Denial of additional water damage claim (wear and tear, gradual deterioration, settling, shrinkage)
Text of the determination
Determination
Case number 795900
Financial firm AAI Limited
Determination | Case number: 795900 Page 2 of 21
Case number: 795900 21 March 2022
1 Determination overview
1.1 Complaint
The complainant holds a home and contents insurance policy with the insurer.
The complainant lodged a water damage claim as a result of a leaking pipe on 12 March
2014. The insurer assessed the damage and accepted liability for the resultant damage
caused by the water leak. Upon obtaining quotes for its portion of liability, the insurer cash
settled the claim upon completion of its assessment.
The complainant says following the drying out period it contacted the insurer and advised that
additional damage has occurred. The insurer reviewed the additional damage and denied
liability on the basis it was not caused by an insured event.
The complainant is dissatisfied with the outcome and seeks $172,836.40 to repair the home
and resolve the dispute.
1.2 Issues and key findings
Can the insurer deny cover for the additional damage?
Yes. This is because the available information shows the additional damage was caused by
wear and tear, gradual deterioration, settling, or shrinkage. These are excluded under the
policy.
1.3 Determination
This determination is favour of the insurer.
The insurer can deny the claim for additional damage and is not required to take any further
action.
Determination | Case number: 795900 Page 3 of 21
2 Reasons for determination
2.1 Can the insurer deny cover for the additional damage?
Complainant has established a valid claim
The complainant must establish, on the balance of probabilities, he suffered a loss caused by
an event to which the policy responds. This is known as a valid claim.
The policy covers specific insured events, including escape of liquid. The policy also covers
accidental damage should the additional cover be taken. The certificate of insurance confirms
the complainant has opted for this additional cover.
Accidental loss, for the purposes of the policy, means ‘loss that is sudden, unforeseen and
occurs without intent’.
If the complainant establishes a valid claim, then the insurer has the onus of establishing
exclusions apply which would entitle it to decline the claim.
The complainant says additional damage was caused by a leak associated with their ducted
heating system. This was identified around early 2016. This was a different leak to the one
lodged in 2014 which involved a leaking sprinkler and where the resultant damage was
accepted by the insurer.
There were also issues discovered in the sewer and stormwater systems in between these
two dates. However, the complainant does not say the additional damage was caused by this.
The insurer disputes any of these events caused the additional damage. The insurer says the
cause of the additional damage is wear and tear, inherent defects, gradual deterioration,
settling, and shrinkage, which are factors excluded under the policy.
Insurers position and expert reports
The insurer’s expert evidence comprises of a leak detection report by G, a builder’s report by
A and numerous engine er’s reports from C, F and MC.
C was engaged to assess the leak in 2014. C concluded some of the movement and cracking
damage was caused by the leaking sprinkler. However, C identified other damage that could
not be related to this. This included external cracks to the western elevation and some
internal cracks. C recommended a six month drying out period prior to commencing repairs.
The insurer cash settled the resulting damage.
Once the 6-month period had elapsed, C reattended to complete a further inspection. The
complainant advised in this time the damage had worsened and C engaged plumber G to
complete a leak detection test. G did not identify any leaks from the water supply pipes.
However, numerous issues were detected to the sewer and stormwater pipes.
C’s subsequent report confirmed damage to the north half of the west wing had worsened
due to escape of liquid from the sewer and stormwater pipes and the damage to the south
half of the west wing has worsened due to the drying effect of adjacent trees. C advised the
defective pipework required repairs and a further one year drying out period was required.
The complainant says the damage to the pipes were caused by movement of the footings due
to the initial burst pipe. C disputes this. C says the damage to the pipes is from seasonal
differential ground movement, long term dilapidation, and the drying effects of nearby trees.
Determination | Case number: 795900 Page 4 of 21
The insurer appointed builder A to inspect the ductwork. A confirmed the system was leaking
and rusted. The insurer then engaged engineer (F) to review the information. F concluded
that the leak in the ducted heating system caused damage to the timber core boards directly
below the header of the air conditioner.
F stated they believe the remainder of the damage to the home had occurred due to
differential footing movement and the general nature of the construction of the house. F
further advised they largely agreed with C’s findings regarding the sewer and stormwater
pipes and movement. In addition, F did not agree the leaking ducting system would have
caused the damage as there was no localised heave.
The insurer received a report from engineer MC dated 22 June 2021 following their
attendance. In their report, MC did not agree the leaking ducted system caused the damage.
MC outlined a range of issues unrelated to this that caused the damages. This included poor
site drainage, the close proximity of trees and vegetation, seasonal moisture variation,
absence of articulation joints, the construction of various items, long-term wear and tear and
maintenance issues. The findings of this report can be found in section 3.3 of this
determination.
