Home / Commonwealth Insurance Limited / Determination 760265
Determination 760265
Claim declined for bathroom cracking damage attributed to failed waterproofing membrane
Summary
After a split pipe was repaired, the complainants claimed $20,405 to re-tile a bathroom with cracking damage. AFCA accepted the insurer's expert evidence that a failed waterproofing membrane caused the damage, which is excluded, and ordered nothing.
The insurer's expert evidence showed the damage was caused by a defect or faulty workmanship in the membrane, which is excluded, and the tiler's evidence was not persuasive.
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
Case number 760265
Financial firm Commonwealth Insurance Limited
Determination | Case number: 760265 Page 2 of 12
Case number: 760265 28 April 2021
1 Determination overview
1.1 Complaint
The complainants hold a home and contents insurance policy with the financial firm (the
insurer).
In February 2020, the complainants discovered a split water pipe under the house after
noticing water at the edge of the property. They repaired the pipe and lodged a claim on 22
March 2020 for escape of liquid under the policy.
The insurer declined the claim because its expert reports found a failed waterproofing
membrane in the bathroom. It says water gradually leaked through the membrane into the
substrata of the bathroom floor causing the cracking damage.
Relying on a report from their tiler, the complainants disagree with the insurer‟s findings and
want the bathroom repaired.
The case manager provided the parties with a recommendation on the issues in dispute. The
recommendation was in favour of the insurer.
As the complainants have not accepted the recommendation, the complaint has been
referred to me for determination .
1.2 Issues and key findings
Is the insurer entitled to decline the claim?
The available information establishes on the balance of probabilities the cracking damage in
the bathroom has been caused by water ingress into the bathroom floor and joists below
which was not caused by the burst pipe but by the compromised water membrane in several
locations in the bathroom floor.
As this cause of damage is excluded from cover, the insurer is entitled to decline the claim.
1.3 Determination
This determination is in favour of the insurer.
It is not required to take any further action in relation to the claim or the complaint.
Determination | Case number: 760265 Page 3 of 12
2 Reasons for determination
2.1 Is the insurer entitled to decline the claim?
Parties’ submissions and material considered
The complainants must establish on the balance of probabilities they have suffered a loss
caused by an event to which the policy responds. This is known as a prima facie or valid
claim.
Once so established, the onus shifts to the insurer to prove on the balance of probabilities
that an exclusion applies if it seeks to deny or limit its liability for the loss.
When making the claim in March 2020 the complainants said on 20 February 2020, they
noticed water at the edge of the house. Upon further inspection they found flooding under the
house. A plumber was called. He advised there was a split in the pipe, and he advised how to
fix it. The male complainant fixed the pipe. The complainants say he also flattened out the
area under the house where the water had washed away.
Over the next few weeks, the complainants say the house began to move and crack and
water was flowing from the shower. The male complainant inspected under the house again
and said water was leaking from the shower.
The complainants claim the first leak caused the house to move. The complainants rely on
material from their tiler and claim $20,405 to demolish and re-tile the bathroom.
The insurer arranged for the damage to be inspected and obtained reports about the cause of
the claimed damage.
The relevant extracts from the material relied on by the parties are set out in supporting
section 3.3 of this determination.
After the recommendation, no further submissions were made, and no new material was
provided by either party.
Having reviewed the reports from the parties I accept there is cracking damage in the
bathroom. The dispute relates to the cause of the damage.
Relying on the report from their tiler, the complainants say the movement in and around the
shower recess was sudden and extreme because of a pipe leaking or breaking which caused
ground movement.
The insurer says there was no sudden or unexpected escape of water but that the escape of
water was gradual. The insurer says the deterioration to the bearers and joists supports its
contention there has been an ongoing issue with the property. The insurer also says the
membrane in the bathroom has failed in multiple locations and is the cause of the resultant
damage which is not caused by the burst pipe.
Available material shows it’s probable the waterproofing is compromised
The insurer‟s policy covers the building for loss or damage caused by the sudden and
unexpected escape of water from a fixed water pipe.
