Storm/lightning damage claim to compressor declined under wear and tear and gradual deterioration exclusions; business interruption and claim preparation costs also refused

FirmAIG Australia Limited
Decided2022-04-26
ProductGeneral Insurance · Business / commercial
OutcomeFor the firm
Amount awarded—
Non-financial loss—
Amount claimed$47,804
SourceAFCA PDF

Summary

A small business claimed storm and lightning damage to its cooling system compressor, plus business interruption and claim preparation costs. AFCA found the compressor failed from corrosion, wear and tear and gradual deterioration, so the insurer was entitled to decline the claim and the consequential costs.

Damage caused by wear and tear, gradual deterioration, electrical breakdown or corrosion is excluded under the policy, and business interruption and claim preparation costs depend on the property damage claim succeeding.

Issues

Subjects and remedies

business interruptionsmall businessno remedy

Related

All AIG Australia Limited determinations · Find similar determinations

Text of the determination

Determination Case number 811100 Financial firm AIG Australia Limited Determination | Case number: 811100 Page 1 of 7 Case number: 811100 26 April 2022 1 Determination overview 1.1 Complaint On 18 November 2019, the complainant lodged a claim with the financial firm (insurer) for storm and lightning damage suffered to the compressor servicing the cooling system of his small business. The complainant seeks $15,000 to repair the compressor and also:  business interruption costs for the loss of business gross profits $8,804  claim preparation costs of $24,000 The insurer declined the claim relying on the exclusions for gradual deterioration and wear and tear. 1.2 Issues and key findings Is the insurer entitled to rely on exclusions to deny the claim for damage? Yes. The evidence supports the compressor failed due to corrosion, wear and tear and gradual deterioration. This is excluded under the policy. Is the complainant entitled to cover for business interruption and claim preparation expenses? No. In circumstances where the property damage claim has failed, the complainant is unable to recover business interruption costs or claim preparation costs. Why is the outcome fair? Apart from the coincidence of the electrical storm happening around the time the breakdown was reported, there is no evidence of lightning strike at the insured property nor of this causing any nearby electrical failure. There is clear evidence of longstanding corrosion and gradual deterioration. Accordingly, the outcome is fair. 1.3 Determination The Determination is in favour of the insurer. The insurer is entitled to decline the claim. No further action is required. Determination | Case number: 811100 Page 2 of 7 2 Reasons for determination 2.1 Is the insurer entitled to rely on exclusions to deny the claim for damage? Yes. The evidence supports the compressor failed due to corrosion, wear and tear and gradual deterioration. Complainant has established a claimable loss It is established insurance law that an insured has the onus to establish on the balance of probabilities (that is more likely than not) that the loss or damage falls within the terms and conditions of the policy. This is known as a claimable loss. The onus of proof then switches to the insurer if it wishes to rely on a policy exclusion. Section 1 of the policy provides cover for accidental physical loss or damage to property that occurs during the period of insurance. The policy does not define „ accidental loss or damage ‟ but this is generally accepted to mean damage that is unintended and unexpected. The complainant says the compressor failed as a result of a significant weather event including lightning, strong winds and heavy rainfall. The complainant‟s technician (AA) says the damage was caused by a power surge. The insurer says the equipment was old and corroded. I accept the available information on either scenario confirms, the damage was unintended and unexpected. Therefore, I am satisfied it falls within the terms of the policy and a claimable loss has been established. Insurer has established exclusions apply The insurer relies on policy exclusions for loss or damage caused by wear and tear, gradual deterioration, scratching, marring, developing flaws, normal upkeep or any gradual cause. The storm occurred 17 November 2019. The complainant became aware his chiller had stopped functioning. A circuit breaker had tripped. Both parties have referred to a handwritten note which records 4pm 17 November “big comp cutting in and out.” There is no reference in the note to lightning. The note belongs to the complainant and contains the name of his refrigeration mechanic. It is not revealed who drafted the note nor are there statements from the complainant as to what their staff observed at the time of the breakdown nor is there a statement from its refrigeration mechanic. The failed compressor was reported to the insurer the next day. A different air conditioning mechanic (likely appointed by the insurer) attended on 21 November 2019 and reported the “ cause of fault is from the Crimp type Spade terminal having a poor connection and in turn created a high resistive joint. By the discolouration of the wire, the issue appears to be long term and not a catastrophic failure ”. The compressor motor supply wire/cable showing evidence of overheating and burning was clearly photographed. The parties rely on their respective electrical expert technicians to support their position. Summaries of their reports are in section 3.2 below. In brief: Determination | Case number: 811100 Page 3 of 7  T he insurer‟s technical expert (TI) says the sub-board failure shows a high resistive connection within the sub-board and this caused melting of the sub switchboard. TI says this was a maintenance issue and is due to long-term deterioration. The compressor is 35 years old. Photographs show the compressor and componentry to be in a poor condition, with substantial rust, corrosion, sludge and grime. A switchboard in another part of the premises showed signs of overheating and was overdue for replacement.  