Home / Hollard / Determination 651625
Determination 651625
Denial of storm damage claim to farm chicken sheds
Summary
A farmer claimed storm damage to six chicken sheds after the insurer denied the claim as long-term deterioration. AFCA accepted storm damage to shed 2 and ordered it settled through an independent scope of works, but rejected the claim for shed 1 and other damage.
The proximate cause test showed storm caused the truss failure in shed 2 while long-term purlin sagging and deterioration caused the shed 1 damage, which falls within the wear, tear and deterioration exclusions.
Issues
- Claim denial primary · upheld“The panel is persuaded the proximate cause of the damage to shed 2 is storm; shed 1 and other claimed damage are not covered.”
- Claim amount dispute secondary · unclear“Insurer may cash settle shed 2 repairs on an independent scope of works, not exceeding the $450,000 sum insured.”
Subjects and remedies
business interruptionnatural disasterpay claim
Related
Text of the determination
Determination
Case number 651625
Financial firm The Hollard Insurance Company Pty Ltd
Determination | Case number: 651625 Page 2 of 19
Case number: 651625 9 July 2020
1 Determination overview
1.1 Complaint
On 20 December 2012, the complainant signed a claim form and lodged it with the
financial firm (insurer) for damage caused by a storm on 19 December 2012. The
complainant also says there was a second storm event on 22 December 2012.
The insurer denied the claim and says the claimed damage was not caused by the
storm.
The complainant disputes this and seeks for the claim to be accepted and paid in full.
The complainant also seeks for the insurer to pay for lost profit caused by the
damage.
1.2 Issue and key findings
Is the insurer entitled to deny the claim?
The insurer is liable for the damage to shed 2 and any loss of income associated with
this damage. The insurer is not liable for any of the other damage claimed.
1.3 Determination
This determination is partially in favour of the complainant.
The insurer should settle the claim in the manner set out in section 2.1.
Determination | Case number: 651625 Page 3 of 19
2 Reasons for determination
2.1 Is the insurer entitled to deny the claim?
Complainant must establish a valid claim
The complainant must establish, on the balance of probabilities, it suffered a loss
caused by an event to which the policy responds. This is known as a prima facie
claim.
The policy provides cover for loss or damage to farm property directly caused by an
‘Insured Event’. ‘Insured Events’ include ‘ Storm and rainwater ’ and ‘Accidental
Damage’. ‘Accidental Damage’ responds to accidental loss or damage. The policy
does not define the term ‘accidental’ . However, this is commonly understood to mean
an incident that is unintended and unexpected.
Accordingly, to establish a claimable loss (a prima facie claim), the complainant must
show the damages being claimed were either:
directly caused by a storm, or
unintended and unexpected.
The policy limits cov er to the ‘limit shown for each item or catego ry of item on your
Insurance Certificate’ . The insurance certificate (COI) has a sum insured of $450,000
for each of the six ‘chicken sheds’ and their attached infrastructure.
The policy further limits cover under the ‘Accidental Damage’ insured event to t he
sum insured for accidental damage shown on the COI. The COI has a sum insured
for accidental damage of $250,000.
Insurer says damage is not covered by the policy
The claim was lodged with the description ‘Wind storm damage Chook Sheds’ and
the damage wa s described as ‘Shed rafters & iron were bent out of shape’.
The insurer accepts there is damage to the chicken sheds. However, the insurer says
the damage was not caused by the storm and is instead the result of long-term aging,
gradual deterioration, and wear and tear. The insurer also says the damage was not
directly caused by ‘Storm and rainwater’.
The ‘Accidental Damage’ insured event contains specific exclusions. The insurer has
relied on several of these to deny the claim under this section. The exclusions the
insurer relies on relate to:
inherent vice or latent defect
wear, tear, and gradual deterioration
error or omission in design, plan or specifications or failure of design
settling, seepage, shrinkage or expansion.
