Home / Allianz Australia / Determination 823211
Determination 823211
Claim decline for electrical switchboard damage relying on gradual deterioration exclusion
Summary
The insurer declined the complainants' electrical switchboard claim after a storm-related water ingress, citing gradual deterioration of sealant. AFCA found the insurer had not discharged its onus to establish the exclusion and ordered it to pay the electrical repair cost with statutory interest, but declined non-financial loss compensation.
Once a valid accidental damage claim is established, the insurer bears the onus to prove an exclusion applies, and it failed to do so given the most contemporaneous evidence, as the revised RT report was given less weight.
Issues
- Claim denial primary · upheld
“The insurer has not sufficiently met its onus to establish an exclusion applies. The insurer is required to accept the claim for electrical repair costs.”
- Inadequate claim investigation secondary · upheld
“I consider the most contemporaneous report the more reliable; the insurer's decision was not supported by the information provided to AFCA.”
- Delay secondary · upheld
“I accept the insurer's initial handling of the claim caused a slight delay with the insurer's assessment and consideration of the claim.”
Subjects and remedies
pay claimpay interest
Text of the determination
Determination
Case number 823211
Financial firm Allianz Australia Insurance Limited
Determination | Case number: 823211 Page 1 of 7
Case number: 823211 30 March 2022
1 Determination overview
1.1 Complaint
The complainants hold a home and contents insurance policy with the financial firm (insurer).
The complainants lodged a claim for food spoilage and electrical repair costs after their power
supply was interrupted and the switchboard damaged.
The insurer settled the complainants for the food spoilage. However, it declined the claim for
electrical costs. It says:
the cause of the damage was deteriorated sealant around the switchboard
the policy excludes cover for damage caused by gradual deterioration.
The c omplainants dispute this decision and raise concerns with the insurer’s handling of the
claim.
1.2 Issues and key findings
Can the insurer decline cover for the electrical costs?
No. The exchanged information shows damage occurred when water entered the
switchboard. I accept this was a sudden, unforeseen and unexpected event for the
complainants. The insurer has not sufficiently met its onus to establish an exclusion applies.
The insurer is required to accept the claim for electrical repair costs.
Should the insurer provide further compensation?
While the insurer did not immediately process the claim for electrical damage correctly, I do
not consider an award of compensation for non-financial loss is appropriate in this instance.
Why is the outcome fair?
The outcome is fair because:
the material provided is sufficient to show damage covered by the policy terms
the insurer has the onus to establish it was fair to decline the claim
the material provided does not satisfactorily support the insurer’s claim decisio n and it
does not discharge the insurer’s onus of proof
the payment of the invoiced electrical costs plus the application of statutory interest
pursuant with section 57 of the Insurance Contracts Act 1984 fairly addresses any loss
caused by the insurer’s e rror.
1.3 Determination
This determination is in favour of the complainants.
Upon notification of the complainants’ acceptance of this determination, the insurer is to cover
the claimed electrical costs. The insurer is to apply statutory interest pursuant to section 57 of
the Insurance Contracts Act 1984 (Cth) from 11 August 2021 until payment is made. If an
excess has not already been obtained, the insurer is entitled to apply the applicable excess in
accordance with the policy terms.
Determination | Case number: 823211 Page 2 of 7
2 Reasons for determination
2.1 Can the insurer decline cover for the electrical costs?
No. The exchanged information shows damage occurred when water entered the
switchboard. I accept this was a sudden, unforeseen and unexpected event for the
complainants. The insurer has not sufficiently met its onus to establish an exclusion applies.
The insurer is required to accept the claim for electrical repair costs.
Complainants must first establish a valid claim
The complainants want the insurer to cover the cost of a new switchboard and associated
electrical wiring. The complainants provided an invoice from an electrician for $4,770.
When lodging an insurance claim, the complainants have the initial onus of proof to establish
the loss or damage claimed is covered by the policy terms. This is known as a valid (or prima
facie ) claim.
Once the complainants have established a valid claim, the onus shifts to the insurer to
establish, on balance:
a policy exclusion applies, or
it is otherwise entitled to decline the claim.
Policy provides cover for storm damage and accidental damage
The complainants’ policy provides cover for several listed insured events, including damage
caused by a storm. The complainants also have the optional cover for accidental damage.
This provides cover for ‘damage caused by sudden, unforeseen and unintended events’.
The complainants say they had severe weather over several weeks. One night there was a
deluge of rain causing water to enter the switchboard damaging the electrical wires and circuit
board. They called the power company who disconnected the power.
