Denial of home and contents claim for heating unit damage; lightning vs power surge causation
Text of the determination
Determination
Case number 831634
Financial firm Allianz Australia General Insurance Limited
Determination | Case number: 831634 Page 1 of 9
Case number: 831634 20 April 2022
1 Determination overview
1.1 Complaint
The complainant holds home and contents insurance with the financial firm (the insurer). On
12 May 2021, the complainant lodged a claim on the policy for damage to the heating unit of
her ducted heater/cooler. She said the heater had stopped working due to motor burnout.
The insurer has denied the claim. It says policy exclusions apply as the heater’s motor was
over 15 years old and the most likely cause of the burnout was power surge. It also says the
alternative suggested cause of the damage, lightning strike, was unlikely given weather
records and as the heater is in the ceiling space. Further, the insurer says the complainant
prejudiced its interests by seeking to have the heater repaired before lodging the claim.
The complainant disagrees with the insurer. She wants the insurer to reimburse her the
$19,581.70 she paid to have the heating/cooling unit replaced. She also seeks non-financial
loss compensation for stress and inconvenien ce caused by the insurer’s claim handling.
1.2 Issues and key findings
Is the insurer entitled to deny the claim?
No. On the balance of probabilities, the proximate cause of the damage was lightning. The
complainant has established a valid claim under the policy. The insurer has not proven an
exclusion applies or demonstrated the complainant prejudiced its interests.
Is the complainant entitled to non-financial loss compensation?
Yes. The insurer did not adequately assess the claim under the lightning insured event. It also
raised a number of less than convincing reasons for denying the claim. Th e insurer’s claim
handling caused avoidable delay. The insurer is to pay the complainant $1,000 in non-
financial loss compensation for the stress she experienced as a result.
Why is the outcome fair?
A valid claim under the policy has been established and the insurer has not shown an
exclusion applies or that the complainant prejudiced its interests. Accordingly, it is fair that the
insurer pays the claim. It is also fair that the insurer pays the complainant $1,000 in non-
financial loss compensation for the stress its claim handling caused.
1.3 Determination
This determination is substantially in favour of the complainant.
Within 21 days of receiving notice the complainant accepts this determination, the insurer is
to pay the complainant:
$19,581.70
interest on $19,581.70 pursuant to section 57 of the Insurance Contracts Act, 1984 (Cth)
from 23 November 2021 (when the unit was replaced) to the date payment is made
$1,000 in non-financial loss compensation.
Determination | Case number: 831634 Page 2 of 9
2 Reasons for determination
2.1 Is the insurer entitled to deny the claim?
No. On the balance of probabilities, the proximate cause of the damage was lightning. The
complainant has established a valid claim under the policy. The insurer has not proven an
exclusion applies or demonstrated the complainant prejudiced its interests.
The policy covers insured events and accidental damage
The complainants is required to show, on the balance of probabilities, that she suffered a loss
covered by the policy. This is known as a valid claim.
The complainant holds a premier care home and contents insurance policy with the insurer.
Relevant extracts of the policy’s product disclosure statement (PDS) are set out in section 3.2
of this determination.
The policy covers the complainant for loss or damage caused by specified insured events.
These include lightning as well as EMB.
Relevantly, the EMB insured event does not cover:
replacing a whole appliance if its motor cannot be replaced
any parts or labour for motors that are over 15 years old.
The PDS also covers accidental damage to the complainant’ s home and contents. However,
if the damage is due to an insured event, the claim must be lodged under that section of the
policy. Further, the accidental damage cover does not apply to loss or damage:
excluded under any insured events (unless otherwise stated)
caused by electrical, mechanical or computer breakdown, failure or derangement (other
than motor burnout).
Once the complainant establishes a valid claim, the insurer is liable for the loss unless it
shows an exclusion or limiting condition applies. The insurer has the onus of proof in
establishing the application of the exclusion. The standard of proof is the balance of
probabilities.
The PDS contains general exclusions that apply to both the insured events cover and the
accidental damage cover. The policy excludes cover for damage caused by or arising from:
Power surge.
electrical, mechanical or computer breakdown or loss or damage to electrically
powered items caused by power surge originating from the supply authority.