Determination | Case number: 651625 Page 4 of 19
Insurer’s experts say there is damage caused by aging and deterioration
The insurer appointed a building consultant (LD) to report on the damage and its
cause. LD provided a report dated 9 May 2013 and in it says:
the sheds were full of chickens which made detailed inspection difficult
the sheds do not have wall or roof bracing and the timber purlins do not have
bridging between them
the two older sheds with the greatest sagging run in an east west direction and the
storm hit from the west
LD noted the timber purlins are sagging in a vertical direction. LD said that had the
sagging been caused by the storm, he would expect the timber purlins to fail in a
horizontal direction. He would also expect some of the purlins to have split or broken
and the roof sheeting fixing devices to have been pulled out. There was no evidence
of this.
LD therefore recommended an engineer be appointed to provide a more detailed
inspection once the chickens have been removed.
The insurer appointed an engineer (MK) who, in its report dated 23 May 2013, says:
the uniformity of the deformation of the roof material seems common to many of
the buildings and gives the impression of being gradual deformation rather than a
‘ One off Event ’ .
the uniformity, evenness and consistency of deformation in shed 1 is consistent
with, and indicative of, long term settlement and deformation
the roof purlins have no midspan bridging support and this has allowed
deformation to occur
the roof purlins in shed 1 do not meet current Australian standards. Design checks
were undertaken for the normal dead and live loading in line with the current
standards:
> it was found the basic working stress was exceeded and the allowable deflection
exceeded appropriate limits. The actual calculated deflection appears to match
what has occurred on site
> the purlins were inadequate for the design wind velocity and appropriate wind
loading for the site
to assess these buildings for potential storm damage is a complex exercise. Storm
events can differ widely in their intensity from one location to another and obtaining
accurate wind data beyond recognized weather stations can only be interpolated at
best
generally, wind damage will be concentrated and not consistently uniform
throughout a building
a close inspection of roof trusses in shed 2 reveals a failure of the roof trusses at
the apex of the main steel portal frames. This is typical of high wind damage.
Determination | Case number: 651625 Page 5 of 19
However, shed 1, which is to the immediate west of shed 2, does not have the
same degree of damage despite the direction of prevailing winds. Shed 1 should
have been more susceptible to damage.
Complainant’s expert says damage is caused by a storm
The complainant engaged an engineer (WB) who provided a letter dated 31 October
2014. This letter says:
under today’s standards these sheds w ould not be approved. However, they likely
met the standards at the time they were built.
shed 1:
> the timber purlins have bowed badly but this is due to age not a storm event
> the entire shed appears to have moved 150 mm along its length at eaves level
> this shed will have received the full brunt of the storm so damage to this building
could have been more severe
> the wind has hit the shed and the lack of wall bracing has allowed the shed to
move approximately 150 mm along its length causing damage to the cooling
panels along the walls and to other non-structural items
> the shed is still structurally sound
shed 2:
> there is storm damage to the pipe trusses. The top chord has bent downwards
and there is some sideways bending
> the top of the columns have bent where the trusses attach to the columns
> the bending of the trusses at or near the apex and the bending of the top of the
columns are indications the roof of the shed has been lifted during the storm and
dropped back onto the columns
> the damage to this shed is quite severe and is no longer structurally sound and
will need to be demolished and re-built.
WB also provided further letters dated 9 December 2019 and 1 April 2020. In these
WB says:
his first inspection says there is serious structural damage to the trusses (or main
structural members of sheds 1 & 2)
his second inspection confirms this
the trusses have been subjected to a severe uplift loading by the wind
the roof has then dropped back down creating a severe compression loading of the
top chord of the trusses at the position of maximum movement near the apex
if a minor wind lifted the roof again and dropped back onto the trusses, complete
failure of the building would occur
the sheds are very dangerous to any chickens or person within
both sheds 1 & 2 will have to be rebuilt.
Determination | Case number: 651625 Page 6 of 19
this type of damage to a roof structure can only be caused by strong winds usually
associated with a storm front.
Complainant lodged another claim in 2014
On 17 November 2014, the insurer inspected the shed in relation to a separate storm
claim lodged on 5 November 2014. This claim was accepted and settled. There is no
information to suggest the complainant raised WB’s report during the 2014 claim
despite WB’s inspection occurring only days before that storm.
The insurer’s inspection report for the 2014 claim notes shed 6 now has similar
damage to shed 1 and 2.