Complainant’s experts say damage is related to claimed event
The complainant provided a report from plumber H disputing the findings of the in surer’s
plumber G. H says some tree roots were found in both sewer and stormwater drains. H says,
however, no breaks or collapses were found in the pipes and fittings. H also says the sewer is
not blocking or holding water on a regular basis or flooding back to the building. H says
stormwater pipes are laid flat and will hold water should it become blocked. H is of the opinion
neither of the issues identified with these drains would have caused movement to the home
and that regular maintenance of these pipes will keep both drains clear.
The complainant provided several reports from an engineer LP to support his position. LP
believes the additional damage was caused by the ducted system. In LP’s latest report dated
27 October 2020, he says previous floor levels taken by F indicate localised heave along the
northern wall of the family room and kitchen. LP notes this area is not adjacent to abnormal
moisture conditions such as the leaks found by the insurer’s experts. LP notes that as the
timber core board lining under the ducting has been removed due to water damage, moisture
egress from the ducting cannot be dismissed.
Insurer can deny the claim
Having carefully considered all of the available information, the panel notes the following.
LP’s evidence is not p ersuasive in showing the additional damage was caused by the leaking
ducted system. LP’s reports are brief. They do not consider and address all factors, such as
the site drainage or localised trees and vegetation. These are plainly relevant factors when
assessing the cause of foundation movement.
At least two engineers engaged by the insurer (F and MC) have provided detailed and
considered reports about the damage claimed. They included photos and other evidence to
show a range of factors causing the damage claimed. These include:
site drainage issues allowing excessive moisture into the foundation:
localised effect of trees
lack of articulation joints in the brickwork
evidence of deterioration
Determination | Case number: 795900 Page 5 of 21
These conclusions are plausible and logical. Whilst the complainant went through these
reports to challenge various findings, his submissions were not substantiated by his expert
reports. The panel is not prepared to place weight on the complainant’s opinion given he is
not an expert on the issue in question.
Further, there is no clear evidence the leak in the ducted system was as extensive as the
complainant claims such that it could result in the widespread movement and cracking
damage claimed. The insurer’s experts expressed several reservations about this. LP’s
reports do not clearly identify that the leak was extensive enough to reach the founding soils
and result in the widespread movement and cracking damage.
Given all this, the panel is persuaded the additional damage being claimed was likely caused
by either wear and tear, gradual deterioration, settling or shrinkage. As these all fall within
policy exclusions, the insurer is entitled to deny the claim.
Determination | Case number: 795900 Page 6 of 21
3 Supporting information
3.1 The AFCA process
AFCA’s approach is based on fairness
AFCA has determined this complaint based on what is fair in all the circumstances, having
regard to:
the legal principles
applicable industry codes or guidance
good industry practice
previous decisions of AFCA or its predecessor schemes (which are not binding).
The respective parties have completed a full exchange of the relevant information, and each
party has had the opportunity to address any issues raised. We have reviewed and
considered all of the information the parties have provided.
While the parties have raised a number of issues in their submissions, we have restricted this
determination to the issues that are relevant to the outcome.
A panel determined this matter
Due to the nature of this complaint, we referred it to a panel for determination. The panel
includes:
an ombudsman
a member with significant experience in consumer and small business advocacy
a member with extensive experience as a [field of expertise].
We assess complaints on available information and circumstances
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence.
When we assess complaints, we consider:
available documents
the recollections of the parties
all relevant circumstances.
We give more weight to documents created at the time the events occurred. If there are no
relevant documents, we will decide what most likely occurred based on the available
information.
If there are conflicting recollections and these are evenly weighted, we may find that a claim
cannot be established.
Determination | Case number: 795900 Page 7 of 21
3.2 Relevant policy exclusions
Record Key points
PDS
Page 53 - 54
I n respect of all sections in the policy, we will not cover you for
damage, loss or liability caused by, arising from or involving any of
the following:
Wear and tear, lack of maintenanc e or inherent defect,
including gradual det erioration.
Rust, corrosion, mould, mildew, wet or dry rot, rising damp
and damage caused by your failure to keep your home in
good order and repair.
The action of trees or their roots.
Structural def ects or faulty workmanship, settling, shrinkage
or expansion.
3.3 Relevant expert reports
Record Key points
Determination | Case number: 795900 Page 8 of 21
Financial firm’s expert (C )
Report
5 May 2014
CONCLUSIONS:
The soil in the vicinity of northern Victoria is known to contain
reactive clay. An increase in moisture content of such soil will
result in swelling, causing heave of foundations.