Accordingly, it is necessary to determine the proximate cause of the damage claimed.
Proximate cause is the dominant, efficient or operative cause of a loss. It is not required to be
last in time or the sole cause. It is a question of fact that depends on the circumstances of
each case. It requires a common sense evaluation of the evidence.
The heater broke down and needed to be replaced
On 12 May 2021, the complainant lodged a claim on the policy as her heating system had
stopped working.
Determination | Case number: 831634 Page 3 of 9
On 13 May 2021, the complainant obtained a causation report from PF, air conditioning and
heating technician. PF said that the main printed circuit board (PCB) had blown up, the hi
module PCB had melted, and the indoor fan motor had burnt out. PF considered the main
cause of the heater’s failure was a power surge or a lightning strike. He also identified a leak
in the air conditioning’s refrigeration line caused by the indoor fan motor vibrating.
The complainant received two rectification quotes dated 17 May 2021. Both quotes said
installation of a new heating/cooling system was required. PF quoted $20,317 inclusive of
GST. KE, another air conditioning and heating technician, quoted $22,550 inclusive of GST.
On 30 May 2021, PF provided an updated quote to the insurer, totalling $20,680 inclusive of
GST. The updated quote included the following comments:
Existing heater and ac unit
[B] main PCB module cannot be replaced as parts are obsolete from manufacture
Aircon system will not work with new [B] heater
Due to the insurer denying the claim and pending resolution of this complaint, the
complainant arranged for PF to remove the old unit and install a new B heater and air
conditioning system. PF completed the work on 23 November 2021 and charged $19,851.70
inclusive of GST. PF’s invoice said the unit was ‘damaged due to lightning (weather)’.
The insurer says the claim is not covered
Following notification of the claim on 12 May 2021, the insurer appointed MK, loss assessors.
MK inspected the insured property on 8 June 2021. In its report dated 22 July 2021, MK says:
the heating unit was in sound condition, with no signs of water or impact damage
there was evidence of recent attempts at repair
its professional opinion was that the unit was over 15 years old
it appointed builders, NB, to inspect the unit. NB:
> found power to the controller and the gas inlet turned off, electrical cables disconnected
and electrical components missing
> could not ignite the unit after attempting to rectify these issues
> was unable to comment on causation due to the prior attempts at repair
accordingly, the complainant prejudiced the insurer’s interests in that it was denied the
opportunity to properly investigate the cause of the damage.
On 11 August 2021, MK sent an email to the insurer saying:
the gas heater and the air conditioning condenser are separate units but work in sync
the heater can be repaired/replaced without affecting the condenser
the heater is over 15 years old and has reached its life span of operation.
The date on which the insurer denied the claim is not clear. However, on 16 August 2021, the
insurer issued an IDR outcome letter to the complainant. The letter reconfirms the decision to
deny the claim on the basis the EMB insured event does not cover motors that are over 15
years old and given the application of the power surge general exclusion.
In its notice of response dated 8 October 2021, the insurer informed AFCA it considered that
the claim had been correctly denied. It said the EMB insured event does not opera te where
Determination | Case number: 831634 Page 4 of 9
the whole appliance must be replaced as the motor cannot be repaired or the motor is more
than 15 years old. It also said the policy does not cover damage due to power surge.
The insurer submitted that the complainant had breached her obligation under the policy to
allow access and a reasonable time to inspect the loss or damage before any repairs are
completed. It said its interests had been prejudiced as a result.
After the insurer rejected the EMB claim, the complainant raised lightning strike as the cause
of the damage. She says she did so at the suggestion of one of the insurer’s representatives.
In its notice of response, the insurer said lightning was unlikely to have been the cause of the
damage given weather records confirmed there was no thunderstorms in the complainant’s
area on 11 or 12 May 2021. In any event, the insurer said it was unlikely lightning could affect
the heater uni t as it was located within the property’s ceiling space.
On 5 January 2022, the insurer provided a further notice of response, in reply to specific
questions from AFCA. The insurer reconfirmed its position set out in the notice of response,
although, it co nceded that there were thunderstorms in the complainant’s area on 2 and 3
May 2021.
