Determination 712995
Denial of roof truss accidental damage claim
Summary
The homeowner's roof truss failure claim under an accidental damage policy was denied on exclusion grounds. AFCA found the insurer had not proved an exclusion applied, so it ordered the claim accepted, $1,550 in professional costs paid and $2,000 for non-financial loss.
The insurer bore the onus of proving an exclusion, and its inconclusive and shifting expert reports did not establish gradual deterioration, structural defect or climatic causes.
Issues
- Claim denial primary · upheld“The insurer has not met its onus to prove, on the balance of probabilities, a relevant exclusion applies to the claim.”
- Poor claim handling secondary · upheld“The cause of damage noted by the insurer's expert reports is not clear and contradicts itself, and the ongoing delays caused considerable stress.”
Subjects and remedies
home or building damagepay claimpay compensationpay non financial loss
Related
Text of the determination
Determination
Case number 712995
Financial firm Insurance Australia Limited
Determination | Case number: 712995 Page 2 of 14
Case number: 712995 14 May 2021
1 Determination overview
1.1 Complaint
The complainant holds an Accidental Home Insurance policy with the financial firm
(insurer), providing cover for accidental loss or damage to buildings or contents plus
cover for specific conditions arising from various incidents as outlined by the policy.
The complainant lodged a claim on 10 February 2020 after noticing the roof of the
home was sagging. The insurer denied the claim and says the damage was caused
by climatic conditions overtime combined with structural defects leading to gradual
deterioration of the nail plates.
The complainant disputes the insurer‟s decision and is seeking for the claim to be
paid as she considers the policy provides cover in this instance.
1.2 Issues and key findings
Is the insurer entitled to refuse payment of the claim?
No. There is no dispute the home suffered accidental damage. The insurer has not
met its onus to prove, on the balance of probabilities, a relevant exclusion applies to
the claim.
Is the complainant entitled to compensation for professional costs?
Yes. Pursuant to Rule D3.5 of the AFCA rules the insurer must pay the complainant
$1,550 professional costs incurred in pursuing this complaint subject to the
complainant providing the relevant invoices for the reports from CTGM and KPC.
Is the complainant entitled to compensation for non-financial loss?
Yes. The claims handling has caused an unusual degree of physical inconvenience
and stress and in the circumstances, it is fair that the insurer pays $2,000
compensation for non-financial loss.
1.3 Determination
This determination is in favour of the complainant.
The insurer is required to accept the claim as set out in section 2.1 of this
determination. In addition, the insurer is to pay the complainant $1,550 to professional
costs incurred and $2,000 compensation for non-financial loss pursuant to AFCA Rule
3.3.
Determination | Case number: 712995 Page 3 of 14
2 Reasons for determination
2.1 Is the insurer entitled to refuse payment of the claim?
No. The damage claimed falls within the terms of the policy.
Complainant has established a valid claim within the terms of the policy
The complainant‟s policy is an Accidental Damage Home Insurance policy covering
both home and contents for accidental damage. The policy defines accidental
damage as:
any loss or destruction of the buildings that make up the home, or your contents
and valuable items, when it is caused by an unintentional act, or an unforeseen
and uncontrollable incident.
The policy also includes “ Additional cover ” which is cover provided in addition to the
sum insured. This includes temporary accommodation of up to 10% of the sum
insured and debris removal and demolition of up to 10% sum insured.
Cover is also provided under specific conditions for various incidents none of which
are relevant to this claim.
The complainant says she first noticed the roof was sagging on about 3 February
2020. The dining room ceiling was sagging and the square set ceiling in the rumpus
room, living room, passage, bathroom and laundry had cracked.
A building consultant, UBS, inspected the home and identified issues with the trusses
A make safe was conducted, providing a prop to the dining room ceiling.
The insurer does not dispute that the home has sustained accidental damage. The
panel is satisfied the damage was accidental damage within the terms of the policy as
the damage was unintentional and an unforeseen and uncontrollable event.
Insurer has the onus to establish exclusion applies
In denying the claim the insurer has relied on the policy exclusions relating the
gradual deterioration, wear and tear, structural defects and climatic conditions. The
onus is therefore on the insurer to prove of the balance of probabilities the exclusions
apply. The relevant policy wording is set out under section 3.3 of this determination.