Conversely, a decrease in moisture content will result in
shrinkage, causing settlement of foundations .
It is our opinion that differential movement of the building had
occurred as a result of variance in moisture content of the
reactive clay soil underlying the foundations. The
differential movement had caused the observed damage to the
residence.
We obse rved no evidence to suggest that the building structure
or foundations had been compromised. In our opinion the
damage is cosmetic in nature.
The movement to the building had occurred due to various
contributing factors, as noted below:
Heave from the irri gation system:
Normal irrigation of the property surrounding the building would
result in localised inc rease in moisture content of soil areas
which are irrigat ed. The leak in the irrigation system would have
caused a concentrat ed increase in moisture to s oil in the vicinity
of the leak and this would have exacerbated heave of the
northern elevation of the western wing.
The heave from the irrigation is evident on the contour plan,
with most significant heave occurring to foundations of the en -
suite and en - s uite toilet.
Settlement from the trees:
Trees located near the building would have had a drying effect
on soil under the building footprint, resulting in settlement of the
foundations. This is also evident on the contour plan, with areas
of settlement coin ciding with the location of trees and shrubs
adjacent to the south and south - west of the western wing.
Mode of Damage:
Comments by the Insured were consistent with the observed
damage and the expected series of events which would have
occurred following th e pipe leak.
It is our opinion that the events and damage had occurred in the
following order:
1. The growt h of trees located to the south and south - west of
the building resulted in gradual settlement of foundations
located near the trees, resulting in the observed cracks to the
brickwork of the western elevation and internal cracks to the
southern wall. This foundation movement also caused tension
within the ceiling, in a north south direction. This movement
would have occurred over a period of several yea rs,
steadily increasing over time with increased moisture demand
as the trees grew.
2. Normal irrigation and leakage of the irrigation system would
have caused a localised inc reas e in moisture, resulting in heave
of the northern elevation of the western wi ng
of the building. This would have res ulted in the observed
movement to laundry wall tiles, the crack to the brickwork of the
northern elevation and misalignment of the laundry doors. This
would also have caused compression within the ceiling of the
build ing in a north - south direction. In our opinion the damage
associated with the irrigation leakage would have occurred
within a period of bet ween several days to
four weeks from when the leak first developed.
3. Following the repair of the irrigation system the soil under the
Determination | Case number: 795900 Page 9 of 21
Financial firm’s expert (G )
Report
18 December 2014
WATER SERVICE
There are two water servic es to the property No1 as per drawing,
feeds the garden taps and toilets which has been
pressure tested at 350kpa (t own pressure) and held for
approximately 1hr and no leaks. No2 as per drawing feeding all
other fixtures in house, has been tested at 350kpa also and held for
approximately 1hr and no leaks.
SEWER PIPES
Sewer drains are earthenware 100mm (clay pipes) and through
CCTV vision they are in poor condition due to tree roots
entering drain through joins and I.O.S and cracks for approximately
22mtrs heading north away from back of house towards
main. We have no footage of internals of pipes due to excessive
tree roots filling camera head. We have loc ated via radio
detection and marked the most effected spots on sewer plan and
numbered for reference.
No1 - Tree roots found at bottom of bend where the camera was
placed down drain.
No2 - At 3mtr and 5mtr I.O junctions have roots entering drain.
No3 - 9mt rs and 10mtr tree roots are entering through joins.
No4 - 13mtr and 15mtrs roots entering through cracks in pipe
No5 - 22mts I.O bend is full of roots.
STORMWATER
Have sent CCTV up the stormwater pipe and again could not take
footage due to large amounts o f debris and tree roots
entering pipe through cracks and joins. Have located as Far as
possible and marked on sewer plan and numbered for
reference.
No6 - Stormwater pipe is earthen ware 100mm pipe, the whole
length of this pipe is in very poor condition a nd has
collapsed at the 33mtr mark.
Please note that the renewal of either the stormwater pipes or sewer
drains would be extremely diffic ult due to limited
access to side and rear of property. They both (stormwater and
sewer) would most likely have to be h and dug.
NOTE: I believe it would be a good idea to have a sewer machine
put down that drains wit h a root cutter on it and then recamera
the drains so that they can be inspected more thoroughly to
establish whether or not the cracks are letting water
seep into the surrounding area.
Financial firm’s expert (C )
Report
22 December 2014
CONCLUSIONS
It is our opinion that the damage to the north half of the west wing of
the Insured’s residence has worsened over the past 6 months as a
result of escape of water from the Insured’s sewer and stormwater
pipes (which are partially blocked with trees roots).
In our opinion, the damage to the south half of the west wing has
wors ened over the past 6 mont hs as a result of the drying effect of
Determination | Case number: 795900 Page 10 of 21
the adjac en t trees.