T he complainant‟s ex pert (TC) says the storm induced locally generated voltage transients within the electrical installation, and had it not been for the electrical storm, the motor would still be operating. The lightning storm was extensive. There is evidence of 6,546 recorded lightning strikes within a 50km radius at the time of the loss. There was no evidence of a direct lightning strike but the time on the handwritten note indicates stoppage occurred during or just after the storm. AA, who regularly services the compressor, says the equipment was in good working order before the storm. AA says the equipment was old but operational. I find the TI‟s evidence more persuasive than that of TC. The existence of long standing corrosion on the spade terminal is obvious to the eye. TC relies on the coincidence of the storm but there was no specific lightning strike observed to directly cause the breakdown. The complainant said that one of the neighbouring properties reported lights flickering. However, no other circuit breaker in the building was tripped and there was no power outage experienced in the surrounding area. It would have been of assistance to have seen maintenance records for the compressor. This does not appear to have been requested by the insurer. In any event the insurer has satisfied the burden of showing the most probable cause was from wear and tear, corrosion and gradual deterioration. As these causes are excluded under the policy, the insurer can deny the claim. 2.2 Is the complainant entitled to cover for business interruption and claim preparation expenses? No. In circumstances where the property damage claim has failed, the complainant is unable to recover business interruption costs or claim preparation costs. Policy does not cover these costs It is common ground that if the insurer is not required to grant indemnity for the above property damage, then it is not liable for business interruption losses. The policy only indemnifies business interruption where the insurer has paid for or admitted liability in respect of such property damage under the relevant Policy Section. As the insurer has not done so, it is not required to cover business interruption. Similarly , claim preparation fees are not recoverable. 2.3 Why is the outcome fair? Apart from the coincidence of the electrical storm happening around the time the breakdown was reported there is no evidence of lightning strike at the insured property nor causing any nearby electrical failure. There is clear evidence of longstanding corrosion and gradual deterioration. Accordingly, the outcome is fair. Determination | Case number: 811100 Page 4 of 7 3 Supporting information 3.1 The AFCA process AFCA’s approach is based on fairness AFCA has determined this complaint based on what is fair in all the circumstances, having regard to:  the legal principles  applicable industry codes or guidance  good industry practice  previous decisions of AFCA or its predecessor schemes (which are not binding). The respective parties have completed a full exchange of the relevant information, and each party has had the opportunity to address any issues raised. We have reviewed and considered all of the information the parties have provided. While the parties have raised a number of issues in their submissions, we have restricted this determination to the issues that are relevant to the outcome. We assess complaints on available information and circumstances AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to require third parties to give evidence. When we assess complaints, we consider:  available documents  the recollections of the parties  all relevant circumstances. We give more weight to documents created at the time the events occurred. If there are no relevant documents, we will decide what most likely occurred based on the available information. If there are conflicting recollections and these are evenly weighted, we may find that a claim cannot be established. 3.2 Key findings from expert reports Record Key points Insurer’s expert (CA) Inspection report 22 - 11 - 2019  Stage one system has an electrically failed semi - hermetic compressor.  The compressor motor windings were found to be electrically down to earth. The motor windings were 1.4 ohms between each winding.  O ne of the compressor ‟s motor supply cables was found to be burnt from the motor winding thermistor relay to the compressor terminal.  This indicate s the cause of fault is from the c rimp type s pade terminal having a poor connection and in turn creating a high resistive joint.  By the discolouration of the wir e, the issue appears to be long - term and not a catastrophic failure. Determination | Case number: 811100 Page 5 of 7 Record Key points Insurer ’s expert ( TI) Technical report 25 - 11 - 2019  There is a previous long - term issue with the sub - board of unit 4. Its sub - board failed months ago and was attended to by the complainant‟s electrical contractor. However, the sw itchboard has not been replaced.  The failure of unit 4 sub - board is not subject to this claim, and TI do es not believe it was the cause of the failure to the chiller system.  