, walls, bridges, roadways, kerbing, driveways,
paths, garden borders and other structural improvements.
…
2) We will not pay for:
…
b) the cost of rectifying faulty or defective materials or faulty or defective
workmanship;
c) consequential loss, loss of use or Depreciation other than as specifically
provided under Extra Benefits, Special Benefits or Optional Covers.
Determination | Case number: 840614 Page 7 of 8
3.3 Expert reports
Record Key points
Financial firm’s expert (M)
Report
16 - 12 - 2021
5.6 Since the insured dwelling was constructed in 2007, its
construction would have needed to comply wit h the BCA of 2006
which also calls up AS: 3740 as its referencing standard. AS: 3740,
section 5.12.2 other floors, section (b) and figure 5.10, shows th e
requirements in plac e at the time of and in fact prior to the insured
dwelling being constructed, required a drainage flange/puddle flange
to be installed.
5.7 The requirements as set out in AS: 3740 of 1994 remains in
force today as a requiremen t as pa rt of AS: 3740 of 2010.
5.8 I can confirm that the requirements for a drainage flange or
puddle flange to be installed to the insured property was a
requirement dating back to 1996 and is still a requirement today.
5.9 As such the lack of a puddle flange to the floor waste fixture of
the insured bathroom is a failure to comply with the BCA and AS:
3740 at the time of constructions and therefore is not only a failure to
comply but a building defect.
Financial firm’s expert (M)
Report
12 - 01 - 2022
5.1 The BCA/ NCC - 2006, Part 3.8.1.21, Membrane to drainage
connections Part b (i) states the following:
“(i) The drainage riser must be fixed to the floor substrat e and the
waterproofing membrane terminat ed not less than 20 m m into the
riser.”
5.2 The key words in the above statement are “must be fixed to the
floor substrat e”. The plumbing report provided by [B] identifies the
following issue:
“I ran water down the waste and found it to be leaking immediately.
It appears that the 50mm PVC waste pipe is simply penetrating the
floor and then waterproofed down into it. The movement in the pipe
has caused the waterproofing at this point to crack and come away,
allowing water through”
5.3 The fact that the pipe has moved indicates that it wasn‟t fixed to
the substrate as required for compliance with BCA/NCC, Part
3.8.1.21 (b) (i)
…
5.7 The fact that the wat erproofing membrane has failed as a result
of movement having caused the membrane to crack is a failure to
use a product that c omplies wit h the requirements of AS:3740, B3
Movement and waterproofing B3.1 General.
…
5.9 Had a properly installed “drainage flange” or “puddle flange”
been installed to comply wit h AS:3740, Section 5. 12.2, Other floors
(b) then the drainage riser woul d not have moved causing the
membrane to crack. The purpose of a drainage flange is to prevent
leakage.
…
Determination | Case number: 840614 Page 8 of 8
Record Key points
5.15 The fact that water was able to seep into the floor cavity and
cause damage to the plasterboard ceiling below is resultant from
movement having cracked the membrane. The cracking of the
membrane is a failure to install the drainage rise to comply with the
additional requirements as set out above with regards the BCA/NCC
and AS:3740.