Insurer limiting liability for building cracking/movement damage claimed after escape of liquid event
Text of the determination
Determination
Case number 833753
Financial firm XL Insurance Company Se
Determination | Case number: 833753 Page 1 of 13
Case number: 833753 27 July 2022
1 Determination overview
1.1 Complaint
The complainants ’ units (1,2 and 3) are covered under a residential strata insurance policy
(policy) underwritten by the financial firm (insurer). A claim has been lodged against the policy
for internal and external cracking/movement damage to the units, said to be due to a burst
mains water pipe discovered in March 2020.
The insurer accepts a valid exists under the policy for damage to the insured property.
However, the insurer is seeking to limit its liability under the claim to damage it accepts to be
due to the escape of liquid (EOL) event. The insurer has offered a cash settlement of
$12,078.83, which has been rejected by the complainants.
The complainants say there is extensive and significant damage to the units caused by the
EOL event which allowed approximately 600kL of water to escape into the foundations of the
units. The complainants maintain this has caused movement within the foundations resulting
in internal and external damage to the units, which is covered under the policy.
1.2 Issues and key findings
Is the insurer ’s assess ment of its liability under the claim reasonable?
Yes. The information shows most of the damage claimed is not related to the EOL event. The
damage for the most part relates to long term natural ground movement, which is excluded
under the policy.
Accordingly, the insurer is entitled to limit its liability under the claim in line with this
determination.
Why is the outcome fair?
The outcome is fair as it is consistent with the more persuasive information which shows most
of the damage to the units (main building) is due to long term ongoing natural ground
movement, which is excluded. However, the outcome also fairly requires the insurer to
increase the level of cover offered to include the recent internal cracking damage that
appeared right after the EOL event. It would be unfair to require the insurer to cover all the
damage claimed in the circumstances.
1.3 Determination
This determination is substantially in favour of the insurer.
The insurer can limit is liability under the claim. However, it is to increase the level of cover
provided under the claim in line with this determination.
Determination | Case number: 833753 Page 2 of 13
2 Reasons for determination
2.1 Is the insurer ’s assessment of its liability under the claim
reasonable?
Yes. The insurer’s decision to limit its liabili ty under the claim is reasonable. This is because
the available information shows most of the damage claimed relates to long term and ongoing
ground movement caused by various contributing factors, which is excluded under the policy.
The policy is an accidental loss or damage contract of insurance
The policy covers the insured property against accidental loss or damage. Cover under the
policy is subject to the conditions, limitations and exclusions specified in the product
disclosure statement (PDS).
The insurer provided the policyholder with the relevant policy documentation including the
PDS and certificate of insurance (COI). Therefore, I accept the insurer is entitled to rely on
the policy provisions to assess its liability under the claim.
The complainants have established a valid claim
There is no dispute the complainant s’ units suffered damage because of the EOL event
discovered in March 2020. I am satisfied this was an unforeseen and unexpected (accidental
damage) event under the policy.
The onus, therefore, rests with the insurer to show an entitlement to decline or limit its liability
under the complainants ’ claim in line with the policy provisions. The insurer says the policy
excludes from cover loss or damage because of:
damage caused by wear, tear, fading, concrete or brick cancer, gradual deterioration or
developing flaws
damage due to normal settling, creeping, heaving, seepage, shrinkage, or expansion in
buildings, foundations/ footings, walls, bridges, roadways, kerbing, driveways, paths,
garden borders and other structural improvements.
The insurer maintains its assessment of the damage shows most of the damage claimed is
excluded under the policy.
Complainants say all the damage has occurred due an insurable event
The complainants say all the damage claimed is because of the EOL event and therefore is
covered under the policy. The complainants rely on the investigations and associated reports
from engineering consultants ‘BE’ and an email from geotechnical engineer ‘SE’. BE’s report
is based on a visual inspection performed of the insured property on 15 January 2021 and 22
March 2021. BE says:
it found substantial signs of subsidence external to the property
stress or foundational movement has occurred across both units 1 and 2 of the entire main
building. This is evidenced by signs of cracking throughout, dislodgement of brick sills,
cracking floor tiles, doors being out of square, and unlevel flooring observed
the stress or foundational movement across the main building caused by the EOL event
which has moved the footings
before and after photographic evidence shows no signs of internal distress before the EOL
event
Determination | Case number: 833753 Page 3 of 13
while no inspection of unit 1 was performed, it is recommended that structural works are
required (in the form of underpinning) across the entire main building to bring back
structural adequacy by raising the foundation
after these works, then a builder can be appointed to complete more cosmetic type
damage to the units.
