Home / QBE / Determination 810608
Determination 810608
Claim denial for submersible pump damage allegedly caused by power surge
Summary
A pastoral company claimed under its farm insurance policy for submersible pump damage it attributed to power surges. AFCA decided the complainant had not established the damage fell within the policy's power surge cover, and the insurer was entitled to decline the claim.
The complainant bears the initial onus to show the loss falls within the policy's insured events, and the evidence did not establish a power surge from an identifiable external source.
Issues
- Claim denial primary · not upheld“The complainant has not established the damage was caused by a power surge caused directly by an identifiable and verifiable source outside the home. The insurer is entitled to rely on the terms of the policy to deny the claim.”
- Inadequate claim investigation secondary · not upheld“I am satisfied the insurer has acted with utmost good faith in investigating the claim to determine the cause and extent of loss.”
- Delay secondary · not upheld“No. The claim was lodged on 21 April 2021... I am satisfied the insurer has acted fairly and appropriately in assessing the claim.”
Subjects and remedies
business interruptionhome or building damagethird party authorityno remedy
Related
Text of the determination
Determination
Case number 810608
Financial firm QBE Insurance (Australia) Limited
Determination | Case number: 810608 Page 1 of 7
Case number: 810608 6 May 2022
1 Determination overview
1.1 Complaint
The complainant, a pastoral company, holds a Farm Insurance policy with the financial firm
(insurer) that includes home and contents cover for several homes within the total farm
property.
In April 2021, the complainant lodged a claim for damage said to have occurred in or about
December 2020 to fix submersible pumps at TG, CG and GG due to fusion/power surge. The
insurer subsequently denied liability and says the complainant has not established the loss or
damage arose from power surge within the terms of the policy.
The complainant says there were numerous episodes requiring the reinstatement of dropped
fuses consistent with power surges. The complainant now says there is damage to pumps at
TG, CG, GG, WAG as well as the failure of miscellaneous water supply pumps.
The complainant also says that because of the insurer’s claims handling, it has suffered
consequential loss.
1.2 Issues and key findings
Did the insurer unreasonably delay the assessment of the claim?
No. The claim was lodged on 21 April 2021. The insurer ’ s loss adjuster (S) sought further
information from the complainant before appointing a technician (AES) to examine the cause
of damage. S has provided detailed reports on the technical findings with respect to the
damage to the pumps and assessment of the relevant invoices provided by the complainant. I
am satisfied the insurer has acted fairly and appropriately in assessing the claim.
Has the complainant established the claim falls within the terms of the policy?
No. The complainant has not established the damage was caused by a power surge caused
directly by an identifiable and verifiable source outside the home. The insurer is entitled to
rely on the terms of the policy to deny the claim.
Why is the outcome fair?
The outcome is fair as the available information does not support the complainant ’ s claim the
damage was the result of a power surge within the terms of the policy. It is fair the insurer is
entitled to rely on the terms of the policy to decline the claim.
1.3 Determination
This determination is in favour of the insurer.
The insurer is entitled to decline the complainant’s claim and need take no further action.
Determination | Case number: 810608 Page 2 of 7
2 Reasons for determination
2.1 Has the insurer unreasonably delayed the assessment of
damage?
No. The claim was lodged on 20 April 2021. The insurer ’ s loss adjuster (S) sought further
information from the complainant before appointing a technician (AES) to examine the cause
of damage. S has provided detailed reports on the technical findings with respect to the
damage to the pumps and assessment of the relevant invoices provided by the complainant. I
am satisfied the insurer has acted fairly and appropriately in assessing the claim.
There is no evidence that the insurer has unreasonably delayed the assessment
of damage.
The complainant says the damage was first identified in December 2020. The claim for
damage to three of the pumps at TG, CG and GG was first lodged on 21 April 2021. The
complainant now says the damage may have been caused by one or more of the outages
that have occurred at the property since 2019.
Following the lodgement of the claim, the insurer appointed the loss assessor S. S first
reported on 6 May 2021 and requested further information from the complainant. This
information was not immediately supplied.
On 22 June 2021, the complainant raised several concerns directly with S relating to S’s
advice to decline the claims. S has provided a detailed response on 9 July 2021.
The insurer then approved the appointment of a technician AES to examine the damaged
pumps. AES conducted the site inspection on 6 July 2021. The loss adjuster spoke with AES
and, the complainant’s electrician AT to clarify comments in the reports. S also reviewed the
invoices from AT before providing its second report in September 2021.