Proximate cause of the loss must be determined
When considering if a complainant has shown a valid claim or if an exclusion applies,
it is necessary to assess what the proximate cause of the damage is. If the proximate
cause is excluded from cover, the insurer will generally be able to deny the claim.
Proximate cause is not necessarily the first or the last or the sole cause of the
damage. It is the dominant or effective or operative cause. The proximate cause of
the loss is a question of fact to be determined based on the surrounding
circumstances.
Shed 2 is covered
Both engineers agree the sheds would not meet the current building standards.
However, WB says they likely would have met the standards at the time they were
built. MK does not refute this. MK says the lack of midspan bridging has allowed the
downward deformation of the roof.
Shed 1 is positioned to the west of shed 2. MK believes shed 1 would have been
more susceptible to damage from the storm than shed 2 as the storm came from the
west. However, MK does acknowledge storms can be complex.
The panel notes no evidence was provided to show the storm came from the west
direction. The panel also notes the complainant refers to a second storm which does
not appear to have been addressed.
In 2014, WB said the timber purlins in shed 1 had bowed badly due to age, not a
storm event. He said shed 1 was structurally sound and indicated it was repairable.
By 2019, WB says shed 1 needs to be rebuilt.
This indicates the damage to shed 1 has become worse over the five years since the
first inspection. This is consistent with MK’s evidence that this damage is long term.
WB’s 2014 report and MK’s evidence are relatively consistent in showing the
structural issues with shed 1 is not directly caused by the storm. Both refer to the fact
that the timber purlins bowed quite badly due to age rather than a storm event.
Determination | Case number: 651625 Page 7 of 19
The panel is not persuaded by WB’s later reports which now say the trusses
damaged in shed 1 is consistent with storm damage. This report was provided about
5 years later. It is inconsistent with his contemporaneous report and MK’s findings.
For shed 2 however, both WB and MK identify a failure of the roof trusses at the apex.
MK also noted this is evident in many of the steel portal frames in the building.
Significantly, MK says this ‘failure is typical of high wind damage’. WB agrees with
this.
This shows both engineers agree that there is storm damage to shed 2. In particular,
MK’s evidence is far from clear in saying this damage was caused by other factors
identified or that those other factors were the proximate cause.
The panel notes that during the dispute, the insurer attempted to have another
engineer inspect the sheds. For various reasons, this was unable to be facilitated.
However, it is unclear to what extent this would assist the insurer. In this regard, the
panel considers greater weight would go to the contemporaneous engineering reports
available.
Having considered the available information the panel is satisfied, on the balance of
probabilities, the proximate cause of the claimed damage to shed 1 is long-term aging
and deterioration.
For shed 2 though, the panel is persuaded the proximate cause of the damage is
storm. This is consistent with both contemporaneous engineer reports. Whilst the
panel acknowledges the purlins were inadequate based on current standards, there is
no evidence to show they were defective at the time of construction. Neither is the
evidence persuasive that they were the proximate cause of the loss. There is also no
dispute there was a storm and that damage was caused by this event
Therefore, the panel accepts the structural damage to shed 2 should be accepted.
Other damage claimed is not covered
The complainant has also claimed for other damage he says was caused by the
storm. This includes the following:
damaged rooflines to sheds 4 to 6
damaged roller door and cool shed to shed 6
damaged fibro surrounds to sheds 3 and 6
caps blown off on the sheds
damaged side curtains in sheds 3 and 4
damaged cool pads in sheds 3 and 4
damaged flooring in shed 3
The complainant has provided various photos to support his position.
Determination | Case number: 651625 Page 8 of 19
The panel is not persuaded that these items are payable. They were not noted on or
commented by any of the contemporaneous assessment or engineer reports. There is
no assessment that these items were damaged by the claimed storm rather than from
other factors or events (e.g. wear and tear).
Further, given the time that has passed, there will no way for the insurer to be able to
meaningfully assess this damage, and as such has been severely prejudiced.
Therefore, the panel does not accept the insurer is liable for the other damage
claimed.
Insurer liable for lost profit and reduced production for shed 2 only
The complainant has claimed for lost income. The policy responds for farm income in
the following circumstances:
We will pay up to the sum insured shown on your Insurance Certificate for loss of
farm income arising from loss or damage to property that is insured under the
Farm Property or General Property sections of this policy
Based on the available information, and given damage to shed 2 falls within the cover
provided, the panel is persuaded the insurer would be liable for any loss of farm
income which can be shown to have resulted from the damage to shed 2 only.