The email from SE consists of a single statement saying that given the amount of water which
escaped from the leaking pipe, the escape of liquid will have impacted the footings causing
movement. SE does not provide any further comment, analysis or supporting information. It is
also not apparent from the email that any physical inspection of the property was performed
by SE.
The complainants say that the BE reports, when considered in combination with SE’s email,
support a view that the damage noted to the insured units is likely the result of the EOL event.
The complainants say due to the large volume of water escaping (600kl) over a relatively
short amount of time, this placed additional saturation of the subsurface soils causing water
erosion and associated movement of the footings.
The complainants say this has compromised the structural integrity of the main building and
caused subsidence damage . The complainants note BE’s findings say that beside the
external repairs required, all three units need underpinning works to maintain structural
adequacy.
Insurer says only limited damage to the insured property relates to EOL event
The insurer accepts the external damage to the main building was caused by the EOL event.
However, the insurer says there is no damage to the main building because of the EOL event.
Rather, the damage to the main building has occurred over time, due to natural foundational
movement, which is excluded under the policy.
The insurer relies on the various site inspections and associated reports from engineering
consultants ‘F’, engineering geologist ‘SM’ and repair quote from builder ‘J’.
F completed a site visit on 15 July 2020 and has provided several reports setting out its
opinions as well as responding to BE’s information. F’s reports found:
the western wall and boundary wall between units 2 and 3 were previously underpinned in
2018. F says this shows the main building was subject to previous foundational movement
underpinning itself does not prevent future movement laterally or due to seasonal moisture
changes. Underpinning also does not prevent movement between the underpinned section
and non-underpinned section of the building, which can cause secondary cracking
previous signs of cracking damage to the main building which had been previously
repaired
poor site drainage due to the absence of surface drainage provisions, poorly graded
permeable perimeter ground between the driveway and the western external wall
the severity of cracking found throughout the main building was low with it generally limited
to between 0.1 mm to 1 mm and 1 mm to 5 mm
no evidence of localised heave damage near EOL location
due to stiffness and permeability of the soils, water from EOL would not have penetrated to
the depth of the footings and cause damage to the main building
elevated moisture levels at footing depth does not in itself mean that the building will move
floor level survey shows differential slab/footing movement across the slabs of the main
building
Determination | Case number: 833753 Page 4 of 13
the EOL event caused or contributed to the damage to areas immediately adjacent to the
pipe location, that is the apron slab and boundary wall between units 1 and 2.
SM was engaged by the insurer to perform a geotechnical survey of the property. This was
performed on 9 August 2021. SM reported as follows:
the footings were at a founding depth of 900 mm
both surface and subsurface site drainage was classified as poor
the soil was classified as a problem site (P), due to the presence of 500 mm of filling,
presence of adjacent vegetation and nearby structures
two bore samples were taken, a control bore sample from the western side of unit 1 and
secondary bore sample from the area immediately adjacent to where the EOL occurred
the control sample (opposite side of EOL area) showed consistent moisture readings of
around 22% across all depths (up to 1.3 meters)
the secondary bore sample (adjacent to EOL area) showed elevated moisture readings
from 44.6% at footing level to 31.2% at 1.5 meters
although the weight and stiffness of masonry buildings reduces expansive clay movement,
the sensitivity of this form of construction to small distortions can create special problems
the sedimentary nature of the Quaternary aged soils and depth of Clay indicates a
moderate soil reactivity and seasonal heave potential
the condition o f the founding level was very stiff with bearing pressure at founding depth of
100kPa in fair to good condition
More detailed information from the consultants’ reports ha s been provided in section 3 of this
determination.