Cover is not provided if the damage is caused by:
a leaking or faulty shower recess or shower base
any gradual escape of liquid
defects, structural or design faults, faulty workmanship, or faulty design.
Determination | Case number: 760265 Page 4 of 12
Extracts from the relevant policy terms are set out in supporting section 2.2 of this
determination.
The complainants have not provided any material from the plumber who advised about repair
of the split pipe. The only available information from the complainants about the cause of
damage is from the tiler.
The tiler‟s report is not dated but I assume from his quotation that he inspected the property in
or about January 2021.
Relevantly, the tiler says:
the movement he saw was sudden and extreme because of a pipe leaking
and causing ground movement
the waterproofing has been done to standard including a puddle flange in
place at the junction of waste pipe and floor
pictures at the underside of the floor show no evidence of mould or
blacking of the underside of the wet area chipboard.
Having carefully reviewed the available material and the photographs provided, while I accept
there was a leaking pipe, I am not satisfied the available material establishes on the balance
of probabilities the damage in the bathroom was caused by the leaking pipe. This is becaus e
even though the pipe was repaired water was still leaking when using the shower. The
complainants assert this was because the leaking pipe had caused movement, but I do not
accept the tiler has the requisite expertise to comment persuasively nor has he adequately
explained the mechanism of the damage.
Photographs taken by the insurer‟s expert (S) show the flooring and floor joists are water
stained both at the shower recess floor waste and through the fibre cement floor sheeting.
The insurer‟s builder said the water staining to the subfloor sheeting and timber members
suggest the waterproof membrane installed to the bathroom floor sheeting is compromised in
several locations and does not comply with Australian Standards. The builder explains as
water has breached the membrane and gone into the timber floor joists causing swelling that
this is the cause of the tile movement.
Insurer is entitled to decline the claim
I have considered the photographs provided. I accept they show evidence of water staining
on the underside of the flooring sheeting and floor joists. I also agree a photograph shows
floor tiling at the floor waste with no evidence of waterproofing turn down in the waste pipe.
The complainants‟ tiler says the waterproofing has been done to standard but has provided
no photographic evidence in support of his statement.
Having considered the available information and photographs provided I prefer S‟s opinion
which is cogently explained and supported by photographs.
I am satisfied the available information establishes on the balance of probabilities the
cracking damage in the bathroom has been caused by water ingress into the bathroom floor
and joists below which was not caused by the burst pipe but by the compromised water
membrane in several locations installed in the bathroom floor.
Determination | Case number: 760265 Page 5 of 12
I am satisfied the damage was caused and/or connected with this defect and/or faulty
workmanship when the membrane was installed. As this cause of damage is excluded from
cover, the insurer is entitled to decline the claim.
Determination | Case number: 760265 Page 6 of 12
3 Supporting information
3.1 Process
AFCA’s approach to this comp laint
This complaint has been determined based on what is fair in all the circumstances, having
regard to legal principles, applicable industry codes or guidance, good industry practice and
previous relevant determinations of AFCA or predecessor schemes (which are not binding).
A full exchange of the relevant information has taken place between the respective parties.
Each party has had the opportunity of addressing any issues raised. All the provided
information has been reviewed and considered. The parties have raised numerous issues in
their submissions to AFCA. However, commentary in this determination is restricted to those
issues considered relevant to the outcome.
It is an accepted principle of general insurance law that the insured bears the onus to
establish on the balance of probabilities that they have suffered a loss caused by an event to
which the policy responds. This is known as a prima facie or valid claim. Once so established,
the onus shifts to the insurer to prove on the balance of probabilities that an exclusion applies
if it seeks to deny or limit its liability for the loss.
How we assess complaints
AFCA is not a court of law. We do not have the power to take or test evidence on oath, or to
require third parties to give evidence. When we assess complaints, we consider available
documents, the recollections of the parties, and all relevant circumstances. We give more
weight to documents created at the time the events occurred. If there is no relevant
documentation, we will decide what is most likely to have occurred based on the information
provided to us. If there are conflicting recollections and these are evenly weighted, we may
find that a claim cannot be established.