How the claim should be settled
The panel notes WB says shed 2 should be rebuilt. MK made no such assessment.
The panel is not persuaded by WB’s report alone given:
it appeared the complainant was using the shed for at least seven years after the
claimed event, and
it is not clear if the recommendation to rebuild was due to the storm damage or the
fact the structure is inadequate based on current standards
Given this, the panel considers it is fair the insurer is given an opportunity to assess
the works necessary to repair the damage to shed 2. To this end, the parties should
do the following:
agree to the appointment of an independent engineer with no prior involvement in
the claim
this engineer is to compile a scope of works to repair the damage to shed 2 caused
by the storm – in doing so, s/he must be given access to shed 2, the reports
provided by the other engineers and all photos of the damage to shed 2 taken
contemporaneous to the event
Determination | Case number: 651625 Page 9 of 19
at least one quotation is to be obtained by the insurer for these scope of works
from a contractor prepared to do the works for the complainant – if more than one
quotation is obtained, then the average of all the quotations is applicable; the
quotation must be at today’s costs and be actionable
the insurer can cash settle based on this amount provided it does not exceed the
sum insured of $450,000
For any lost income, the insurer is entitled to assess this in accordance with the
policy. This is because there is no information provided to substantiate any award.
Therefore, the complainant will be required to provide any information (such as
financial records) the insurer requires to assess this aspect of the claim.
Determination | Case number: 651625 Page 10 of 19
3 Supporting information
3.1 Our approach to this complaint
We have considered it appropriate to expedite this complaint in accordance with the
Operational Guidelines to the AFCA Rules, due to the nature of the complaint.
Accordingly, this complaint has not been the subject of a preliminary assessment and
has proceeded directly to determination.
The determination is made by a panel consisting of the ombudsman together with a
representative who has extensive experience in consumer claims and a
representative who has extensive experience in the insurance industry.
This complaint has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other. All of the material provided by the parties has been reviewed and
considered.
While the parties have raised numerous issues in their submissions, for the purposes
of this determination, commentary has been restricted to those issues considered
directly relevant to the outcome only.
It is an accepted principle of general insurance law that an insured bears the onus to
establish, on the balance of probabilities, they have suffe red a loss caused by an
event to which the policy responds. This is known as a prima facie claim. Once so
established, the onus shifts to the insurer to prove, on the balance of probabilities, an
exclusion applies if it seeks to deny or limit its liability for the loss.
3.2 Relevant policy wording
Subject Terms
Farm Property - 1. Words
with special meaning in this
section
farm buildings mean all fixed structures other than residential
buildings, which are at the location and are listed on your
Insuranc e Certificate as being used in connection with the farm
business. Farm buildings include tanks, fixed plant and services
that are attached to and form part of any farm buildings.
Farm buildings DOES NOT include fencing, power poles and the
overhead wiring b etween the power poles
farm improvements means silos, windmills, boundary fencing,
internal fencing, yards, ramps, races, troughs, feeders, power
and telephone poles, wiring and any of their accessories for
Determination | Case number: 651625 Page 11 of 19
Subject Terms
which you are legally liable. It also includes t rees that are not
grown as a commercial crop, which are us ed as windbreaks or
for sanitary/soil erosion cont rol purposes.
The cover for farm improvements is limited to the improvements
that you have elected to insure and which are listed on the
Insuranc e Certificate.
Farm Property - 2. What we
cover
We will cover you for loss or damage to insured farm property at
the location directly caused by the events listed under ‘Ins ured
Events’ up to the limit shown for each item or category of item
on your Insurance Certificat e.
Farm Property - 3. Insured
Events
We will cover you for loss or damage caused directly by the
following insured events:
…
Storm and rainwater
Storm and Rainwater includes water and any other liquid
discharged from the mains, pipes, gutters, drains, tanks or fixed
apparatus used to hold or carry liquids …
Accidental damage
We will cover you for accidental loss or damage to Farm
buildings and Farm contents provided that the loss or damage is
not already covered by or able to be insured by or is not
excluded by any other section of the policy, whether or not you
have elected to insure under any or all of these sections.