Initially the insurer claimed the damage was not caused by a single event. It now says
the damage while accidental was caused by climatic conditions overtime combined
with structural defects (long trusses, insufficient nail support, lack of sarking) that has
led to the gradual deterioration of the nail plates.
Determination | Case number: 712995 Page 4 of 14
Insurer’s e xpert reports are inconclusive
The insurer engaged a structural engineer (BH) to report on the cause of damage. BH
provided 3 reports that are summarised in section 3.2 of this determination.
In summary the first report indicates that:
the trusses have failed at the nail plate heal joint, a known phenomenon that‟s
applicable in houses contracted 10-15 years ago and is likely due to the quality of
timber used in the manufacture of the trusses
the damage has been ongoing for many years and relates solely to the weight of
the roof
no evidence the damage has been caused by a leak
this is a latent defect and would not have been obvious until significant failure.
After the complainant disputed the insurers decision to deny the claim the insurer
asked BH to clarify his findings.
In the second report BH considered the damage not accidental damage, nor
maintenance related, nor related to a specific storm event. BH considered it may be
described as a latent building defect, although the trusses were designed and appear
to have been erected to all relevant standards and building codes. It is normal climatic
variations, primarily humidity, that has likely been a major contributing factor.
After revi ewing the report from the complainant‟s engineer CTGM, BH provided a
third report on 27 November 2021. BH concluded he could not apportion blame to
any person for the failure of the trusses. T he trusses were designed the relevant
standards, were likely constructed to the relevant standards, and appear to have
been correctly installed. There have been no roof leaks, nor any actions by the
owner that would have contributed towards the failure of the trusses. However, nail
plate backout does occur in Victoria and despite not being a common occurrence
cannot be ruled out as the primary cause of damage in this instance. This backout
may potentially have been initially instigated by a single storm event or may even
have been instigated by poor handling of the trusses prior to installation.
At best BH offers several possible causes but makes no definitive findings.
The complainant ’s engineer’s report supports finding that damage was
accidental
The complainant engaged structural engineers (CTGM) to report on the damages.
The report dated 8 October 2020 concluded that:
wear and tear is not considered to be a significant primary contributor
there is no evidence provided to show that there are any design defects in relation
to roof trusses
to provide evidence of defective materials would require specific testing of
materials from the building and may not be conclusive
the roof trusses showed no obvious signs of poor workmanship
Determination | Case number: 712995 Page 5 of 14
nail plate backout represents a possible theory but there is no significant evidence
to support this
whilst it is unclear if a storm in the area affected the house it is an example of a
storm in the area around the time when damage may have occurred.
The report supports a view that the cause of damage cannot be identified or attributed
to one of the relevant exclusions referred to by the insurer.
Insurer has not established exclusions apply to allow denial of claim
The panel, having considered the information exchanged is not persuaded that the
insurer has established, on the balance of probabilities, that the exclusions apply to
allow it to deny the claim.
The insurer‟s expert reports outline potential causes but cannot say that any of the
suggested causes resulted in the damage. The most recent report from BH confirms
there were no building defects. There was no evidence of faulty workmanship. While
there may be climatic conditions, the roof was not low pitched and had no sarking. It
is unlikely climatic conditions caused the damage.
This information suggests that the damage resulted from nail plate backout of no
obvious cause. The house had been built only 13 years prior to the claim being
lodged. In the absence of building defects, faulty workmanship or climatic changes, it
is unlikely such damage would be due to gradual deterioration or wear and tear.
Insurer is to indemnify the complainant
As the insurer has not established the application of an exclusion, the panel
determines the insurer is to meet the claim in accordance with the terms of the policy.
No quotes or scope of works have been exchanged to determine the extent of the
damage, likely period that temporary accommodation will be required, or likely costs
associated with removal of debris or demolition.
It is fair in the circumstances that w ithin 14 days of the complainant‟s acceptance of
this determination, the insurer appoints an independent engineer to provide a scope
of works and an independent builder to provide an actionable quote for the cost to
complete the repairs.
On obtaining the actionable quote the insurer is to determine whether to exercise its
discretion whether to repair, or cash settle the claim. If the insurer chooses to cash
settle the claim it is to add a 15% allowance on top of the actionable quote to cover
possible contingencies and transfer of risk.