The insurer says it is clear from the reports provided by F and SM that the damage to the
main building has occurred over an extended period because of the reactive clay soils the
property is built on. The damage to the main building has occurred due to normal settling,
heave and ground movement of the footings and foundations as opposed to a distinct single
event. Given this, the insurer says it is entitled to rely on the policy provisions to limit its
liability under the claim and decline cover for most of the damage claimed.
Information from the insurer is more persuasive
There is no dispute an EOL event occurred leaking a significant amount of water (moisture)
and which has caused some damage to the external areas of the insured property. It is also
not disputed that the main building on the property, which comprises units 1, 2 and 3,
presents with evidence of previous ground movement damage and associated previous
repairs.
The information from the consultants provide photos of internal cracking to walls and cornices
which appears fresh. The complainant from unit 2 purchased the property in 2019 where
these current cracks were not present.
I am satisfied it is reasonable to accept the main building does show evidence of and has
been subject to ongoing long term natural ground movement and associated repairs. I am not
satisfied all the damage to the main building is related to or caused by the EOL event.
I accept the complainants’ opinion that F is incorrect in its assessment that the significant
water leak event did not allow moisture to reach the founding level of the main building’s
foundations. I also note both F and BE’s initial site assessments and a ssociated reports were
based on investigations before SM’s attendance and geotechnical report. This report confirms
higher moisture levels to the foundation materials.
Determination | Case number: 833753 Page 5 of 13
However, based on SM’s report, I am satisfied it is fair to accept this introduction of moisture
to the foundation clay soils did not result in all the damage claimed. The foundations were
found to be in fair to good condition, very stiff and having a bearing pressure of 100kPa. This
indicates the foundation materials and footings were in a stable condition despite elevated
moisture levels.
I note SM has said there may have been some localised heave around the leaking pipe which
has since stabilized. SM says masonry buildings reduce expansive clay movement but the
sensitivity of this form of construction can experience special problems through small
distortions. SM’s report shows the i nsured property is constructed o n what is classed as a ‘P’
(Problem) site with the sedimentary nature of the quaternary aged soils to react moderately
with seasonal heave potential.
The fact the property is susceptible to normal seasonal movement is supported by the
information which shows historical widespread minor cracking to the main building and
associated repairs. Also, that the previous owner of unit 2 was required to complete
underpinning works in 2018.
Floor surface measurements support evidence of largely uniform movement which is not
consistent with movement or damage from a single recent EOL event. I am of the opinion the
available information suggests a historical vulnerability to foundational seasonal movement
and associated damage.
I accept there are some failings in F’s findings with respect to the levels to which moisture
from the EOL travelled. However, given the analysis above, I am persuaded the EOL event is
not responsible for all the damage claimed.
Insurer is entitled to limit its liability under the claim
The proximate cause of the loss is a question of fact, depending on the circumstances in
each case. The proximate cause is not necessarily the first or the last or the sole cause of
loss. It is the effective or dominant or operative cause of the loss.
I am satisfied the insurer has established, on balance, the EOL event is not the proximate
cause for all the damage claimed. The available information does not show the EOL event
has caused movement or damage to the foundation and footings. Rather, that th e main
building has been the subject of ongoing long term natural foundation movement which has
continued to cause damage.
However, in saying that, I am of the opinion it is fair in the circumstances to accept the fresh
internal cosmetic damage to plaster walls and cornices etc, can be associated with the EOL
event. Given this, I find the insurer is to increase the level of cover accepted under the claim
to include the internal cosmetic damage to the main building. This does not include the
flooring or any suggested underpinning works recommended by BE.
The policy excludes damage caused due to normal settling, heave, shrinkage or expansion in
the building, foundations, footings or walls. Accordingly, I am satisfied the insurer is entitled to
limit its liability under the claim in line with this determination.
Insurer to increase payment for internal cosmetic repairs
The insurer accepted liability for damage external to the main building as arising from the
EOL event and provided a quote from J for those works in the amount of $12,078.83. I have
not been provided with any information to show that this quoted amount is incomplete or
inadequate.
Determination | Case number: 833753 Page 6 of 13
Within 21 days of the insurer receiving notice of the complainants’ accepta nce of this
determination, the insurer is to arrange for J (or an adequately qualified builder) to provide an
actionable quote for repairs to the fresh internal cracking/cosmetic damage that became
apparent shortly after the EOL event. Within 7 days of receiving this quote, the insurer is cash
settle the claim based on this quote, in addition to the $12,078.83 for external repairs.