There is no cover for accidental damage to farm produce, farm
machinery, hay, grain, wool or livestock. The maximum am ount
we will pay for any one event under this accidental damage
cover is the sum insured shown on your Insurance Certificate for
Accidental damage.
We will not cover accidental loss or damage caused by or
involving:
1. fermentation, heating or any process in volving the
application of heat;
2. roots from trees;
3. rust or oxidation, mildew, mould, wet or dry rot, corrosion,
change of colour, atmospheric conditions or other variations
in temperature, evaporation, diseas e, inherent vic e or latent
defect, loss of weight, change in flavour, texture or finish;
4. deterioration and putrefaction of refrigerated goods;
5. loading or unloading, delivery or dispatch;
6. faulty packing or storage;
7. mechanic al, hydraulic, electrical or electronic breakdown,
failure, malfunction or de rangement of any machine or
electrical device or temperature controlling equipment;
8. contamination or pollution;
9. wear, tear, fading, scratching, marring, gradual
Determination | Case number: 651625 Page 12 of 19
Subject Terms
deterioration, normal upkeep or making good;
10. error or omission in design, plan or specification s or failure
of design;
11. theft;
12. fraud or dishonest acts, embezzlement, forgery, erasure,
counterfeiting and fraudulent misappropriation by electronic
means or otherwise;
13. unexplained inventory short age, unexplained
disappearanc e, disappearance resulting from clerical or
accounting errors or shortage in the supply or delivery of
materials to or from you;
14. loss or damage caused to:
- vehicles, caravans, trailers, motor cycles, watercraft,
aircraft or aerial devices;
- property insured during and as a result of i ts processing;
- property insured during construction, erection,
renovation or demolition;
- property in transit.
15. insects, vermin, moths or by the pecking, clawing, eating or
nesting by birds and other wildlife;
16. faulty materials or faulty workmanship;
17. any orde r of any government, public or loc al authority
including the confiscation, nationalisation, requisition,
repossession of or damage to any property;
18. computer virus;
19. loss of or damage to property directly or indirectly caused by
or contributed to by normal settling, seepage, shrinkage or
expansion in buildings or foundations, walls, pavements,
roads and ot her structural improvements, creeping, heaving
and vibration.
20. any pers on deliberately switching off or disconnecting the
power supply.
3.3 Expert reports
Reco rd Key points
financial firm’s expert (LD )
Building consultant’s r eport
9 May 2013
Observations and Di scussions
At the time of the inspection the chicken sheds were full of
chickens and could not be inspected fully. The chicken sheds will
be empty in approximately 14 days from the date of the inspection
and may be then fully inspected.
The Chicken Sheds
At the time of the inspection the sheds were full of chickens which
presented difficulties in undertaking a detailed inspection.
The chicken sheds ha ve been constructed over approximately the
last 30 years.
The older sheds have been constructed from steel pipe columns
and steel pipe webbed trusses. Timber purlins have been used.
This was a common form of construction of chicken sheds in the
Determination | Case number: 651625 Page 13 of 19
Reco rd Key points
1980s. The sheds do not have wall or roof bracing and the timber
purlins do not have bridging bet ween them. I would have expected
the walls would have had bracing between the columns and in the
roof.
The newer sheds are of a similar construction and in some of the
sheds the timber purlins have been replaced with C section steel
purlins.
The insured has claimed that the wind storm has hit the end of the
Older Sheds which has caused a concertina effect, which has
caused the timber purlins to sag from the pressure. Th e older two
sheds with the greatest sagging of the timber purlins run in an east
west direction. The storm hit the sheds at the end from a westerly
direction.
The newer sheds which run in a north south direction have not
experienced the sagging of the tim ber purlins to the same extent
as the sheds running in an east west direction. These sheds have
experienced loosening of iron sheeting and air conditioner
flashings which the insured has repaired.
It is feasible that the storm hitting the end of the sheds has caused
the sagging of the timber purlins.
The timber purlins are sagging in a vertical direction.