The insurer is also required to cover the full costs of any additional benefits to which
the complainants are entitled under the policy including temporary accommodation
and removal of debris.
Determination | Case number: 712995 Page 6 of 14
2.2 Is the complainant entitled to compensation for professional costs?
The complainant has provided invoices for professional costs incurred in obtaining the
report from CTGM ($990) and from KPC ($165) totalling $1,550.
Under AFCA rule D3.5 AFCA can determine the insurer contribute towards
professional costs incurred by a complainant in resolving the complaint.
The reports obtained by the complainant has assisted the panel in determining this
dispute and clarifying the nature of the damage sustained.
In the panels view it is fair in the circumstances that the insurer covers the
complainant‟s costs of obtaining the reports of $1,550 subject to the complainant
providing the relevant invoices to the insurer.
2.3 Is the complainant entitled to compensation for non-financial loss?
AFCA may award compensation in certain circumstances
Under paragraph D.3 of the AFCA Rules, we may award compensation for non-
financial loss (capped at $5,400) where there has been an unusual amount of:
physical inconvenience
time taken to resolve the situation
interference with the complainant‟s expectation of enjoyment or peace of mind.
We take a conservative approach to compensation and expect a complainant to bear
a normal degree of inconvenience during a claim.
The panel acknowledges that some of the delays in this claim may have been
inevitable. However, the policy is an accidental damage policy. The cause of damage
noted by the insurer‟s expert reports is not clear and contradicts itself. The ongoing
delays caused interference with the complainant and her partner ‟ s expectation of
enjoyment or peace of mind. The house was unsafe to live in yet due to the
sensitivities of this being their home, and, leaving the complainant confused and
unsure on how to approach their claim. The process caused considerable stress for
the complainant.
The panel considers it is fair in these circumstances that the insurer pays $2,000
compensation to the complainant for non-financial loss under AFCA rule 3.3.
Determination | Case number: 712995 Page 7 of 14
3 Supporting information
3.1 Process
AFCA’s approach to this complaint
This complaint has been determined based on what is fair in all the circumstances,
having regard to the legal principles, applicable industry codes or guidance, good
industry practice and previous decisions of AFCA or its predecessor schemes (which
are not binding).
A full exchange of the relevant information has taken place between the respective
parties. Each party has had the opportunity of addressing any issues raised. All of the
provided information has been reviewed and considered. The parties have raised
numerous issues in their submissions to AFCA. However, commentary in this
determination is restricted to those issues considered relevant to the outcome.
This matter was determined by a panel
Due to the nature of this dispute, it has been referred to a panel for determination.
The panel comprises the lead ombudsman, a member with significant experience in
consumer and small business advocacy and a member with extensive experience as
a [field of expertise].
3.2 Relevant reports
Record Key points
Insurer’s expert report (B H )
18 February 2020
NATURE OF RESIDENCE AND EXTENT OF DAMAGE .
… The main area of damage in this house is to the single storey
northern portion, where the timb er trusses span the entire width of
the house, a span of approximately 13m. There is no evidenc e of
damage to the double storey portion where the trusses only
effectively span halfway across the house.
……
There is no evidence of significant footing movement occurring in
this house that would be impacting the damage that has occurred to
the roof trusses. There was no excessive cracking of external
brickwork, or of the internal plasterboard wall linings to indicate any
significant movement.
The damage to this house comprises a significant sag in the ceiling
over the dining room area, along with visible damage to the top of
the plasterboard walls / cornice, along the line of the playroom wall
internal wall on the west side of the lounge room, and lesser
damage to the top of the walls along the east side of the lounge
room int ernal walls. The damage to these internal walls is clearly
Determination | Case number: 712995 Page 8 of 14
Record Key points
occurring due to the roof trusses sagging down and now being
supported on these internal walls. The roof trusses were origin ally
designed to span from the east side external wall to the west side
external wall, with these internal walls designed as a non -
loadbearing walls. Refer photograph 1. Externally, the fascia has
pushed away from the brickwork in several places along the west
side of the house, but particularly adjacent to the dining room and
midway along the playroom external wall, and the roof has sagged
significantly, particularly over the dining room area where there were
no internal walls to support the failed trusses . Refer photograph 2.