The insurer should also pay an additional 20% on these settlement amounts to allow for
contingencies (such as potential variances in the works) and the transfer of risk to the
complainants in arranging the repairs.
2.2 Why is the outcome fair?
The outcome is fair in all the circumstances because the information provided indicates the
property has subsided due to normal settlement over time and not due to the EOL event. It
would be unfair to require the insurer to cover all of the claimed damage. Equally, it is fair in
the circumstances that the fresh cracking damage to the units which appeared after the EOL
event to be covered.
Determination | Case number: 833753 Page 7 of 13
Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all the information the parties have provided.
While the parties have raised several issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
3.2 Relevant information from the consultants
Record Key points
Financial firm’s expert ( F )
Report
13 August 2020
Site is on relatively flat land which is generally consistent with the
natural topography of the surrounding land
Poor site drainage due to presence of poorly graded
permeable(unpaved) perimeter ground between the driveway,
western external wall and absence of active form of surface
drainage provisions, su ch as pits, cut - off drains
Determination | Case number: 833753 Page 8 of 13
Record Key points
Signs of settlement of the eastern external wall, apron slabs,
boundary wall between units 1 and 2 and step between the
kitchen floor of unit 2 and adjacent paved apron areas
Signs that crack developed between external and bounda ry wall,
with previous repairs evident
Apron slab has been undermined
Cracks observed in units 1, 2 and 3
Floor level survey conducted of units 2 and 3, which showed a
total variance from 0 to + 120 mm.
General pattern of relative settlement towards the entrance of unit
2
Expects that the foundation soil would be classed as highly
reactive, class H1/H2 reactivity expected in accordance with
AS2870 - 2011
When buildings founded on reactive clay soils, differential
variations in the foundation soil moisture content can result in
building movement related damage , that is if the moisture content
increases, heave damage expected, and if moisture content
decreases clay soil tends to shrink and settlement of the footings
occur
Underpinning works undertaken to unit 2 during 2018.
Underpinning was performed to the western wall and boundary
wall between units 2 and 3 only. The design required 6 pins to be
installed below the strip footing,
Nature of obs erved internal and external damage consistent with
building damag e associated with long - term differential
foundation/ footing movement of buildings on reactive clay soils,
which in this case exacerbated by poor ground surfac e drainage
adjacent to the building and presence of substantial trees/
vegetation near. Nat ure of observed building damage consistent
with footing movement indicated by the general/overall pattern of
the floor level surveys.
Severity of cracking to building fabric limited to very slight (0.1mm
to 1 mm) to slight (1 mm to 5 mm).
This is categorised as non - structural and so requires repairs after
adverse site conditions addressed
EOL has released significant volume of water below the eastern
side of the unit, causing observed saturation and partial erosion of
the soils underside of the slab. The washout/ erosion of the soils
underside of the slab pavement has resulted in local bearing
failure of the founding soils at this location causing the observed
subsidence of the pavement and crack to the boundary wall
between Units 1 and 2
Slabs and boundary wall a t site of EOL were observed to be
showing signs of long term damage with evidence of previous
repairs. F’s opinion that subject area had been subject to long
term movement which has been exacerbated by EOL.
EOL has caused saturation soils in immediate vici nity , the
Determination | Case number: 833753 Page 9 of 13
Record Key points
subsequent wash - out was limited to the localised areas Of the top
soil of the eastern yard. No damage caused to the main building
due to the EOL.
Fact that underpinning performed in 2018 indicates the building
has been subject to foundation move ments and remedial works
were required to stabilise and prevent long term foundation
movements,
Underpinning does not necessarily prevent further movement as it
does not fix an inadequate foundation system or remove ongoing
seasonal changes in soil conditi ons. Furthermore, as in this case,
where the building has been partially underpinned, differential
movement expected to occur between the underpinned and non -
underpinned areas, as underpinning of localised area would cause
other parts of building to move d ifferentially leading to further
secondary cracking damage to building. Underpinning also does
not prevent lateral movement.