Had the sagging of the timber purlins been resultant from a storm,
I would have expected to see the timber purlins fail in a horizontal
direction from the impact forces from a concertina effect. Some of
the purlins may have split or have broken from the impact of the
forces applied. The roof sheeting fixing devices would have also
pulled out from the impact forces applied.
I did not see evidence of the timber purlins failing in a horizontal
direction, cracked or broken purlins or the roof fixing devices being
pulled out from the impact forces applied.
In my view I could find no clear evidence of storm related damage
to the shed. There is no lifting of s heeting and fixings as one would
expect to find in wind driven damage situations.
Also, I was not able to do a detailed assessment internally as the
shed was, unfortunately, full of chickens at the time and it was
simply impossible to do a detailed physica l examination.
Ultimately, if a categoric assessment of the damage to this shed is
required then an Engineer would be required to view the structure
and scientific ally calculate the load bearing capacity of the bearers
supporting the areas that are sagging and which are alleged to
have been damaged by the storm event. If we are to do so then
we would need to ascertain the actual severity of the wind gusts in
the region via the BoM.
One reason for the timber purlins failing in the vertical direction
may hav e result ed from the timber purlins being green or having
high moisture content resulting in a high flexing ratio at the time of
construction. Gravity and the weight of the roof have pulled the
timber purlins down in the vertical direction due to the green timber
having a high flexing ratio.
At the time of construction green timbers may have been used in
Determination | Case number: 651625 Page 14 of 19
Reco rd Key points
preference to seasoned timber for the ease of installing the fixing
devic es. Seasoned hardwood timber is next to impossible to drive
in a roofing nail or tek screw.
Naturally we are unable to categorically determine the condition of
the timber at the time of construction, at this late stage.
The appointment of a consulting structural engineer would be able
to determine if the timber purlins were of sufficient size for the
spans and whether or not this caused the sagging to occur over
time or if this or any other deficiency in conjunction with the storm
caused the sagging to occur.
Conclusion
The inspection of the sheds at [insured address] has revealed the
following that:
1. The Bobc at Carport Shed has experienced minor damage
from the storm and is repairable
2. The sheds known as the Combine Shed and Adjacent Shed
have been destroyed beyond economical repair by the storm
event,
3. The sagging of the timber purlins in the Older Chicken Sheds
is most probably not storm created or related and
4. A structural engineer to be appointed to determine if the
timber purlins were of sufficient size for the spans and if the
storm was result ant for the sagging of the purlins.
Financial firm ’s expert ( MK )
Engineer’s Report
23 May 2013
We wish to advis e that we have undertaken inspections of the
above mentioned buildings on the 22 nd May and 24th May 2013
and we report as follows.
Whilst the aim of our site inspection was to ascertain the structural
adequacy of the existing Timber Roof Purlins, several other
observations were made in regard to the overall structure.
Constructed on the site are a series of Steel Portal Frame
buildings, clad with corrugated iron with Hardwood timber roof
purlins. Although there were slight differences in materials used
the buildings were generally of similar structural content.
We will relate our discussion to building 1 and 2 the western most
buildings. These buildings had a clear span of 12300mm, an eave
height of 3000mm, Apex Height of 4000mm and main frame
spacing of 3640mm. Columns for individual frames were 65 O.D .
Pipe, and Roof members were fabricated trusses with 30 O. D .
Pipe top and bottom chords and 10mm MS rod truss chords . Roof
Purlins consist of 95x45 hardwood timbe r sections placed at
1200mm centres .
From an initial external visual inspection many of the sheds show
deformation of the roof mat erial between the internal steel portal
frames as illustrated in Figure 1 below. The uniformity of the
deformation seems commo n to many of the buildings and gives
the impression of being a gradual deformation with time rather
than a "One off Event".
Our report will further consider this, as there do seem to be a
combination of factors to take into consideration around the
circums tances involved .
Determination | Case number: 651625 Page 15 of 19
Reco rd Key points
The uniformity, evenness and consistency of this frame to frame
deformation is consistent with and indic ative of long term
settlement and deformation of the roof purlins. These roof purlins
as mentioned span 3640mm and have no midspan brid ging
support that has further allowed deformation under normal working
stresses to occur.
A design check was undertaken on these Roof purlin members to
assess structural adequacy in accordance with current Australian
Standards.