CAUSE OF DAMAGE.
The current sagging in the ceiling and damage to the top of the
internal plasterboard walls, along with the movement in the fascia on
the external wall is failure of the heel joint of the timber roof trusses.
….. . Fai lure of this joint has allowed the entire truss to sag, which
has resulted in the trusses now bearing over the top of the int ernal
walls, causing the current damage to the top of the plasterboard on
these internal walls.
The distortion in the trusses has a lso caus ed some of the int ernal
truss web member nail plate joins to also partially fail, as the plates
are lifting at the edges due to the inc reased stresses now being
applied to these web members.
…
We therefore believe that the trusses of failed due to a large span of
the truss, the use of a heavy tiled roof, and the probable use of a
poorer quality timber, although at the time the timber was almost
certainly provided to the truss manufacturer with a claim from the
supplier to have the appropriat e stress grade, likely F5. To
absolutely confirm if the timber was the problem, we would need to
take samples and have them properly tested for strength grade,
including timber density. This is however unlikely to be relevant in
assessing this claim.
The failure o f the nail plates has progressively been occurring for
many years, as evidenc ed by the progressive increased damage to
the plasterboard along the top of the playroom internal wall. The
magnitude of subsidence of the dining room ceiling would not have
been is obvious as it is now following the installation of the
temporary prop.
The dining room area on the west side of house represents the
maximum unsupported span of the trusses, where they could not
settle on to internal walls, and is the primary reas on why the worst
damage has occurred where it has.
We note that there is no sarking under the tiles, hence the roof
cavity will receive ventilation through the tiles themselves, which
Determination | Case number: 712995 Page 9 of 14
Record Key points
should assist in reducing humidity in the roof space. Excessive
humidity could also have contributed towards the breakdown of the
timber, but there is no reason that this roof space would have
excessive humidity.
SUMMARY
The trusses to the northern end of this house, spanning from the
east to west external walls, have virtually all failed at the nail plate
heel joint. This is a known phenomenon that has particularly been
applicable to houses constructed around 10 to 15 years ago, and is
likely to be primarily due to the quality of timber used in the
manufacture of the trusses. Since then, most truss manufacturers
would also use a larger nail plate for trusses of this size, particularly
when supporting a tiled roof.
The damage has been ongoing for many years and relates solely to
the weight of the roof. It is our opinion that failure has not been
instigated or caused by a single, or multiple storm events, nor is the
westerly aspect of the trusses of significant relevance. There is no
evidence of damage being caused by a roof leak, or leaking
plumbing pipe or fixture.
This defect in th e trusses may be described as a latent defect that
would not readily be obvious to a homeowner until significant failure
/ deflection of the ceilings and roof of the hous e were noticed. We
understand that nails securing the plasterboard ceiling started to pop
adjacent to the playroom internal stud wall around 3 - 4 years ago,
however damage at that time was not sufficient to rais e any alarms.
The builder of the house is currently still trading, however we
understand that the truss manufacturer no longer exis ts. We do note
however that both of these parties acted in accordance with current
practice at the time of the construction of the hous e, and it has only
been in more rec ent times that the extent of the problems wit h the
nail plates / timber quality of the trusses manufactured at that time
has become apparent.
Insurer’s expert report –
commentary from BH – 24
March 2020
1. The additional information provided by the insured is exactly
what I expected it to be. There was not hing in this information
that contradicts our finding. It confirms that the trusses were
constructed in accordance with the relevant Australia Standards,
and indeed still comply with current standards. The main
differenc e between trusses made at that time and current
trusses is that la rger nail plates tend to now be used to
compens ate for nail plate „back - out‟ issues that have occurred
on a relative large number of trusses.
2. We have done extensive further research on this matter as a
result of your query, and believe that the basic find ings of our
initial report stands, however climatic effects are likely to have
also made a significant contribution to the failure, as discussed
below.