Also, for the first time, the insurer provided commentary on the accidental damage cover
provided by the PDS. It said that cover did not apply because:
that coverage section does not apply to damage excluded under an insured event or to
electrical breakdown other than motor burnout
as the claim was excluded under the EMB insured event, it could not be covered as
accidental damage.
The most likely cause of the damage was lightning
According to the insurer, on 12 August 2021, the complainant expressed dissatisfaction with
MK’s findings and said the claim should be lodged under the lightning insured event. The
complainant says the insurer’s representative encouraged her to do so .
In his causation report dated 13 May 2021, PF said the main cause of the heater’s failure was
a power surge or a lightning strike. PF was more specific in the invoice he issued on 23
November 2021 – he said the unit was ‘damaged due to lightning (weather)’.
The complainant says KE also told her that it assumed the damage was caused by weather.
She also notes that the Bureau of Meteorology (BOM) issued a thunderstorm warning
applicable to her area.
The insurer submits lightning is unlikely to have been the proximate cause of damage as the
BOM records it obtained confirm there were no thunderstorms on 11 or 12 May 2021.
However, the BOM records show that there were thunderstorms on 2 and 3 May 2021 and
the insurer has not provided a BOM storm report for 10 May 2021.
The insurer also says it is not likely that lightning could affect the heater unit as it was located
within the property’s ceiling space . This submission is based on a desktop review undertaken
on 12 August 2021 by one of the insurer’s technical claims specialists. That person’s
qualifications to express such an opinion have not been stated.
The insurer has not provided any external expert opinion to support its view that lightning is
unlikely to be the proximate cause of the damage claimed.
Determination | Case number: 831634 Page 5 of 9
In the circumstances, I am satisfied that the complainant has shown on the balance of
probabilities that the proximate cause of the damage was lightning. She has established a
valid claim under the policy.
Insurer has not established an exclusion applies
The only general exclusion the insurer relies precludes cover for loss or damage ‘ caused by
power surge originating from the supply authority ’ .
The insurer relies on PF ’ s report dated 13 May 2021. However, that report says the main
cause of the damage was power surge or lightning strike. Further, PF clarified on 23
November 2021 that it considered the damage was due to lightning.
I am not satisfied the insurer has shown the power surge exclusion applies.
Insurer has not proven an entitlement to reduce its liability
Section 54 of the Insurance Contracts Act applies where a policy provision would permit the
insurer to refuse to pay a claim, wholly or partially, due to the act or omission of an insured or
some other person after the policy commenced.
Where the act or omission could not reasonably be regarded as being capable of causing or
contributing to a loss covered by the policy, the insurer may not refuse to pay the claim. It
may, however, reduce its liability to the extent the act or omission prejudiced its interests.
The PDS sets out a number of claim conditions, including:
When we ask, you will need to:
provide us with access and a reasonable time to inspect the loss or
damage before you allow anyone to fix or interfere with it …
The insurer says in seeking to repair the unit prior to lodging the claim, the complainant
breached this claim condition and prejudiced its interests. In doing so, it relies on MK’s
description of NB’s views.
However, a report from NB has not been provided. The pre-existing damage it says it found
and the scope of its testing is not confirmed. Further, the complainant denies that any
attempts to repair the heater were made prior to notification on 12 May 2021.
In addition, the insurer has not stated how its ability to investigate lightning as a cause of
damage has been compromised.
Accordingly, the extent to which the insurer’s interests may have been prejudiced by the
complainant’s alleged failure to allow access and a reasonable time to inspect the damage is
unclear. The insurer bears the onus of proving prejudice. It has not done so.
Insurer is to cover the claim
In the circumstances, the complainant is entitled to be indemnified for the claim.