The comparison of floor levels taken in May and December 2014
confirms our opinion that the damage has worsened over the past 6
months.
Accordingly we do not recommend that repair works are undertaken
at the Insured’s residence at this time, as da mage is likely to re -
occur.
RECOMMENDATIONS
We reiterate the rec ommendations of our first report that all
defective plumbing is to be repaired (blocked and leaking sewer and
stormwat er pipes should be replac ed), and that the drying effect of
trees is addre ssed.
The Insured should refer to the CSIRO Document BTF18 –
Foundation Performance: A Homeowner’s Guide, which
Financial firm’s expert (C )
Report
14 January 2015
RESPONSE TO INSURED’S QUEERY
We understand that the leaking sprinkler was repaired on
12/03/ 2014 and that the leaking sewer and stormwater pipes are yet
to be repaired.
The leak to the sprinkler was discovered on 12/03/2014 while the
leaking sewer and storm water pipes were identified on 18/12/2014.
No evidence was observed (during either o f our two inspections)
that would allow us to determine when the leaks to the sprinkler,
sewer or storm water pipes first occurred and when tree roots first
entered the pipes.
It is the Insured’s opinion that escape of water from the first of the
three pip es to leak (the sewer, the stormwater or the sprinkler)
caused differential ground movement which caused damage to the
other two pipes (which subsequently leaked as a result of the
damage).
Refer to Figure 1, which shows five locations where the sewer pipe s
are leaking. At least two of the leaks to the sewer are not located in
close proximity to the leaks to the stormwater or the sprinkler.
Therefore, it is our opinion that the leaks to the sewer were not
caused by ground movement as a result of escape of w at er from the
stormwat er or sprinkler pipes. Accordingly, it is our opinion that the
sewer pipes were the first of the three pipes to leak.
In our opinion, the damage to the sewer pipes was caused by
seasonal differential ground movement, long term dilapid ation and
the drying effect of the adjacent trees.
It is our opinion that the primary causes of damage to stormwater
pipe were seasonal differential ground movement, long term
dilapidation, the drying effect of the adjacent trees and the
secondary cause of damage was escape of water from the sewer
pipes.
We understand that the escape of water from the sprinkler occurred
as a result of the sprinkler head being dislodged. It is our opinion
that the damage to the sprinkler head is not related to differential
g round movement and was not caused by an escape of water
Event.
Determination | Case number: 795900 Page 11 of 21
Whilst the footings to the residence have moved as a res ult of
differential ground movement, the footings are not located in close
proximity to the leaks in the stormwater or sewer pipes. It is
therefore our opinion that the movement of the footings did not
cause the leaks to the sewer or stormwater pipes.
Financial firm’s expert (C )
Report
14 January 2015
CONCLUSIONS
We reiterate our previously advised conclusions that it is our
opinion that the damage to the north half of the west wing of the
Insured’s residence occurred as a result of escape of water
from the Insured’s sewer and stormwater pipes and the
sprinkler pip e.
In our opinion, the damage to the south half of the west wing
occurred as a result of the drying effect of the adjacent trees.
RECOMMENDATIONS
We reiterate the rec ommendations of our first report that all
defective plumbing is to be repaired (blocked an d leaking sewer
and stormwater pipes should be replac ed), and that the drying
effect of trees is addressed.
We note that the sewer and stormwater pipe leaks have not
been repaired and that the drying effect of the adjacent trees
has not been addressed.
Financial firm’s expert (A )
Report
14 March 2016
Loss Cause: Escape of Liquid
- An expert building report was required to attend site and assess
the damage to the subfloor ducting, using CCTV. In order to
determine the full extent of the damage due to the burst heating
coil, the duct work and heating coil above the ground level will be
removed and the duct work inspected.
- The heating system unit is situated in the plant room, at the east
end of the house . The plant room hous es the heating coil. Air is
pushed past the heating coil and travels down through the
ducts. The ducts run under the concrete slab and feeds small vents
in each room. The ducts beneath the flooring are made of three
zones. The first du ct runs to the eastern zone, the second
through the middle zone (kitchen/living area) and the third zone
travels the entire length of the house and feeds the western end of
the house.
On Attendance:
- Upon attendance to site, a plumber and additional trade were
required to attend site in order to assess the heating unit and duct
work.
- The Insured advised they had a leaking pipe on the coil, which is
situated in the plan room. They advised they had no knowledge of
how long the wat er was leaking for, howeve r they
believe it was ongoing for a long period of time, which had
increased their water bill quite significantly.