Complainants have established a claim for accidental damage
The attendance report from the power company confirms there were burnt wires and water in
the meter box. It also confirms the switchboard required replacement ‘due to water damage’.
The complainants organised an electrician (RT) to attend. RT provided a letter dated 23 July
2021 which states:
On further investigation we found significant water damage to the switchboard
causing it to be damaged beyond repair.
This switchboard required replacement. Our tradesman also used silicone to
ensure no more water would get it and to prevent any further issues happening in
the future. This has now been completed and all in working order. [sic]
While the insurer says the complainant has not established damage caused by a covered
event, t he insurer’s claim notes of 26 July 2021 say it reviewed the damage report and the
cause of damage is consistent with high rainfall in the area around the date of loss.
Determination | Case number: 823211 Page 3 of 7
There is no dispute water entered the meter box. On balance, I accept there is sufficient
information to establish damage to the switchboard and electrical wiring caused by a sudden,
unforeseen and unexpected event for the complainants. This is a covered event under the
policy.
The onus is therefore on the insurer to establish an exclusion applies, or it is otherwise
entitled to decline the claim.
Insurer says the cause was gradual deterioration
The insurer says the policy excludes cover for damage caused by depreciation, gradual
deterioration, wear and tear or lack of maintenance. It says RT’s report confirms silicone was
applied to the affected area to prevent further water ingress.
The insurer also says RT’s report initially stated:
On further investigation we found significant water damage to the switchboard
causing it to be damaged beyond repair. Water had entered into the switchboard
through the sealant which had deteriorated over time.
This is different to the above extract because it includes the comment that ‘Water had entered
into the switchboard through the sealant which had deteriorated over time’.
The insurer says that following its assessment, RT amended the report to remove the
commentary about the deteriorated sealant contributing to the damage, and this was at the
co mplainants’ request. In response , the complainants say the insurer contacted RT to amend
the report.
Comments about deterioration not contemporaneous with RT’s assessment
RT’s letter with the commentary about the deteriorated sealant is dated 1 0 August 2021. This
is after RT’s letter dated 23 July 2021, which was provided by the complainants and made no
mention of deterioration over time. It is also after another letter from RT dated 7 August 2021.
RT’s letter dated 7 August 2021 made no comment about the sealant deteriorating over time.
However, it included the following sentence which was not in the letter dated 23 July 2021:
‘Due to the damaged wires the entire switchboard required replacement’.
The insurer says:
It should be uncontested that [RT] have clearly and unambiguously provided that
Water had entered into the switchboard through the sealant which had
deteriorated over time.
Given the amended versions, I disagree.
The insurer also says:
If there is evidence which is readily available to but not tendered by one party (or
tendered and then withdrawn and revised), it is reasonable to draw an adverse
inference that the evidence is not supportive of their contentions or positions.
Determination | Case number: 823211 Page 4 of 7
Based on the exchanged information, the first edition of RT’s report was later revised. The
insurer’s claim notes show the addition of the commentary regarding the deteriorated sealant
came at the request of the insurer.
The claim notes show:
on 3 August 2021 the insurer contacted RT directly and the staff advised the attending
repairer would amend their report and resend to the insurer
on 6 August 2021 the in surer noted: ‘ Reviewed the report which stated "The switchboard
wasn't sealed properly, allowing water to seep in damaging the wires" ’
Neither party have provided a report to AFCA that states the switchboard was not sealed
properly. Even if they had, the insurer has not explained why this would be excluded.
The claim notes also show that on 10 August 2021 the insurer called RT again and discussed
the cause of damage. This time the claim notes state:
Called [RT] and spoke to them about the [cause of damage (CoD)]. They
confirmed CoD as being due to the sealant deteriorating over time water got in to
the fuse box. They also confirmed they provided a new report to the insured
removing mention of the sealant issue at the insured's request. They have now
sent an updated report that now states clearly that COD as being wear & tear.
It is not c lear if the ‘sealant issue’ RT removed reference to was that the switchboard was not
sealed properly, or that water had entered through sealant that deteriorated over time. These
are two different things.
Each letter from RT is addressed to the complainants. The insurer has not provided its own
report from RT. Given the various changes that appear to have been requested by both
parties, I consider the most contemporaneous report the more reliable. This is consistent with
the insurer ’s approach to drawing an adverse inference about revised evidence.
