Storm/lightning damage claim to compressor declined under wear and tear and gradual deterioration exclusions; business interruption and claim preparation costs also refused
Text of the determination
Determination
Case number 811100
Financial firm AIG Australia Limited
Determination | Case number: 811100 Page 1 of 7
Case number: 811100 26 April 2022
1 Determination overview
1.1 Complaint
On 18 November 2019, the complainant lodged a claim with the financial firm (insurer) for
storm and lightning damage suffered to the compressor servicing the cooling system of his
small business. The complainant seeks $15,000 to repair the compressor and also:
business interruption costs for the loss of business gross profits $8,804
claim preparation costs of $24,000
The insurer declined the claim relying on the exclusions for gradual deterioration and wear
and tear.
1.2 Issues and key findings
Is the insurer entitled to rely on exclusions to deny the claim for damage?
Yes. The evidence supports the compressor failed due to corrosion, wear and tear and
gradual deterioration. This is excluded under the policy.
Is the complainant entitled to cover for business interruption and claim
preparation expenses?
No. In circumstances where the property damage claim has failed, the complainant is unable
to recover business interruption costs or claim preparation costs.
Why is the outcome fair?
Apart from the coincidence of the electrical storm happening around the time the breakdown
was reported, there is no evidence of lightning strike at the insured property nor of this
causing any nearby electrical failure. There is clear evidence of longstanding corrosion and
gradual deterioration. Accordingly, the outcome is fair.
1.3 Determination
The Determination is in favour of the insurer.
The insurer is entitled to decline the claim.
No further action is required.
Determination | Case number: 811100 Page 2 of 7
2 Reasons for determination
2.1 Is the insurer entitled to rely on exclusions to deny the
claim for damage?
Yes. The evidence supports the compressor failed due to corrosion, wear and tear and
gradual deterioration.
Complainant has established a claimable loss
It is established insurance law that an insured has the onus to establish on the balance of
probabilities (that is more likely than not) that the loss or damage falls within the terms and
conditions of the policy. This is known as a claimable loss. The onus of proof then switches to
the insurer if it wishes to rely on a policy exclusion.
Section 1 of the policy provides cover for accidental physical loss or damage to property that
occurs during the period of insurance. The policy does not define „ accidental loss or damage ‟
but this is generally accepted to mean damage that is unintended and unexpected.
The complainant says the compressor failed as a result of a significant weather event
including lightning, strong winds and heavy rainfall. The complainant‟s technician (AA) says
the damage was caused by a power surge. The insurer says the equipment was old and
corroded.
I accept the available information on either scenario confirms, the damage was unintended
and unexpected. Therefore, I am satisfied it falls within the terms of the policy and a claimable
loss has been established.
Insurer has established exclusions apply
The insurer relies on policy exclusions for loss or damage caused by wear and tear, gradual
deterioration, scratching, marring, developing flaws, normal upkeep or any gradual cause.
The storm occurred 17 November 2019. The complainant became aware his chiller had
stopped functioning. A circuit breaker had tripped. Both parties have referred to a
handwritten note which records 4pm 17 November “big comp cutting in and out.” There is no
reference in the note to lightning. The note belongs to the complainant and contains the name
of his refrigeration mechanic. It is not revealed who drafted the note nor are there statements
from the complainant as to what their staff observed at the time of the breakdown nor is there
a statement from its refrigeration mechanic.
The failed compressor was reported to the insurer the next day. A different air conditioning
mechanic (likely appointed by the insurer) attended on 21 November 2019 and reported the
“ cause of fault is from the Crimp type Spade terminal having a poor connection and in turn
created a high resistive joint. By the discolouration of the wire, the issue appears to be long
term and not a catastrophic failure ”.
The compressor motor supply wire/cable showing evidence of overheating and burning was
clearly photographed.
The parties rely on their respective electrical expert technicians to support their position.
Summaries of their reports are in section 3.2 below.
In brief:
Determination | Case number: 811100 Page 3 of 7
T he insurer‟s technical expert (TI) says the sub-board failure shows a high resistive
connection within the sub-board and this caused melting of the sub switchboard. TI says
this was a maintenance issue and is due to long-term deterioration. The compressor is 35
years old. Photographs show the compressor and componentry to be in a poor condition,
with substantial rust, corrosion, sludge and grime. A switchboard in another part of the
premises showed signs of overheating and was overdue for replacement.