3.2 Relevant policy terms
The relevant policy extracts are referred to in the correspondence between the parties and in
the insurer‟s Notice of Response. Both the policy document and the Notice have been
exchanged with the complainant.
Escape of Liquid
What is covered
Your building and/or contents are covered for loss or damage caused by the
sudden and unexpected escape of liquid from any:
Water main;
Fixed water pipe (but not a garden hose);
Fire hydrant;
Pool or spa;
Fixed water feature;
Determination | Case number: 760265 Page 7 of 12
Fixed tank;
Washing machine or dishwasher;
Sink, basin, bath or toilet;
Sealed portable heater; or
Fixed heating or cooling system.
If we have agreed to cover the loss or damage caused, we will also pay the
reasonable cost of locating the source of the damage, where necessary,
provided that:
It is at your insured address; and
We have agreed to pay this cost before you make arrangements for any
work to commence.
You are only covered for up to $500 for the repair or replacement of the item from
which the liquid escaped if it formed part of your building or contents.
What is not covered
You are not covered under this Insured Event for:
· loss or damage caused by any escape of liquid of which you were aware and failed to
notify us of within a reasonable period;
• loss or damage resulting from a leaking or faulty shower recess or shower base;
• loss or damage caused by any gradual escape of liquid;
• loss or damage to trees, plants and shrubs growing outdoors;
• the cost to replace the liquid which escaped;
• exploratory or restoration costs if we have not accepted a claim under this Insured
Event.
Your building and/or contents are not covered under this Insured Event for loss or
damage as described in the General Exclusions did on pages 78 – 81.
General Exclusions
Under this policy there is no cover provided for any loss, damage or liability
caused directly or indirectly by or in any way connected with:
1. defects structural or design faults, faulty workmanship or faulty design;
5. water, including rainwater, after it has disappeared beneath the surface of the
land at your insured address;
9. the vibration, settling, shrinking or expanding of earth or any building,
foundation, wall, pavement or path (except in the case of the Insured Events
„Lightning‟ and „Earthquake‟ claims);
13. mould, toxic mould, mildew, wet or dry rot, rising damp or dampness;
35. gradual loss or damage of any kind
Determination | Case number: 760265 Page 8 of 12
3.3 Case law and proximate cause
Case law establishes:
· The proximate cause of the loss is the dominant or effective or operative cause of the
loss whether or not that be the last in time or the sole cause.
· If there are several causes operating contemporaneously, each must be examined for
the qualities of reality, predominance and efficiency as the active, efficient cause that
sets a relevant chain of events in action. If one cause would have caused the harm in
any case, and the other would not have done so in the absence of the first, the first is
the proximate cause.
· A common - sense approach is taken to determine proximate cause.
3.4 Extracts from material relied on by the parties
Date Action
Complainant‟s tiler (ML)
Letter Undated
Inspected tiles in the ensuite and noticed an extreme
amount of movement in and around the shower
recess .
Bottom row of wall tiles had a 12 – 15mm gap open up
from the floor tiles and also the floor level for the
drainage of the water had changed from running water
to the drain in the shower to running out the ensuite
door .
This type of movement has been sudden and extreme
as a result of a pipe leaking or broken and creating
ground movement .
Waterproofing has been done to standard including a
puddle flange in place at the junction of waste pipe and
floor .
Usually a shower recess takes a while to leak and
show evi dence of damage. As there is none of this in
the ensuite just extreme movement, even pictures at
the underside of the floor showing no evidence of
mould or blacking of the underside of the wet area
chipboard.
Quote (MBC)
10 November 2020
Stripping and re - sheeting bathroom including building
materials and labour $4, 400 including GST .
Quote (ML)
16 January 2021
Demolish and retile bathroom $20,405 including GST.