The sub - board failure shows a high resistive connection within the sub - board was the cause of the melting of the sub switchboard. This is considered a maintenance issue.  Identified it to be in a poor overall condition, with rust and corrosion evident throughout the entire chiller system.  When one of the three motor windings fail from a n open circuit or a series resistive effect resulting from a high resistive join, this creates an imbalance of back [electromotive force] EMF in the motor.  Thus, the two remaining motor windings will draw more current than specified , due to the lack of ba ck EMF.  This results in overheating of the windings which overheat the motor , shorting it down to earth.  TI cannot support the insured‟s contractor‟s theory the chiller compressor failed due to storms or power surges.  The evidence has proven the compress or failed as a result of a high resistive connection between the compressor and the thermal relay , which is gradual det erioration and wear and tear. Complainant’s expert (TC) A nalysis report 06 - 01 - 2020  The timing coincidence of the earth fault with an electrical storm cannot be avoided as the proximate cause of the loss.  The storm will induce locally generated voltage transients within the electrical installation , as the electrical equipment responds to dips, flickering and brownouts that accompany sto rms.  Windings W1 & W2 were of similar resistance suggesting they had aged similarly.  Winding W2 was ~ 12% out of balance suggesting it has aged disproportionately when compared to the other two. It was, however, undamaged.  The earth fault occurred on the W 1 winding which cannot be attributed to age - related wear and tear or to the presence of the hot joint, as the winding resistance of W1 appears unaffected. Insurer’s expert (TI) Technical report 19 - 01 - 2020  T ests identified the motor windings were electrically down to eart h.  T he motor showed a burnt motor supply cable between the motor and the thermistor relay, which is caused by a high resistive connection on the spade terminal of the thermal relay.  I f one of the three electrical mains power phases is not attached (disconnected), or is damaged to the extent it will pass little or no current to the windings of a 3 - phase motor, it is deduced the mot or : > operates at a reduced speed and torque / relative power to the motor > will experience vibrations due to the out of balance rot ational effect within the motor.  This means t he windings to the motor are not able to withstand the Determination | Case number: 811100 Page 6 of 7 Record Key points inc rease in electrical current and heat.  When insulation is damaged to the windings within the motor , a short circuit is created in the windings that cause the motor to burn.  When the m otor starts to overheat and burn, the varnish type insulation of the windings become damaged, thus breaking open.  The damaged windings can then come in cont act with the body of the steal electrical motor housing, again referred to as the stator. This is referred to as an “Earth Fault”.  I t is proven there was a current resistive effect to the L3 [conductor] active to the motor b eing in such a dest royed state and the other two windings operating would have undoubtedly heated up d ue to a higher current draw and a lack of back EMF.  The connection to the conductor , feeding power directly to one of the motor windings in the 3 - phase motor , was in such a damaged state that this damaged conductor would allow little to no current into the 3 - phase motor for the winding this particular burnt conductor was attached to .  It seem s the „ thermostat ‟ placed within the motor windings to indica te to the control circuit of higher than expected running temperatures, has: > f ailed over time from general heat and 35+ years of age > its thermostat circuit disconnected or bypassed from the control circuit , or > t he thermal bimetal strips within the two overload units no longer operational . Complainant’s expert ( TC) A nalysis report 09 - 03 - 2020  Electric m otors are very rarely damaged by induction effects, but more likely by incoupling on the services lines.  [There were] 6 , 546 recorded lightning strikes within a 50km radius at the time of the loss.  I t is highly unlikely the lightning strike at 3 . 15pm caused any direct damage to the subject motor due to induction effects.  However, the damage did occur to the motor in response to supply voltage fluctuations as a result of incoupling , as evidenced by the report of „flickering lights‟. This indicates voltage fluctuations within the ins ured electrical installation.  Essentially a flicker gives rise to stator curren ts that interact with the rotor in terms of negative and positive damping giving rise to self - perpetuating behaviour. 3.3 Terms of the policy Policy section Policy terms Policy section 1 - property damage Your insurance cover under thi s section 1.2 What You are covered for You are covered for accidental physical loss of or damage to Your Property Insured. We will pay You up to the Insured Amount for the loss or damage to Your Property Insured at the Situation during the Determination | Case number: 811100 Page 7 of 7 Period of Cover. Exclusions applicable to thi s section 1.42 We will not cover You for loss or damage caused by: (a) wear and tear, gradual deterioration, scratching, marring, developing flaws, normal upkeep or any gradual caus e; (b) mechanic al, hydraulic, electrical breakdown or electronic failure or malfunction; (c) corrosion, rust, oxidation, any form of fungus, wet or dry rot, dampness of atmosphere, variation in temperature, evaporation, disease, shrink age;

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.