- Upon attendance, the wat er to the coil was turned off and the
ducts had dried out. A camera was installed down each end on the
three separa te ducts, and the rust damage was found in all ducts.
Determination | Case number: 795900 Page 12 of 21
- Most of the duct work was in good order but on joints and junction
points, there is a definite sign of rust.
- The rust and deterioration is a result of water flooding int o the duct
work, which is evi dent due to the water levels in the duct. The
bottom of the duct is dirty and discolored, whilst the top
of the duct is clean. This appears to be caused by the pipe being
half filled with water.
- The Insured advised there have been some severe movement si n
the area of the property. Therefore it’s believed that the movement
could be a result of the leaking water out of the coil in
the plant room, which was running down the duct work and into the
sub floor.
- There was no disconnection of the metal duct work in the plant
room, confirmed from inspection of the wat er flooding out of the coil
area and into the plant room cellar.
- As the metal duct work in the plant room has to be dismantled to
repair the coil, it is recommended that the metal duct be removed in
order to inspect the leaking coil. This would allow greater access to
install a camera and ins pect the three ducts beneath the hous e.
This would confirm the condition of the duct work and provide the
route the wat er has travelled.
- Please not e: There is a map attached, with circles indicating where
the rust is evident.
- We have re - attended to conduct the authorized exploratory works
to the property.
- On attendance, we have met with the ins ured and proceeded to
pull out the large duct over the coil. This coil sits over the large duct
that runs under the house approximately 1m x 1m. On
pulling the duct apart, we were able to view the leak on the header
pipe of the duct.
- It appears the coil has leaked and the water has leaked onto the
duct. Once the water has entered the duct work it can travel along
the duct work, which travels the length of the house.
- This duct is meant to be air tight, but is not water tight. It is
believed that the water has leaked out of the joins in the duct. The
worst of these lea ks would be in the middle of the house where
the large square duct meets the round duct.
- As the duct is so big we were able to gain access and view the
duct. The duct is divided up int o three sections. They have used
chip board to divide the ducts into th ree.
- The leaking water has rotted the chip board causing the chip board
to collapse. This chip board is lying on the bottom of the 1m x 1m
duct.
- The coil requires repair and the duct work requires
repair/modification. The duct opening has been covered with chip
board to stop vermin and cold air, however the ins ured is without
heating.
Financial firm’s expert (F )
Report
5.0 Conclusion
5.1 It is F’s opinion the leak in the water filled heat er coils of the
Determination | Case number: 795900 Page 13 of 21
20 June 2016 ducted heating system located in the equipment room
discovered in February 2016 did cause damage to the timber
core boards directly below the header of the air conditioner as
discussed in paragraph 4.16 this report. (The timber core
boards divide the brick culvert into three separate air con ditioner
zones.)
5.2 It is F’s opinion that except for the damage to the timber
core boards directly below the header of the air conditioner, the
leak in the water filled heater coils of the ducted heating system
did not cause, nor contribute to, the damag e to the subject
house as discussed in paragraphs 4.1 to 4.8 of this report.
5.3 It is F’s opinion that except for the damage to the timber
core boards directly below the header of the air conditioner, the
damage to the house has been caused by differentia l footing
movement and the general nature of construction of the house,
as discussed in paragraph 4.18 of this report.
Financial firm’s expert (F )
Report
11 July 2016
1.2 Leak Related Damage
(1) At the time of the leaks the HOUSE was OCCUPIED.
(2) Based on the visual non - intrusive inspection of the building
carried out by DE, Forensic Engineer at F, on 6 June 2016, the
damage caus ed by the leaks includes, but is not necessarily
limited to, the following:
Vertical crack up to 8mm wide located on the nort h wall
outside the toilet [1].
Binding door located on the nort h wall of the laundry [2].
Vertical crack to brickwork located at the northwest
corner of the dressing room [3].
Plaster joint to the ceiling has opened located in the hall
[4].
Plaster joint to the ceiling has opened located between
bedroom 1 and the dress room [5].
Damage to tile grout of the north wall of the laundry [6].
Typical separation of the hallway ceiling [7].
Damage to the ceiling trim and the door frame of
bedroom 1 [8].
Horiz ontal cr ack to internal double brick wall shown
typically located in the walk - in - robe [9].
Binding window located in the ensuite.
1.3 Building Defects and Damage not related to the leaks.
(1) In F’s opinion the following observed building defects and
damage are no t relat ed to the leaks which includes, but is not
necessarily limited to, the following:
External brick wall cracks to the western elevation.
Internal cracks to walls at the southern side of the
bedrooms and master bedroom.