Australian Standards utilize d in our assessment include
> AS1720. 1 - 1988 Timber Structures Code
> AS1170. 0 - 2002 Structural Design Actions
> AS1170. 1 - 2002 Structural Design Actions Part 1 Permanent,
Imposed and other actions
> AS1170. 2 - 2002 Structural Design Actions Part 2 Wind Loads
These pur lin sections were found to be inadequate . Design checks
were undertaken for two loading cases. The first case was for
1. normal Dead and Live loading and the second case
considered was for
2. the appropriate wind loading for the site.
The site would be considered as a Region A Terrain Category 2 in
accordance with AS 1170.2 - 2011 Structural Design Actions Part 2
Wind Loads .
Load Case 1
> It was found that the Basic Working Stress in Bending in
accordance with AS 1720.1 - 1988 Timber Structures Code Part 1
Design Methods was exceeded and the allowable deflection
exceeded appropriate limits . The actual calculated deflection
appears to match what has actually occurred on site.
Load Case 2
> Adopting a Design Wind Velocity of 41m/s and the appropriate
Wind loadin g coefficients in accordance with AS 1170 . 2 - 2011
Structural Design Actions Part 2 Wind Actions these purlin
sections were found to be inadequate. Modelling was
undertaken assuming a Terrain Cat egory 2 Wind Loading
condition and utilising Spacegass Structur al Software.
The design analysis findings support our professional opinion that
the consistency of deformation or sagging of the roof purlins
evenly along the buildings is a direct result of the ageing, drying
and subs equent shrinkage of the purlins, and t he inadequacy of
inherent properties to perform over the required span bet ween
portal frames and the subsequent spacing of the purlins (centre to
centre) and the lack of Lateral Restraint in the form of sag rods or
mid span bridging .
[figure 2] clearly sho ws the consistency along the building of the
roof deformation between main building steel port al frames . The
eave purlin can clearly be seen and has basically failed under load
and weat her forces.
Of further int erest is that this consistency of deformation is
apparent in other buildings furt her supporting our design and
Determination | Case number: 651625 Page 16 of 19
Reco rd Key points
Analysis findings that the purlin sections are inadequate for the
intended purpose.
To assess these buildings for potential storm damage that may
have occurred on the 22 nd December 2012 as r eported by the
owner is a complex exercise. Such storm events can differ widely
in their intensity from one location to another and obtaining
accurate wind data beyond recognized weather stations can only
be interpolated at best. What is also of further in terest in modelling
these buildings under a design wind load is that the net force on
the Western side of the Roof of building 1 and 2 is a net outward
force. Again, the downward or inward deformation of thes e roof
pur l ins does not support high wind loadin g damage that would be
caused under a design wind. Different damage would be evident
and this damage based on our previous experience would not be
uniform as we are seeing with the roof deformation that we have
witnessed. Generally wind damage will be conc ent rated and not
consistently uniform throughout a building.
However, a close inspection of roof trusses in Building 2 reveals a
failure of the roof trusses at the Apex of the main steel portal
frames. In building 2 this is evident in many of the steel por tal
frames in the building. This failure is typical of high wind damage.
What is surprising however is that Building 1 to the immediate
west of Building 2 does not have the same degree of damage.
Building 1 given the direction of prevailing winds should ha ve been
more susceptible to damage. As previously mentioned these
Weather events can be complex in nature.
This report does not extend to undertaking a structural analysis
and design check of the steel portal frames, however we do
believe that they would p rove deficient under current design
Australian Standards.
Complainant’s expert ( WB )
Engineer’s Report
31 October 2014
An inspection of the above chicken sheds was carried out by [WB]
on the 27th October 2014 and we report as follows:
1. Description.
The sheds 1 and 2 are older sheds constructed in the early
1980's. These sheds have steel trusses made with 35 mm
diametre pipe as top and bottom chords x 350 mm deep with
timber purlins at approximately 1200 mm centres and 60 mm
diametre columns at approximat ely 3500 mm cent res. Posts are
2300 mm above a concrete dwarf wall and the apex of the roof is
2700 mm high.
The trusses span approximately 12 metres.
It should be noted that under todays standards these sheds
would not be approved, however under the stan dards in 1980
they would more than likely have complied.