The insurer has relied on the reports to determine liability as little information has been
provided by the complainant to support the claim.
I am satisfied the insurer ’ s claims handling was fair and has not delayed the progress of the
claim. I am satisfied the insurer is not liable for any consequential loss that the complainant
claims.
2.2 Has the complainant established a claim within the terms of
the policy?
No. The complainant has not established the damage was caused by a power surge caused
directly by an identifiable and verifiable source outside the home.
Complainant has the onus to establish the claim falls within the terms of the
policy
It is established insurance law that an insured has the initial onus to prove on the balance of
probabilities (that is more likely than not) that the loss or damage claimed falls within the
cover provided under the terms of the policy. This is commonly called a prima facie claim.
Only once this has been established does the onus shift to the insurer to prove the application
of an exclusion should an insurer seek to refuse payment of the claim.
Determination | Case number: 810608 Page 3 of 7
The complainant’s policy is a Farm Insurance policy that provides a broad range of cover
including home and contents cover for the complainant’s farm properties at various locations.
The policy provides accidental damage cover for the property located at TG and insured
event cover for the properties located at HG, GG, WG, CG and WAG. The policy also
provides cover for farm property and machinery breakdown at the above properties plus at
location EG.
The complainant lodged a claim on 21 April 2021 for damage said to have occurred in
December 2020 to fixed submersible pumps at TG, CG and GG. The complainant has since
claimed additional damage at WAG with respect to a failed bore pump flow controller and
possible electric bore pump as well as the failure of miscellaneous house water supply pumps
as detailed in invoices provided by AT, an electrician.
Pumps are domestic appliances for purpose of the policy
The complainant says the various pumps in question are, for the purpose of the policy,
domestic appliances covered under the house and contents section of the policies. The
insurer does not disagree with this.
Under the listed events cover for the houses other than TG, there are 13 insured events
including:
Power surge to domestic appliances or domestic equipment directly caused by an
identifiable and verifiable source outside your home including:
A lightning strike, an object contacting power lines, resumption of power following
a blackout caused by a storm or unexpected interference with a power company
transformer by an animal, but not for loss or damage:
a) to domestic appliances or domestic equipment more than 15 years from date
of purchase when new; or
b) resulting from a power surge originating at the address.
The accidental damage cover for TG whilst providing cover for loss or damage that is
unexpected or unforeseen does not cover loss or damage caused by power surge except as
set out under the insured events section of the policy.
The complainant says the damage has been caused by numerous power outages due to
power surge and storm. The onus is therefore on the complainant to establish that the loss or
damage sustained as claimed has occurred because of power surge or another insured event
under the terms of the policy.
Complainant has provided limited information in support of its claim
The complainant says that because of storms and power outages at the property the pumps
have been damaged and therefore the insurer should be liable for the damage.
There is a quote from PEP to cover the costs of supplying a submersible pump dated 26
March 2021 for $10,057.32. It is unclear from the quote, to what location the quote relates.
The complainant has referred to a power failure report from its energy provider Essential
Energy covering a total of 14 outages at the property from 7 March 2019 to 21 August 2021.
The complainant says the power failure report confirms repeated loss of power to the property
Determination | Case number: 810608 Page 4 of 7
from remote events that are covered under the terms of the policy for power surge or storm
events. The information provided does not provide any significant detail of the events.
Four of the events are after December 2020 when the initial damage is said to have occurred.
The events listed do not refer to power surge or damage caused by power surge.
The complainant has relied on various invoices from its electrician (AT). The invoices relate to
service at the property from 16 July 2019 to 28 June 2021. A review of an excel spreadsheet
of the invoices refers to the repair of a pump at TG for $190 on 18 December 2020 and a
report on the solar pumps and hot water services. It does not refer to CG or GG pumps being
fused due to a power surge. It does not assist in identifying the cause of damage to the
pumps.
There is an email from AT dated 31 March 2021 that refers to having checked the
submersible pump at TG and finding it non-repairable which AT considered most likely the
result of an over voltage event such as a surge or lightning. The invoices would suggest that
the pump claimed was disconnected on 21 April 2021 some four months after the
complainant has claimed it was originally damaged and according to the invoices, replaced
for $190.
No other reports have been provided by the complainant to support its position.