The cause of the nail plate failure can be related to many factors
Determination | Case number: 712995 Page 10 of 14
Record Key points
such as poor placement of the nail p late on the join, excessive
flexing of the trusses during delivery and erection, poor timber
quality (despite being stamped F5), or poorly designed nail plates
themselves. Longer term damage due to the repeated shrinkage
and swelling of the timbers due to climate / humidity (cyclic
mechano - sorptive swelling and shrinkage) is however also
recognised as a significant factor. The shrink / swell process has a
„ratchetting‟ effect causing the nailplates to „back - out‟ progressively
over time. A CSIRO study of thi s type of failure (attached) claims
that nailplate back - out predominantly occurs in tile roof houses
without a moisture barrier (sarking), as exists in this instance. The
relative humidity under an unsarked roof has a far greater daily
variation than under a sarked roof, cont ributing to a greater
„ratchetting‟ effect.
The conclusion of the study was:
Nailplate backout can occur when cyclic mechano - sorptive swelling
and shrinking of wood and/or thermal expansion and contraction of
wood and/or metal results in a „ratcheting‟ mec hanism in which
withdrawal deformations of the fastener accumulate over time. This
ratcheting mechanism will only occur when frictional resistance to
withdrawal between the side of the nailplate teeth is significantly less
than the cru s hing resistance underneath the teeth. Under these
conditions, the teeth are restricted from fully re - penet rating the wood
on shrink age (or tooth expansion) and thus the withdrawal
deformations during swelling can accumulate over time.
We therefore believe that this mechano - sorptive swelling and
shrinkage, is the likely main cause of the failure, particularly as
these trusses are a relatively long span and support a tiled roof. This
process has therefore been occurring effectively since the trusses
w ere erected.
3. This is not accidental damage, nor is it maintenance related, nor
is it related to a specific storm event. It may be described as a
latent building defect, although the trusses were designed and
appear to have been erected to all relevant sta ndards and
building codes. It is normal climatic variations, primarily
humidity, that has likely been a major contributing factor. The
nature of the timbers used and the size / type of nailplates used
however are major factors as to whether a specific trus s is
affected by this type of failure. For this reason, and given the
prevalence of this type of failure, truss manufacturers now tend
to use larger nailplat es, even though the relevant s tandards and
regulations do not specifically require this.
4. The added weight of the pumped in insulation should have been
allowed for in the truss design, although it is not specifically
mentioned in the truss design documents – Copy attached. It is
our opinion that the weight of the insulation is not a factor in the
failur e.
Determination | Case number: 712995 Page 11 of 14
Record Key points
5. A scope of works is not provided as the damage has not been
caused by a specific wind or storm event. The scope of works
will however involve the complete removal and replac ement of
the roof, including the installation of new trusses.
Complainant’s
Report paper :
Nai lplate Backout – is it a
Problem in Plated Timber
Trusses?
By Senior Research Scientist
at CSIRO.
https://www.researc hgat e.net/publication/264240392
5.2 Roof Inspections
A program of random roof inspections is being undertaken to help
determine the extent of nailplate backout in the existing housing
stock, and to add to data collected from a previous inspection
program conducted on more than 100 retirement units [4]. The
retirement home inspections revealed a high proportion of problem
nailplate connections due to a range of factors. Preliminary findings
from the random inspections indicate that the prevalence of
mechano - sorptively driven backout (and other nailplate sepa ration
problems) is lower than reported for the retirement units. This could
possibly be explained by the prevalenc e of a specific type of
problematic nailplate in the retirement homes which was thought to
be under - designed and is no longer used.
Forest & Wood Products
Australia - Mechano -
Sorptive Nailplate Backout
in Nailplated Timber Trusse s
Report - Page 72
6.2.2. Summary of results and conclusions
Detailed reports of causes of observed backout for the many
different cases of backout are given in Nguy en & Paevere (2009).
Each documented case of backout needs to be considered in its
own context, however some common feat ures of many of the
problem roofs were:
Steelfast brand nailplates (thes e are no longer used), which are
underdesigned and carrying larger than appropriate loads
Un - s arked concrete tiled roofs
Evidence of wat er penet ration was found into the roof space
where backout due to mechano - sorptive creep effects were
observed
Majority of nailplate backouts were attribut ed to improper
manufactur e and improper storage and handling of trusses.
Complainant’s CTGM Report
– 8 October 2020
Possible cause s of movement
… Several different
possible contributing factors have been raised however this review
finds no compelling evidence to support a
primar y cause in the matters raised.