Determination | Case number: 651625 Page 17 of 19
Reco rd Key points
A. Inspection - Shed 1.
i) There is no wall bracing in this building.
ii) The timber purlins have bowed quite badly but this is due
to age rather than a storm event.
iii) The entire shed appears to have move approx imat ely
150 mm along its length at the eaves level, causing a
considerable amount of damage to cooling panels and
other non structural items.
3. Discussion and Recommendations, shed 1.
Where this shed is located it will have received the full brunt of
the storm so damage to this building could have been more
severe. The wind has hit the shed and the lack of wall bracing
has allowed the shed to move approximat ely 150 mm along its
length c ausing damage to the cooling panels along the walls and
to other non structural items. This shed is still structurally sound
but will require wall bracing added to strengthen the structure
plus repairs to the non structural items.
B. Inspection - Shed 2
i) There is storm damage to the pipe trusses, the top chord
has been bent downwards near the apex on most of the
trusses by approximately 50 mm, also some sideways
bending.
ii) Where the trusses are attached to the columns the top of
the columns have bent.
4. Discussion and Recommendations, shed 2.
The bending of the trusses at or near the apex and the bending
of the top of the columns are classic indications that the roof of
the shed has been lifted during the storm and dropped back onto
the columns. The roof structure i s dropped downwards the roof
causes the columns to spread and with this there is a large
increases the compression on the top chord causing the bending
near the apex. The top of the columns bend as the trusses
spread and land back onto the columns.
The dam age to this shed is quite severe and in our opinion is no
longer structurally sound and will need to be demolished and re -
built.
Complainant’s expert ( WB )
Engineer’s Report
9 December 2019
We have reviewed the existing reports of [LD] and the report from
[ M K] and advise as follows:
Determination | Case number: 651625 Page 18 of 19
Reco rd Key points
1. [LD] reports of the 9th May 2013 complete reports on the
timber members on all buildings. His conclusions firstly
relate to two minor timber sheds, one not covered by
insurance, he directs that "A structural engineer to be
appo inted to determine if the timber purlins were of sufficient
size for the spans and if the storm was resultant for the
sagging of the purlins".
[MK] 's report as directed by [LD] reports mainly on the
timber members, he does comment on the buckling of the
ra fters but states that "this report does not extend to
undertaking structural analysis and design check of the steel
portal frames ... "
2. [LD]'s second report dated 14th November 2019, makes no
mention of the damage to the trusses in sheds 1 & 2 and
refers u s to [MK’s firm] .
3. Our first inspection advised that there had been serious
structural damage to the trusses ( or main structural
members of sheds 1 & 2). Our second ins pection confirms
this opinion. The trusses have been subjected to a severe
uplift loading by the wind, the wind and dead weight of the
roof has then dropped the centre area of the roof back down
creating a severe compression loading of the top chord of
the trusses at the position of maximum movement near the
apex.
This compression load could not be sustained by the truss
top c hord and it bent sideways.
We believe that if a minor wind lifted the roof again and
dropped back onto the trusses, complete failure of the
building would occur. In our opinion the sheds are ve ry
dangerous to any chickens or person within the shed and
could cause loss of life. The only item that is holding the
shed up at present is the sheds roof sheeting taking the
compression. We quote from our original report dated 31st
October 2014 "The dama ge to this shed is quite severe and
in our opinion is no longer structurally sound and will need
to be demolished and re - built". It is our present opinion that
both sheds 1 & 2 will have to be rebuilt.
Complainant’s expert ( WB )
Engineer’s Report
1 April 2020
1. The damage to the roof trusses has been caused by uplift from
suction created during a storm event, creating uplift from suction
caused by the wind blowing over the top of the sheds. Some
minor int ernal uplift would have occurred, but this loading wou ld
only be minor compared to the loading on the roof sheeting from
the suction.
Determination | Case number: 651625 Page 19 of 19
Reco rd Key points
This type of damage to a roof structure can only be caused by
strong winds usually associated with a storm front.
2. We recommend reading our previous report again (copy attached
for your convenience) as it is very clear that both shed's
structural integrity is severely compromised and have to be
demolished and re - built, the sheds cannot be repaired.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.