1.4 On - going Building Movement
(1) It must be understood that, after the repairs specified in this
SOW have been completed, ongoing building movements and
associated future damage may occur for the following reasons:
Determination | Case number: 795900 Page 14 of 21
The clay soils at the subject site are reactive, and hence
differentia l variations in soil moisture contents will result
in differential foundation soil movements. Thes e soil
moisture variations can occur due to seas onal weather,
soil desiccation by the roots of nearby trees, variations
in paving conditions around the buildi ng, soils restoring
‘normal’ moisture contents once the site improvement
works have been completed, and the like.
It may not be practicable to ‘maintain’ the site strictly in
accordance with the recommendations provided in the
Australian Standard AS2870 - 20 11 Residential slabs
and footings, and the CSIRO publication BTF 18
Foundation Maintenance and Footing Performance: A
Homeowner’s Guide.
Financial firm’s expert ( MC )
Report
22 June 2021
9.0 Conclusion
9.1. My instructions were to inspect and report on the following:
Attend site and submit a report.
Please attend to inspect the claimed damage and compile a
scope of works of claim related damage.
For all damage that is not covered, please state why.
9.2. The following findings are based upon the evidence
pr esented and these should be read in conjunction with the
preceding comments in the body of this report.
9.3. MC cannot provide comment in relation to policy coverage
in relation to damage.
9.4. The proximate caus e of the damage as outlined by the
Insured i s provided below for your reference and policy
determination.
Proximate Cause and Effect
9.5.1. BRI CKWORK CRACKI NG:
9.5.1.1. Cracking to the external brickwork is a result of the
cumulative effect of the following issues that have been pre -
existing and dev eloping over a long period of time, resulting in
moisture variations of the underlying soils causing subsequent
long - term building movement reflecting to brickwork cracking:
9.5.1.1.1. The close proximity of significant trees, shrubs and
vegetation drying out the underlying soils.
9.5.1.1.2. The removal of significant trees altering/hydrating
underlying soil conditions.
9.5.1.1.3. Ground surface levels graded towards the home
allowing surface stormwater run - off to flow towards and seep
into the underlying f ounding soils causing soil moisture
variations.
9.5.1.1.4. The absence of a surface stormwater drainage
system to collect surface water run - off exacerbating the volume
of water seeping into the underlying soils.
9.5.1.1.5. The close proximity of the sprink ler system adjacent
to the building footings providing moisture to the underlying soils
Determination | Case number: 795900 Page 15 of 21
during periods of watering.
9.5.1.1.6. Seasonal soil moisture variations.
9.5.1.1.7. Absence of articulation joints exacerbating the
development of brickwork cracking.
9.5.1.2. Event related building movement, heave, subsidence
and/or damage within the proximity of the purported leaks has
not occurred.
9.5.2. EXTERNAL GARAGE PAVERS:
9.5.2.1. The inherent construction of the external pavers on a
flexible base has resulted in long - term movement and
subsidence of the paving.
9.5.2.2. The absence of a stormwat er drainage system to collect
surface water run - off has allowed water to seep through the
pavers exacerbating the settlement.
9.5.2.3. The pavers graded towards the home allowing water to
pond and seep through to the underlying soils has provided an
additional volume of wat er exacerbating the settlement.
9.5.3. CELLAR:
9.5.3.1. The absence of appropriate external ground surface
levels and surfac e stormwater draina ge system allows moisture
to seep through to the underlying soils resulting in efflorescence
to the brickwork.
9.5.3.2. The presence of the soluble salts has exacerbated the
extent of corrosion.
9.5.4. PLANT ROOM DOOR:
9.5.4.1. The plant room door is subje ct to long - term paint peel,
rot, and moisture decay.
9.5.4.2. Poor quality repairs have been previously undertaken
indicating a long - term and ongoing decay issue.
9.5.4.3. The damage to the plant room door is as a result of
poor maintenance, wear, and tear .
9.5.5. VERANDA PAVI NG:
9.5.5.1. The veranda paving has not incurred subsidence.
9.5.5.2. The veranda paving was not constructed to the
underside of the window frames and has not incurred the
purported subsidence.
9.5.5.3. The veranda structure has not in curred movement or
damage that would reasonably have developed if the veranda
paving had incurred movement.
9.5.6. EXTERNAL PAVING:
9.5.6.1. The external paving is constructed on a flexible base
and has incurred nominal differential movement between the
pa ving and veranda tiled area.
9.5.7. VERANDA POST:
9.5.7.1. The veranda post has not twisted and is a pre - existing
construction issue as noted with it having been fixed askew to
the steel sub post.
9.5.8. EXTERNAL SLIDING DOORS:
9.5.8.1. The binding to the external sliding doors is due to
Determination | Case number: 795900 Page 16 of 21
misalignment of the hanging tracks and rollers.