Insurer’s reports dispute complainant’s claim
As the information supplied by the complainant did not identify the cause of damage, the loss
adjuster S appointed an electrical services company AES to conduct site and equipment
inspections. AES provided an initial report on 6 July 2021 and made the following comments
in his report:
Pump 1 TG – electric bore pump
incorrect resistance of windings, causing motor not to be operational
under load
looks to have happened by a surge within the windings which could have
been by storm damage
Pump 2 CG – House Bore
Pump had been dismantled
Found to have unbalanced windings
Looks to have occurred due to a surge within the system, could have
been caused by a storm event.
Pump 3 GG – Solar Pump
Bore fault to be due to low water sensor activated.
Pump 4 SG – Air pumps
Fault being caused but contact being fused open.
Unit repaired.
Pump 5 WAG – Electric Bore Pump
Presents fusion of electrical components within switch
This could have been caused by a spike in power due to a storm event.
Determination | Case number: 810608 Page 5 of 7
AES concluded however that due to not being the first responding technician on the site for
each bore pump, it was quite difficult to tell if damage to each system had been caused from
storm, wear and tear or just general breakdowns.
S subsequently had discussions with AES as to the cause of damage. A transcript and call
recording of those discussions has been exchanged between the parties and I do not propose
repeating contents of those discussions in detail. AES confirmed during the call that it was
unlikely that the damage at TG was due to a power surge and that the damage at CG and GG
was most likely mechanical or machinery breakdown which is not covered under the terms of
the policy.
S also spoke with the complainant’s electrician AT. According to the information provided, AT
advised that only the tail cable of the pump was tested and that the motor starts about 50% of
the time and then locks up at certain times. AT confirmed the complainant has approximately
40 submersible pumps in use and he was first informed about the issue at TG approximately
12 months ago (approximately June 2000). AT had little other information as to the damage to
the pump at TG.
The insurer says information supports the insurer’s finding that:
the cause of damage to the bore pump at TG cannot be determined but it is unlikely an
external power surge, lightning or storm was the cause of damage. An insured event has
not been established for this loss
the pump at CG was most likely damaged by machinery breakdown or fault. As it is a
pump used for domestic and residential purposes, the cover does not extend to cover
machinery breakdown or fault
the pump at GG was most likely damaged by low water or sensor fault. Such damage is
considered a machinery fault and is not caused by power surge. Machinery fault is not an
insured event under the terms of the policy.
Complainant has not established claim falls within the terms of the policy
I agree with the insurer ’ s position and am not satisfied the complainant has established the
damage claimed in April 2021 falls within the terms of cover provided by the policy.
I am not satisfied the complainant has provided sufficient information to establish that the
pumps were damaged by a power surge directly caused by an identifiable or verifiable source
outside of the home.
During the complaint to AFCA the complainant has also claimed for damage to pumps at
WAG and throughout the farm properties. The available information does not indicate that any
actual claim has been lodged with the insurer for that damage. I note however that AES
reported fusion damage was considered likely at WAG. It is unclear whether this damage has
been investigated further. It is also unclear whether the pump at WAG was a pump for
domestic use or farm use.
The insurer entitled to deny liability for the claim
The insurer is entitled to deny liability as the complainant has not established a claim that falls
within the terms of the insured events covered under the policies or under the accidental
damage cover provided to TG. The information exchanged is not sufficient to establish the
damage was caused because of a power surge within the terms of the policies. As no claim
appears to have been lodged with the insurer for damage to the pumps at WAG and other
pumps, it is not appropriate to make any findings with respect to that part of the complaint.
Determination | Case number: 810608 Page 6 of 7
2.3 Why is the outcome fair?
There is no dispute that the relevant policy documentation has been provided to the
complainant or that the complainant has had the opportunity to review and assess the level of
cover.
While the complainant has raised issue with respect to cover for machinery breakdown,
machinery breakdown is not covered under the home and contents section of the policy under
which the claims are lodged.
As the complainant’s claim is for damage to domestic appli ances, then I am satisfied it is fair
that the insurer relies upon the terms of cover under the home and contents sections of the
policy in determining the extent of its liability.
In the absence of evidence establishing that the loss or damage was caused by an insured
event, in this claim, power surge, I am satisfied that it is fair that the insurer is entitled to rely
upon the terms and conditions of the policy to refuse payment of the claim.
I am also satisfied that the insurer has acted with utmost good faith in investigating the claim
to determine the cause and extent of loss. In the absence of any additional information from
the complainant, I am satisfied the insurer has acted reasonably in denying the claim.
Determination | Case number: 810608 Page 7 of 7
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all the information the parties have provided.
While the parties have raised several issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.