Locations and pattern of wall cracks is typical of damage caused
by differential movement. The wall cracking pattern and floor lev el
surveys indicate relative settlement towards the north and west of
the site, which are in the general directions towards where
substantial trees/ veget ation located in close proximity, and where
there is no protective paving adjacent to, sloping away fr om , the
external walls/ footings of the building, causing accent uated
fluctuation of moisture levels
Floor level survey of Unit 2 indicat e settlement of approximately 60
mm toward the northeast region. Similar patterns of magnitude of
the floor movements were also observed in Unit 3, which is 15 m
away from EOL, This suggests he general movement behaviour of
both units consistent even though Unit 2 was subject to pipe burst
Movement to main building caused by:
>
> Soil drying caus ed by trees in close proximit y to house,
combined with relatively low rainfall
> Seasonal changes in soil moisture content, amplified by nearby
trees
> Reactive clay founding soils
> Poor site drainage
That if the damage to main building was caused by EOL, F would
have expected to observe:
> Distinct localised raised floor levels in areas adjacent to EOL
> Localised damage consistent with heave in vicinity of EOL
> Severity of damage closest to EOL and reducing in severity the
further way it is from ponding location
F says:
> Floor level survey re sults indicate differential slab/ footing
Determination | Case number: 833753 Page 10 of 13
Record Key points
movement across entire building slab, not localised
> Similar levels of int ernal/ external cracking damage observed
throughout main building. No greater severity of building
damage observed at location of EOL.
> Observ ed varying degrees and patterns of previously repaired
cracks, indicating that cracking has been present for an
extended period of time
> EOL did not cause the damage to the main building. All the
observed differential footing movement and associated damage
to the floors and wall of the mina building are caused by long
term foundational movement,
> Underpinning works in 2018 had no bearing on EOL
> Recommended that in order to reduce future foundational
movement that footings of external walls need to be protected
against moisture variation by making them impervious and the
garden bed/ unpaved areas immediately adjacent to the main
building be paved with 50 mm fall over the first 1 m away from
the main building,
> EOL did caus e/ contribute to the damage to t he area
immediat ely adjacent to EOL, that is the apron slabs and the
boundary wall between Units 1 and 2
Financial firm’s expert ( F )
Report
29 September 2020
Bearing capacity of soil beneath footings not comprised as:
> Floor level survey results showed no distinct pattern of localised
settlement in vicinity of affected footings
> Building damage would have been localised to the adversely
affected sections of the building and in close vicinity to the
affected locations and not widespread throughout the buil ding.
This was not obs erved .
While plausible EOL has caused wash out of the top soil, it is not
expected to have affected the natural founding soils of the footings
Topsoils which is of silty and sandy materials, are permeable and
able to allow water to pa ss through it quickly, without causing
damage to footings. Based on floor level surveys , no significant
localised subsidence of footings occurred
Relatively stiff and impermeable underlying clay soils directly
below the topsoils at the subject site would have prevented the
escaping water physically undermining the footings of the main
building
Based on the reactivity of the clay and its stiff to very stiff
consistency, it is F’s experienc e that the water would not ingress
to depths that would compromise th e founding soils of the footings
Any water flowing on the surface would not penetrate downwards
to depths that would cause significant foundation movement in the
form of heave or compromised bearing capacity.
Expected the majority of the surface water woul d have eit her
drained way relatively quickly or locally saturated the ground within
Determination | Case number: 833753 Page 11 of 13
Record Key points
the upper disturbed soil layer without affecting the moisture
content of the underlying clay soils below the footings
Complainant’s expert ( BE )
Report
12 April 2021
Report compiled from visual ins pection on units 2 and 3
Photographs taken showed cracking throughout units 2 and 3
Unit’s 2 and 3 have experience movement in the footings.