1. Wear & Tear
…. The House is less than 15 years old and was generally
considered to be in relatively good condition with no significant
obvious degradation of materials. Roof timber and the roof space
Determination | Case number: 712995 Page 12 of 14
Record Key points
generally was considered to be dry and there were no obvious signs
of moisture ingress or high moisture levels. There was no evidence
of significant corrosion of nail plates. Timber was generally observed
to be in good condition and straight with the exception of the
deflections observed as a direct result of the nail plate failure at the
eave connection. Wear and tear is not considered to be a significant
primary contributor.
2. Design Faults
Roof trusses have been designed and certified by the manufacturer
using industry accepted design tools. The design allows for a site
wind classification of N2 for wind loading in accordance with AS
4055 which is supported by the BH report. Loads allow for concrete
roof tiles, plasterboard ceiling and associated incidental loads. The
building design documents including truss design has been
accepted by the presiding building surveyor as complying wit h the
Building Code of Australia. There is no evidence provided to show
that there are any design defects in relation to roof trusses.
3. Material Faults
As stated in item 1 above, the mater ials in the roof space appear to
be in good condition with no obvious defects apart from the nail
plate failure. Speculation has been raised in relation to the qualities
of the materials used and reported variability of materials available
at the time. No evidence in relation to the materials used in this
building has been presented. It is understood that the company who
manufactured the roof trusses is no longer trading however truss
manufacturers would normally have quality control systems in place
to ens ure compliance. To provide evidence of defective materials
would require specific testing of materials from the building and may
not be conclusive.
4. Workmanship
The general quality of finish in the building was considered good.
The only significant plas ter damage and movements observed can
be attributed to the truss nail plate failure and subsequent truss
movements. The roof trusses showed no obvious signs of poor
workmanship. It is not clear if poor workmanship contributed
to the isolated locations wher e nail plat e failures have occurred
however this does not appear consistent with the general condition
of the trusses.
5. Nail Plate Backout
“Nail Plat e Backout” has been pres ented as a possible cause of the
failure. This is a phenomena where nail plates back - out away from
the timber causing a significant reduction in joint strength. Research
on this subject is limited however the condition has been linked to
high variations in humidity and relatively low pitch
roof trusses. Some literature identifies spec ific nail plates which
stopped being used several years prior to the manufacture of these
roof trusses.
The roof trusses used for this building have a pitch of 22 degrees
which is very common and not considered to be “low pitched”. There
is no sarking un der the tiles which has been identified as a common
trait of backout affected trusses however, as observed in the BH
report this improves ventilation and would reduce the risk of major
humidity variations in the roof space caused by moisture introduced
fro m the house. The height of the roof yields a significant roof space
Determination | Case number: 712995 Page 13 of 14
Record Key points
volume which would als o help reduce humidity variations.
As with the other items outlined above this represents a possible
theory but there is no significant evidence to support this. Th ere are
many similar houses constructed nearby of similar age and it would
be expected that there would be more cases of similar failures
reported if this was the problem.
6. Weather Events
It should be noted that wind loads vary with time and location. W ind
loads for design are typically derived from a range of factors
including wind records, geographic location, topography etc and
provide design loading based on a probabilistic approach. Rare,
extreme and often localised storms can exceed the design
load s.
Records have been provided identifying a storm event which
occurred in the Mt Clear area in late November 2012 and resulted in
localised damage to property such as removal of roofs and
uprooting of trees. Whilst it is unclear if this storm affected 39
Tulloch Close it is an example of a storm in the area around the time
period when damage may have occurred.
3.3 Product disclosure statement & legislation
Record Key points
Product Di sclosure
Statement – Exclusions To
Your Cover
Page 27
Accidental Damage cover, additional cover and Strata Title
Mortgagee Protection exclusions
We will not cover any loss or damage as a res ult of or caused by:
erosion, rust, corrosion, gradual deterioration, depreciation, wear
or tear
a defect in an i tem, structural defects or faulty workmanship or
design
Product Di sclosure
Statement - General
Exclusions
Page 27
General Exclusions
We will not cover any loss or damage, or liability as a result of, or
arising from:
…
Determination | Case number: 712995 Page 14 of 14
Record Key points
Mildew, atmospheric or climatic conditions
…
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.