T he complainant‟s ex pert (TC) says the storm induced locally generated voltage transients
within the electrical installation, and had it not been for the electrical storm, the motor
would still be operating. The lightning storm was extensive. There is evidence of 6,546
recorded lightning strikes within a 50km radius at the time of the loss. There was no
evidence of a direct lightning strike but the time on the handwritten note indicates stoppage
occurred during or just after the storm. AA, who regularly services the compressor, says
the equipment was in good working order before the storm. AA says the equipment was
old but operational.
I find the TI‟s evidence more persuasive than that of TC. The existence of long standing
corrosion on the spade terminal is obvious to the eye. TC relies on the coincidence of the
storm but there was no specific lightning strike observed to directly cause the breakdown. The
complainant said that one of the neighbouring properties reported lights flickering. However,
no other circuit breaker in the building was tripped and there was no power outage
experienced in the surrounding area. It would have been of assistance to have seen
maintenance records for the compressor. This does not appear to have been requested by
the insurer. In any event the insurer has satisfied the burden of showing the most probable
cause was from wear and tear, corrosion and gradual deterioration.
As these causes are excluded under the policy, the insurer can deny the claim.
2.2 Is the complainant entitled to cover for business
interruption and claim preparation expenses?
No. In circumstances where the property damage claim has failed, the complainant is unable
to recover business interruption costs or claim preparation costs.
Policy does not cover these costs
It is common ground that if the insurer is not required to grant indemnity for the above
property damage, then it is not liable for business interruption losses. The policy only
indemnifies business interruption where the insurer has paid for or admitted liability in respect
of such property damage under the relevant Policy Section. As the insurer has not done so, it
is not required to cover business interruption.
Similarly , claim preparation fees are not recoverable.
2.3 Why is the outcome fair?
Apart from the coincidence of the electrical storm happening around the time the breakdown
was reported there is no evidence of lightning strike at the insured property nor causing any
nearby electrical failure. There is clear evidence of longstanding corrosion and gradual
deterioration. Accordingly, the outcome is fair.
Determination | Case number: 811100 Page 4 of 7
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
3.2 Key findings from expert reports
Record Key points
Insurer’s expert (CA)
Inspection report
22 - 11 - 2019
Stage one system has an electrically failed semi - hermetic compressor.
The compressor motor windings were found to be electrically down to
earth. The motor windings were 1.4 ohms between each winding.
O ne of the compressor ‟s motor supply cables was found to be burnt from
the motor winding thermistor relay to the compressor terminal.
This indicate s the cause of fault is from the c rimp type s pade terminal
having a poor connection and in turn creating a high resistive joint.
By the discolouration of the wir e, the issue appears to be long - term and
not a catastrophic failure.
Determination | Case number: 811100 Page 5 of 7
Record Key points
Insurer ’s expert ( TI)
Technical report
25 - 11 - 2019
There is a previous long - term issue with the sub - board of unit 4. Its
sub - board failed months ago and was attended to by the complainant‟s
electrical contractor. However, the sw itchboard has not been replaced.
The failure of unit 4 sub - board is not subject to this claim, and TI do es not
believe it was the cause of the failure to the chiller system.
The sub - board failure shows a high resistive connection within the
sub - board was the cause of the melting of the sub switchboard. This is
considered a maintenance issue.
Identified it to be in a poor overall condition, with rust and corrosion evident
throughout the entire chiller system.
When one of the three motor windings fail from a n open circuit or a series
resistive effect resulting from a high resistive join, this creates an
imbalance of back [electromotive force] EMF in the motor.
Thus, the two remaining motor windings will draw more current than
specified , due to the lack of ba ck EMF.
This results in overheating of the windings which overheat the motor ,
shorting it down to earth.
TI cannot support the insured‟s contractor‟s theory the chiller compressor
failed due to storms or power surges.
The evidence has proven the compress or failed as a result of a high
resistive connection between the compressor and the thermal relay , which
is gradual det erioration and wear and tear.