Subsidence has created several areas of distress and have
partially compromised the structural integrity of the building. It is
highly likely that the subsidence damage has been caused by the
significant escape of water
The main building is structurally safe and appears to have
stabilised, rectification works in required to bring back str uctural
adequacy prior to EOL. Unit 2 observed to have a significant
number of defects, while unit 1 is not inspected
Movement in the internal and external walls is extensive and is not
isolated to any one area, structural alignment needs to be
addressed t o prevent further distress
Saturation of foundations in the main building would have needed
to be considerable and so movement related to the EOL
Engineering underpinning design needed to re - establish dwelling
alignment
Raising of the foundation, re - levell ing and re - s upport of the main
building required to fix subsidence
Sagging of roof over window (roofline bowing) potentially caused
by defect i n construction, not EOL related. This has contributed to
the foundational movement
Terrace slab at rear of Unit 3 has illustrated subsidence via soil
erosion
Complaints expert ( BE )
Report
14 April 2021
Report delivered in respons e to F’s report of 13 August 2020
F made assumption that volume of liquid restricted to subject
localised area. Assumption is disputed, as impractical to assume
this volume would not have affected a larger area than reported.
The absorption rate of the soil would mean that saturated soils
would be affected in a larger area and exacerbated by the fact that
the water leak was over a relative ly short period of time.
Some localised heave evident in the kitchen and bathroom area,
which is localised to the origin of the event where clay has swollen
Referred to photos which BE said was taken in early 2020 which
evidenced no signs of internal distr ess prior to the EOL
Floor level survey comprised only two measurements which is
inconclusive
Agreed some repairs had been observed throughout the property.
However, the current distress throughout only reoccurred since the
EOL.
Determination | Case number: 833753 Page 12 of 13
Record Key points
Financial firm’s expert ( F )
Report
23 August 2021
Geo technical investigation performed by L
Site was classified as classified as class P due to:
> Presence of filling up to 500 mm over site in general
> Presence of vegetation on the subject and adjacent sites
> Susceptible nature of the clayey silt to water inundation]
> Presence of existing structures, paving and services
> In the absenc e of the above conditions, Class M would have
been appropriate for the site due to the sedimentary nature of
the quaternary alluvial soils and depth of c lay
Two bore samples were taken which showed:
> Founding material was natural clay with condition and moisture
at founding depth classified as very stiff and moist
> Bearing pressure of 100 kpa
> The bore sample adjacent to the EOL showed moisture readings
of 44 .6 at footing depth (900mm) and 31.2% at 1.5 meters
> The bore sample for the control sample taken from the opposite
side of the EOL showed readings between 22% to 24% ac ross
all depths
No bearing pressure failure of footings
Complainants expert ( BE)
Report
1 February 2022
Estimate of $118,146.87 for remediation of each unit
Email from G
9 February 2022
Given the amount of water that escape from the leaking pipe and
the large variation in moisture content from the provided Geotech
report, it is our opinion that the escape of liquid will have impacted
the footings and caused movement
Financial firm’s expert ( F )
Report
18 February 2022
L report they agree shows elevated moisture levels of the soil in
affected areas, However, exacerbated/ fluctuated moisture content
of soils does not always translate to building movement when
loading effects from the presence of a building are considered
That if the elevated moisture would have affected the footings to
cause heave, they would have expected to see:
> Uplifting of footings near vicinity of the EOL, F says this was not
observed
> Bearing pressure of the soils at founding level was classified as
very stiff with bearing pressure of 100 kpa. AS287 Residential
slabs and footings requires that the allowable bearing pressure
of natural soils for the constructio n
of residential building shall be 50kPa – 100kPa, suggesting that
the identified bear ing capacity
of the soil beneath subject footings is sound and no bearing
capacity failure or alleged “washout”
Determination | Case number: 833753 Page 13 of 13
Record Key points
of founding soils has occurred as a result of the pipe burst event.
The EOL has caused/ contributed to the damage adjacent to the
EOL but not th e main building.
3.3 Relevant policy wording
Page Wording
14 Loss or damage
Means direct physical loss of, destruction of, or damage to property
from any sudden and accidental cause not otherwise excluded
under policy
‘
21 Section 1 - Buildings
What is covered
We insure you up to the sum insured shown on the schedule for
Section 1, against accidental Loss or Damage to your insured
property which occurs during the period of ins urance.
27 What is not covered?
We will not pay for loss and damage:
Caus ed by wear, tear, fading, concrete or brick cancer, gradual
deterioration or developing flaws
Due to normal settling, creeping, heaving, seepage, shrinkage, or
expansion in buildings, foundations/ footings, walls, bridges,
roadways, kerbing, driveways , paths, garden borders and other
structural improvements.