Insurer report (DW) Inspected and photographed 20 May 2020 .
When using shower complainant noticed water ran
from the shower recess and out the door of the
bathroom.
Insured inspected the subfloor and found one of the
water waste lines had split allowing water to spill out
onto the subfloor when the shower was in use.
Arranged repairs.
Determination | Case number: 760265 Page 9 of 12
Bathroo m built six years ago.
Movement in the subfloor has affected other rooms
with cracks appearing.
Area repaired but water still leaking when using
shower.
At time of inspection damage was visible to the
bathroom – damage to subfloor area movement –
noted movement cracks to doorways. Although
repaired, under the floor there were a number of leaks
coming through the floor in the shower rec ess area.
Subfloor le aking around the waste line along the
shower wall with water evident leaking in five or six
separate areas of the shower. No photographs of
damaged line. Said line was split and not a separation
of the junction.
Subsequent subfloor movement has caused
sep aration between the flooring and the walls in the
shower jeopardising the waterproofing and allowing
water to exit through separate areas of the wall and
floor. Constant exposure to the escaping water prior to
this being found has caused a shift in the pie rs of the
sub flooring of the property. Also, general movement of
the property in other areas.
Recommended an engineer be appointed as the area
had been repaired and DW could not determine if the
cause of the damage was because of a building fault
or a spl it in the pipe.
Email from DW to insurer
2 July 2020
Ensuite of the main bathroom has been affected by the
escape of liquid into the sub floor area of the property.
There is significant movement to the flooring area of
the ensuite. This is quite noticea ble under foot when in
the bathroom.
Resulting damage to the area appears to have
occurred over a period of time due to constant
exposure to escaping liquid from the damaged waste
line. This movement has occurred over a period and is
not the result of a o ne - off event. Due to the constant
escape of liquid in the same area the resulting
foundational movement is constant with the escape of
liquid.
Email from DW to insurer
23 July 2020
Resulting movement that has occurred to the nort h
western corner of the property (ensuite/main bedroom)
is not the result of a burst pipe over a 24 - hour period.
The resulting damage to the area has been a gradual
one.
Noted deterioration to the bearers and joists of the sub
structure indicat e that exposure to constant water h as
been an ongoing issue. If the area had been exposed
to a 24 - hour exposure of constant water resulting
damage both internally and in the sub floor area would
be more evident to the area that was affected most.
There appears to be none of that with the ground
Determination | Case number: 760265 Page 10 of 12
showing no signs of being washed away over a 24 -
hour period as an area would be when exposed to a
constant flow of wat er.
Insurer‟s forensic building report (S)
23 June 2020
Inspected and photographed 15 June 2020
1960‟s building transported to the site with additions
comprising of the bedroom and bat hroom in 2 014
supported on concrete block pi llars wit h poured
concrete foundations .
Complainant said water service poly pipe had split and
was repaired under the western wall of the kitchen
adjoining the western bathroom wit hin the subfloor
area.
He advised that the western bedroom and bathroom
were constructed in 2014, these works included the re -
roofing of the whole of the building.
He had additionally noticed water ingress to the
subfloor area underneath the western bathroom floor
when the shower was in use.
Show er water had also been noticed tracking from the
shower recess internally across the ceramic tiled floor
to the bathroom doorway adjoining the bedroom to the
south.
Western bathroom shower recess had not been in use
for a number of weeks.
Noted the subfl oor sewer drainage within the
bathroom, draining from the bat h, floor waste, vanity
unit and shower recess waste are interconnected in
50mm PVC prior to draining into a 50mm trap installed
within the subfloor. Additionally, on inspection the
sewer pipework drainage to the bathroom did not have
a visible vent pipe installed.
Western bathroom floor structure consists of LVL
timber bearers and floor joists with fibre cement sheet
flooring.
Flooring and floor joists show signs of water staining
both at the shower recess floor waste and at visible
nail penetrations through the fibre cement floor
sheeting which suggests a failure in the required
waterproof membrane on the floor surface int ernal ly.