The insurer is required to reimburse her for the $19,581.70 she paid to replace the unit. It is
also to pay interest on that amount pursuant to section 57 of the Insurance Contracts Act from
23 November 2021 (when the unit was replaced) to the date payment is made.
Determination | Case number: 831634 Page 6 of 9
2.2 Is complainant entitled to non-financial loss compensation?
Yes. The insurer did not adequately assess the claim under the lightning insured event. It also
raised a number of less than convincing reasons for denying the claim. The insurer’s claim
handling caused avoidable delay. The insurer is to pay the complainant $1,000 in non-
financial loss compensation for the stress she experienced as a result.
Compensation is awarded conservatively
Under the AFCA Rules, we may award compensation (capped at $5,400) for non-financial
loss where a complainant has suffered an unusual degree or extent of physical
inconvenience, time taken to resolve the situation or interference with their expectation of
enjoyment or peace of mind.
We take a conservative approach to compensation for non-financial loss. It is not awarded
when a person suffers the normal degree of inconvenience when a problem occurs.
Complainant is entitled to compensation
The complainant says that the insurer unreasonably delayed progression and determination
of her claim. She says she had to often chase up the insurer for updates. The complainant
submits she has suffered significant stress and inconvenience due to the insurer’s actions.
She particularly notes that she and her ill husband had to endure winter without heating.
Given the matters set out in section 2.1 of this determination, I am satisfied that the insurer
did not thoroughly investigate lightning as a potential cause of the damage.
In addition, it raised a number of reasons for denying the claim which were not convincing
and which in some cases were later disproved. For example, the insurer argued:
the cause was power surge based on PF’s report dated 13 May 2021
the unit was over 15 years old (and therefore not covered under the EMB insured event)
based on MK’s ‘professional opinion’. No exp lanation was provided of how MK reached
that view or of its expertise in assessing the age of heating units. The complainant
maintained the heater was less than 15 years old. On 1 March 2022, it was confirmed that
the unit was made in 2011.
In the circumstances, I agree with the complainant that the insurer unreasonably delayed
determination of her claim. However, I am not satisfied that the insurer is fully responsible for
the complainant and her ill husband experiencing winter without adequate heating. This is
because lightning as a possible cause of the damage was not raised until mid August 2021.
Overall, I accept that the complainant’s claim experience has been unsatisfactory due to the
insurer’s actions . The insurer is to pay her $1,000 in non-financial loss compensation.
2.3 Why is the outcome fair?
A valid claim under the policy has been established and the insurer has not shown an
exclusion applies or that the complainant prejudiced its interests. Accordingly, it is fair that the
insurer pays the claim. It is also fair that the insurer pays the complainant $1,000 in non-
financial loss compensation for the stress its claim handling caused.
Determination | Case number: 831634 Page 7 of 9
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. I have reviewed and considered
all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, I have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
Determination | Case number: 831634 Page 8 of 9
3.2 PDS extracts
Page 12
General Exclusions
…
Your policy does not cover any loss or damage that is caused by or arises from:
…
Power surge.
electrical, mechanical or computer breakdown or loss or damage to electrically powered
items caused by power surge originating from the supply authority.
Page 19
Lightning.
Covered.
Loss or damage caused by lightning.
Page 22
Electrical motor burnout.
Covered.
Loss or damage to electric motors that are part of your building or contents if the motor is
burnt out at the building or site, and the burnout is directly caused by electric current, for
example, the motor in items such as an air conditioner, pool pump or garage door.
If we agree to pay a claim, we will cover the cost of repairing or replacing the electric
motor, the servic e call fee and labour charges. If the motor can’t be replaced, we will pay
the current replacement cost of an equivalent motor of the same specification and
standard.
Not covered.
• fuses, switches, lighting or heating elements, electrical contacts or prot ective devices,
• replacing the whole appliance if a motor cannot be replaced,
Determination | Case number: 831634 Page 9 of 9
…
• any parts or labour for motors that are over 15 years ol d from the date of manufacture.
Page 23
Accidental loss or damage
Covered.
Accidental loss or damage to:
• your build ing and/or contents at the site, or
…
If loss or damage is caused by any other insured event, you must claim under that section
of your policy.
…
Not covered.
Any loss or damage excluded under any insured events, unless otherwise stated.
Loss or damage caused by:
• electrical, mechanical or computer breakdown, fai lure or derangement (other than motor
burnout),
…