9.5.8.2. Misalignment of the tracks and rollers is a general
maintenance, wear, and tear issue.
9.5.8.3. The doors and trucks require maintenance and
adjustment.
9.5.9. ALCOVE :
9.5.9.1. The cracking and subsidence to the alcove is due to
poor construction practice.
9.5.9.2. Reflective movement to the adjacent walls has not
occurred.
9.5.9.3. The conc rete paving graded towards the home allows
surface stormwater run - off to drain and seep through to the
underside of the wall/slab.
9.5.10. INTERNAL CRACKING:
9.5.10.1. Internal cracking is consistent with nominal long - term
building movement as a res ult of the following generally issues
causing soil moisture variations:
9.5.10.1.1. Cl ose proximity of trees.
9.5.10.1.2. Removal of trees.
9.5.10.1.3. Ground surface levels graded towards the home.
9.5.10.1.4. Absence of surface stormwater drainage.
9.5.10.1.5. Close proximity of sprinkler watering system.
9.5.10.1.6. Seas onal soil moistur e variations.
9.5.10.2. Event related and/or localised building movement,
heave, subsidence and/or damage within the proximity of the
purported leaks has not occurred.
9.5.11. PAINT PEEL/CRACKING:
9.5.11.1. Paint peel and cracking to the cornice mouldings and
window joinery joins/repairs is nominal drying and cracking of
the enamel paint.
9.5.11.2. The paint peel and cracking is a general maintenance,
wear, and tear issue.
9.5.12. INTERNAL CAVITY DOORS BINDI NG:
9.5.12.1. The binding of the internal cavity d oors is as a result of
misalignment of the hanging track and rollers requiring general
maintenance and adjustment.
9.5.12.2. The full height doors and lack of adequate clearance
to the cavity is an exacerbating factor requiring regular and
ongoing maintena nc e and adjustment.
9.5.13. FLOORBOARD GAPS:
9.5.13.1. The increase gaps to the hardwood floorboards is due
to nominal drying of the natural timber products over time.
9.5.13.2. The rate of dry and gap development is exacerbated
to areas exposed to direct sunlight.
9.5.13.3. Moisture related swelling of the floorboards has not
occurred.
9.5.14. FLOORBOARD CREAKI NG:
9.5.14.1. Floorboard creaking is a natural phenomenon bet ween
the drying of the floor walls, supporting battens/joist and the
nailed fixings.
Determination | Case number: 795900 Page 17 of 21
9. 5.14.2. Moisture related swelling of the floorboards has not
occurred.
9.5.15. CRACKING TO ENTRY TILES:
9.5.15.1. The cracking along the entry title grout joint is located
at the concrete slab construction joint to the entry extension.
9.5.15.2. The absenc e of an articulation joint to allow for
nominal differential movement bet ween the two concrete slabs
has resulted in cracking to the grout joint.
9.5.15.3. The cracking to the grout is a pre - existing construction
defect.
9.5.16. Building movement as a res ult of the purported sprinkler
head dislodging from the sprinkler system has not occurred.
9.5.17. Building movement as a res ult of water draining into the
heater ducting has not occurred.
9.6. Pre - existing Issues
9.6.1. The items outlined wit hin the pr oximate cause and effect
are pre - existing issues to the property as a result of:
9.6.1.1. Construction defects/issues.
9.6.1.2. External paving, drainage, and landscaping.
9.6.1.3. Seasonal factors.
9.6.1.4. Wear and tear.
9.6.1.5. Absence of adequate main tenance.
Complainant’s expert
Plumber (G)
7 April 2015
SEWER CAMERA REPORT
After viewing the disc of the camera work on both the sewer and the
storm water drains, the results show there are tree roots in the joins
of the earthenware pipes, in both the sewer and the stormwater
drains.
The sewer drain shows only small roots in the joins, and no breaks
or collaps es in the pipes and fittings.
To date, the sewer is not blocking on a regular basis. The drain is
not holding water, so it is not flooding back under the building.
The stormwater drain also has tree roots in the joins and fittings.
Stormwater drains are laid flat and will hold water if they bec ome
blocked with tree roots, leaves dirt and sticks.
My experience shows both the sewer or stormwater drains would
not be causing the movement in the house.
Routine maintenance of c leaning, both sewer and stormwater drains
will help keep both drains clear.
Complainant’s expert
Plumber (FG )
Report
13 March 2014
To expose sprinkler heads in back lawn close to laundry, remove
sprinkler heads to establish saturation point.
Sprinkler cl osest to laundry was dislodged from irrigation pipe,
refitted sprinkler capped off and tested all sprinklers in area for leaks
- there were no other obvious leaks.