Internally, the floor tiling installed to the bathroom
shows signs of movement. The installed grouting has
cracked and or de bonded between the floor tiles
predominantly adjacent to the shower recess. Mould
was not visible within the shower recess.
F loor wastes fitted to the bathroom do not show
evidence of waterproofing turn down into the pipework
drainage.
Concluded
Sewer drainage pipework requires inspection for
compliance to ensure the drainage system is fully
operational.
Non - compliance of the existing drainage would be
considered a building defect.
Determination | Case number: 760265 Page 11 of 12
Evidence of wat er staining to the subfloor floor
sheeting and structural timber members suggests the
waterproof membrane installed to the bathroom floor
sheeting is compromised in several loc ations and does
not comply with the requirements of AS3740. Water
ingress into timber floor joists is the suggested cause
of swelling within the joists and therefore is the cause
of movement wit hin the internal tiled surfaces.
Waterproof membrane installed to t he bathroom floor
is compromised in several locations and is the cause
of movement wit hin the internal tiled surfaces. This
item is considered to be a building defect.
Insurer‟s forensic building report (S)
11 September 2020
Complainant had said there wa s a burst pipe he
repaired under the old part of the house and S
confirmed the inspection included the subfloor areas of
the original structure and the newer extension as well.
As for identifying any burst pipe S said at the time of
inspection water servi ce poly pipe was exposed on the
subfloor ground surfaces and there was no evidence of
leaking pipes or saturated soil surfaces at the time of
inspection .
Reiterates cause movement cracks within the house is
water ingress into the timber floor joists and
a dditionally the original structure and extension have
different met hods of structural pier support (supported
by photograph 1).
Movement and cracking bet ween the original structure
and the more recent extension are caused by differing
foundation structure and moisture levels within the sub
floor soils.
If, after compliance inspection, the sewer drainage
pipework is deemed non - comp liant wit h AS3500 and
local authority requirements, it would be defective.
Defective pipework can be a contributing factor to
damage within a building.
Where water has made its way through the waterproof
membrane and flooring into the timber floor joists, the
additional moisture within the timber has allowed it to
swell and cause “movement and cracking of tile
grouting in the ceramic tiled floor surface” within the
bathroom only.
Unable to confirm what type of waterproofing
membrane had been installed. Ho wever, the fact
remains that water has breached what ever membrane
has been used and therefore is considered defective.
Insurer‟s forensic building report (S)
22 January 2021
Reviewed material from ML report and not es it is not
dated and so he could not co mpare to his inspection
15 June 2020.
Gapping in wall tiles referred to by ML not seen when
S inspected.
As for the movement being sudden S said a
contributing factor to high moisture levels within the
Determination | Case number: 760265 Page 12 of 12
subfloor soils is the lack of roof guttering, downpi pes
and an effective roof water drainage system which
were not installed at the time of the inspection.
Additionally, high seasonal rainfall experienced within
the 2020 calendar year has compounded the
concentration of water entering the subfloor and the
r eactive clay soils.
As the 12 - 15mm gaps were not present at the time of
my inspection I cannot agree the movement was
sudden and extreme.
Re ML comment regarding pictures of the underside of
the floor, S said the ceramic tiled bathroom floor is
fitted t o a fibre cement sheet substrate fixed to a
timber bearer and joist subfloor frame. The floor is not
chipboard as stated and the attached phot ograph‟s 2,
3 and 4 show evidence of water staining on the
underside of the fibre cement sheet flooring.
Reiterat es from section 5.2 of report 23 June 2020
which states: “The evidence of water staining to the
subfloor floor sheeting and structural timber members
suggests the wat erproof membrane installed to the
bathroom floor sheeting has been compromised, in
several locations and does not comply with the
requirements of AS 3740.
3.5 Other relevant material considered and relied on
Parties‟ submissions/emails and all attachments to all submissions/emails
Parties‟ expert reports
Photographs
Correspondence between the parties