Complainant’s expert
(TC)
A nalysis report
06 - 01 - 2020
The timing coincidence of the earth fault with an electrical storm cannot be
avoided as the proximate cause of the loss.
The storm will induce locally generated voltage transients within the
electrical installation , as the electrical equipment responds to dips,
flickering and brownouts that accompany sto rms.
Windings W1 & W2 were of similar resistance suggesting they had aged
similarly.
Winding W2 was ~ 12% out of balance suggesting it has aged
disproportionately when compared to the other two. It was, however,
undamaged.
The earth fault occurred on the W 1 winding which cannot be attributed to
age - related wear and tear or to the presence of the hot joint, as the
winding resistance of W1 appears unaffected.
Insurer’s expert (TI)
Technical report
19 - 01 - 2020
T ests identified the motor windings were electrically down to eart h.
T he motor showed a burnt motor supply cable between the motor and the
thermistor relay, which is caused by a high resistive connection on the
spade terminal of the thermal relay.
I f one of the three electrical mains power phases is not attached
(disconnected), or is damaged to the extent it will pass little or no current
to the windings of a 3 - phase motor, it is deduced the mot or :
> operates at a reduced speed and torque / relative power to the motor
> will experience vibrations due to the out of balance rot ational effect
within the motor.
This means t he windings to the motor are not able to withstand the
Determination | Case number: 811100 Page 6 of 7
Record Key points
inc rease in electrical current and heat.
When insulation is damaged to the windings within the motor , a short
circuit is created in the windings that cause the motor to burn.
When the m otor starts to overheat and burn, the varnish type insulation of
the windings become damaged, thus breaking open.
The damaged windings can then come in cont act with the body of the steal
electrical motor housing, again referred to as the stator. This is referred to
as an “Earth Fault”.
I t is proven there was a current resistive effect to the L3 [conductor] active
to the motor b eing in such a dest royed state and the other two windings
operating would have undoubtedly heated up d ue to a higher current draw
and a lack of back EMF.
The connection to the conductor , feeding power directly to one of the
motor windings in the 3 - phase motor , was in such a damaged state that
this damaged conductor would allow little to no current into the 3 - phase
motor for the winding this particular burnt conductor was attached to .
It seem s the „ thermostat ‟ placed within the motor windings to indica te to
the control circuit of higher than expected running temperatures, has:
> f ailed over time from general heat and 35+ years of age
> its thermostat circuit disconnected or bypassed from the control circuit ,
or
> t he thermal bimetal strips within the two overload units no longer
operational .
Complainant’s expert
( TC)
A nalysis report
09 - 03 - 2020
Electric m otors are very rarely damaged by induction effects, but more
likely by incoupling on the services lines.
[There were] 6 , 546 recorded lightning strikes within a 50km radius at the
time of the loss.
I t is highly unlikely the lightning strike at 3 . 15pm caused any direct damage
to the subject motor due to induction effects.
However, the damage did occur to the motor in response to supply voltage
fluctuations as a result of incoupling , as evidenced by the report of
„flickering lights‟. This indicates voltage fluctuations within the ins ured
electrical installation.
Essentially a flicker gives rise to stator curren ts that interact with the rotor
in terms of negative and positive damping giving rise to self - perpetuating
behaviour.
3.3 Terms of the policy
Policy section Policy terms
Policy section 1 -
property damage
Your insurance cover under thi s section
1.2 What You are covered for
You are covered for accidental physical loss of or damage to Your
Property Insured. We will pay You up to the Insured Amount for the
loss or damage to Your Property Insured at the Situation during the
Determination | Case number: 811100 Page 7 of 7
Period of Cover.
Exclusions applicable
to thi s section
1.42 We will not cover You for loss or damage caused by:
(a) wear and tear, gradual deterioration, scratching, marring,
developing flaws, normal upkeep or any gradual caus e;
(b) mechanic al, hydraulic, electrical breakdown or electronic failure
or malfunction;
(c) corrosion, rust, oxidation, any form of fungus, wet or dry rot,
dampness of atmosphere, variation in temperature,
evaporation, disease, shrink age;
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.