Complainant’s expert
Plumber (G )
Report
Findings on Attendance:
I attended the property to inspect and report on house hold
Determination | Case number: 795900 Page 18 of 21
4 April 2018 pl umbing drains around nort h side of house The area is
experiencing severe cracking, possibly due to water escaping from
plumbing drain.
My findings were as follows:
Sewer pipe work outside ensuite
On inspecti ng the sewer pipes outside the bathroom and ensuite I
was able to install camera down the sewer inspection points. On
doing this I found some slight cracking on the sewer main drain
which runs from the toilet inspection point all the way to the sewer
main connection point. On inspecting pipe work I found several
areas slightly affected by the tree roots but none serious enough to
obstruct the flow of water. My main concern is crack on the bottom
of the D. T. This crack is on the bottom of the Vit clay D.T. f itting and
is leaking during use. Please note: The D. T is meant to hold water
and does not due to the crack. Possible cause of destabalization
due to previous water leak.
Areas Untested – There are several areas of pipe work untested.
These pipe lines are under the conc rete slab and are extremely
difficult to gain access to due to the ins pection points being under
ground 1m. I have flow tested all fixtures and found water flowing
correctly into the outside drains. I am slightly concerned of the
connection p oints where the house fixture drains connect into the
main sewer. There is slightly root infestation which could indicat e
slight cracks in clay pipes. These roots are visible down the ensuite
D.T.
Areas that were untested were toilet sewer drain under conc rete
floor, both ensuite and main shower fixture drains and bath fixture
drain.
Please note: Although not cameraed they flow tested okay.
Caus e of Action
Hous e drains on north side
I recommend the D. T. be dug up and repaired. I also recommend
the house fixture drains be inspected during this time.
Complainant’s expert
Engineer (LP )
Report
30 March 2016
Further to our site visits and perusal of engineering reports, and
floor levels provided by your insurance company, and in conjunction
with the report prepared by the (CA) we advise as follows.
We were on site when the initial inspection was carried out b y the
CA and water flows were identified, prior to the hydronic heating coil
(heating system) being dismantled.
We agree that further investigation should be carried out to
determine the integrity of the under floor ducts in relation to the
release of moi sture under the slab, in particular to the western end
Determination | Case number: 795900 Page 19 of 21
of the dwelling where heave has been identified by previous
investigations.
The movement at this location is due to excessive moisture and the
sub floor duct work, given the results of the latest inve stigations,
could be a contributing factor due to the volume of water that could
be released if the ducting was defective
Complainant’s expert
Engineer (LP )
Report
27 October 2020
Floor levels previously taken by F Engineering indicat e localized
edge hea ve along the northern wall of the family room and kitchen.
This area is not adjacent to alleged cause of the abnormal moisture
conditions, i.e. sewer, storm water or damaged sprinkler.
It is also noted that the surface adjacent to the family room and
kitch en is covered by an impervious expanse of protective tile
paving which would tend to stabilise moisture conditions under
normal circumstances.
We also note in C’s report (S Building Co - ordinator) that we
stipulated that this area of tiling had heaved, we w ere in fact
referring to the adjacent edge footing heave which would contribute
towards the difference in level between the window sill and tiles.
We are advised that the timber core board lining the under - floor
brick ducting was in a state of disintegration and was removed due
to the water damage.
We are therefore of the opinion that moisture egress from the
ducting cannot be dismissed.
Complainant’s expert
Engineer (LP )
Report
21 July 2020
INTRODUCTION:
At this site a single storey solid masonry dwelling exists, constructed
in 1969.
Distress has developed over a period of time, due to excess sub -
floor moisture.
This company has been engaged to:
1). Inspect the site and provide relevant engineering comments.
2). Prepare a scope of work s for remedial works attributed to
ingress
of water at sub - floor level due to compromised under floor ducting.
GENERAL OBSERVATIONS AND COMMENTS:
We have reviewed several engineering reports, prepared on behalf
of S Pty. Ltd., the owner’s insurer.
We o riginally provided recommendations in relation to further
investigation of the air conditioning/heating system subfloor ducting
Determination | Case number: 795900 Page 20 of 21
in March 2016.
Cons equently, the faulty ducting has been replaced and appropriate
repair works carried out to the system.
The scope of works incorporated in this correspondence relat es to
damage and distress due to excess sub - floor moisture, i.e. heave of
the clay foundation material, due to the faulty ducting.
Whenever a reactive clay soil is subjected to an increase in
moisture content it undergoes an increase in volume i.e. heave. This
results in vertical movement of the ground surface and subsequent
building distress and damage.