Based on the exchanged information, the most contemporaneous report is the one dated 23
July 2021. The copy provided to AFCA makes no reference to deteriorated sealant being the
cause of the damage.
RT’s r eport of 23 July 2021 confirms significant water damage to the switchboard. The
insurer’s claim notes of 26 July 2021 state the cause of damage is consistent with high rainfall
in the area around the date of loss. I am satisfied that this, in addition to the information from
the power company, establishes damage caused by a sudden, unforeseen and unexpected
event for the complainants.
I am not satisfied the comment that silicone was applied to the repaired switchboard
automatically means the cause of the damage was gradual deterioration, wear and tear or
lack of maintenance. I therefore do not accept the insurer has sufficiently established the
application of this policy exclusion.
Insurer’s further submissions do not assist
The insurer has recently provided a copy of the Bureau of Meteorology rainfall data for Perth
and says there was insufficient rainfall to cause the damage. The insured property is not in
Perth. I do not consider the rainfall data for Perth is an accurate reflection of the rainfall data
in the complainants’ location, or that it shows a covered event did not cause the damage.
Determination | Case number: 823211 Page 5 of 7
The insurer has more recently raised concerns that the damage was repaired before it was
given the opportunity to assess it. The insurer says this prejudiced the outcome and section
54 of the Insurance Contracts Act 1984 (Cth) applies.
The insurer has not explained how it has been prejudiced. While the damage was repaired,
the complainant took photographs of the damaged switchboard and provided a report from an
independent electrician. I am also satisfied the immediate repair of the property’s electricity
supply was necessary in the circumstances. I am not satisfied section 54 allows the insurer to
decline the claim.
The insurer also says the Wayne Tank principle applies to allow it to decline the claim. This
only applies where there are two or more concurrent causes of damage. The exchanged
information does not establish a concurrent cause exists.
Insurer to cover the electrical repair cost
For the reasons outlined above, I consider it fair in all the circumstances for the insurer to
cover the electrical damage and associated repair cost.
The insurer has not raised any concerns with the repair cost quoted by RT. Given this, and in
the interest of bringing finality to the complaint, I accept it is fair for the insurer to cover this
cost.
The insurer is required to add statutory interest pursuant to section 57 of the Insurance
Contracts Act 1984 (Cth). This is to be applied from 11 August 2021, the date of the insurer’s
decline letter, until payment is made.
If an excess has not already been obtained, the insurer is entitled to the applicable excess in
accordance with the policy terms.
2.2 Should the insurer provide further compensation?
While the insurer did not immediately process the claim for electrical damage correctly, I do
not consider an award of compensation for non-financial loss is appropriate in this instance.
Complainants want compensation for stress and inconvenience
The complainants raise concerns with the way the insurer handled the claim. They say it was
clear they wanted to claim for the electrical costs, but this was initially ignored by the insurer.
They also say:
the insurer did not pass on their supporting documents to the assessor, and
when they were advised their claim would be settled the assessor instead contacted the
electrician to amend their report.
The claim notes show there was confusion on the insurer’s behalf when the claim was initially
lodged. It was lodged as two separate claims, the insurer initially offered the incorrect limit for
food spoilage, and the insurer was unsure what insured event it would consider the claim
under.
Insurer not required to compensate complainants for their non-financial loss
I accep t the insurer’s initial handling of the claim caused a slight delay w ith the insurer’s
assessment and consideration of the claim. However, I am not satisfied it requires the insurer
to compensate the complainants for their non-financial loss.
Determination | Case number: 823211 Page 6 of 7
AFCA can award compensation for non-financial loss when there has been an unusual
amount of physical inconvenience, time taken to resolve a situation, or interference with the
complainant’s expectations of enjoyment or peace of mind. However, we will not award
compensation for the ordinary degree of inconvenience that comes with making a claim, or
when a problem arises.
It is clear the complainants were dissatisfied with the insurer’s claim decision. However, the
exchanged information does not show the insurer’s claims handling, as opposed to its claims
decision, caused any stress and inconvenience greater than that reasonably expected in the
circumstances. There was a slight delay in processing the electrical damage claim. However,
this did not cause any additional loss and the damage had already been repaired.
I accept the insurer’s d ecision was not supported by the information provided to AFCA.
However, this is addressed by the change in outcome and the application of statutory interest
under section 57 of the Insurance Contracts Act 1984 (Cth). I do not consider it appropriate to
compensate the complainants any further.
Determination | Case number: 823211 Page 7 of 7
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.