Home / Strata Community Insurance Agencies Pty Ltd / Determination 630135
Determination 630135
Insurer partly declined water ingress claim for sewing room ceiling as gradual damage
Summary
A strata body claimed for water ingress damage, and the insurer accepted the event but declined the sewing room ceiling damage as gradual deterioration. AFCA found the ceiling damage predated the event and was excluded, and ordered no action.
Damage caused by gradual operating causes such as wear, tear and failure to maintain is excluded, and the evidence showed the ceiling damage existed since 2016.
Subjects and remedies
no remedy
Text of the determination
Determination
Case number 630135
Financial firm Strata Community Insurance Agencies Pty Ltd
Determination | Case number: 630135 Page 2 of 7
Case number: 630135 12 December 2019
1 Determination overview
1.1 Complaint
The complainant holds a commercial strata insurance policy (the policy) underwritten
by the financial firm (insurer) covering the insured building. In January 2019, the
complainant lodged a claim seeking cover for water damage to the ins ured property,
said to have been the result of a water ingress event.
The insurer accepted the claim however has declined to cover damage to the ceiling
in the downstairs sewing room on the grounds this damage was not the result of the
event giving rise to the claim. Rather, on the balance of probabilities, this damage had
been occurring gradually over an extended period of time.
1.1 Issues and key findings
What does the policy cover?
The policy covers accidental loss or damage to the insured property subject to the
limitations and exclusions specified in the product disclosure statement (PDS).
Is the insurer entitled to limit its liability under the claim?
The insurer has been successful in establishing, on the balance of probabilities, the
damage to the ceiling in the downstairs sewing room at the insured property is not the
result of the event giving rise to the claim. Rather, on balance, this portion of the
claimed damage is clearly excluded from cover under the policy.
Accordingly, the insurer is entitled to partially decline the claim in line with the policy
provisions specified in the PDS.
1.2 Determination
This determination is in favour of the insurer.
The insurer is entitled to decline cover for the damage to the ceiling in the sewing
room given the available information and policy exclusions.
Determination | Case number: 630135 Page 3 of 7
2 Reasons for determination
This complaint has been the subject of the preliminary view provided to the parties on
15 August 2019, by AFCA. I acknowledge the preliminary view is in favour of the
complainant. Having considered the available evidence, including additional
information received after the preliminary assessment was provided, I am not of the
same view and this determination is in favour of the insurer. The reasons for this are
detailed below.
2.1 What does the policy cover?
The policy is an accidental damage policy of insurance
The policy provides cover for loss or damage to the insured property (building and
common area contents) which occurs during the period of insurance, including
additional covers as provided in the policy documentation.
Cover under the policy is subject to the policy limitations and exclusions also specified
in the PDS.
The complainant lodged a claim seeking cover for water ingress damage to one of
three offices located upstairs as well as the downstairs sewing room ceiling. The
insurer has accepted to cover the damage to the office however it has declined cover
for the ceiling damage in the sewing room.
The insurer is of the position the damage to the sewing room ceiling is not the result
of the water ingress event giving rise to the claim. Rather, that this damage has been
present for several years and has continued to deteriorate over time due to wear, tear
and gradual deterioration.
It is established law that in order to seek cover under the policy the onus first rests
with the claimant to establish, on the balance of probabilities, the loss claimed is
covered by the terms of the policy.
Only once this has been established, will the onus shift to the insurer to establish, on
balance, that it is not responsible to cover the claimant for the loss in line with a
provision or exclusion present in the terms of the policy.
2.2 Is the insurer entitled to l imit its liability under the complainant’s claim ?
The onus rests with the insurer to establish it can decline cover for the ceiling
The available information establishes the insured building has suffered damage
because of a water ingress event relating to the evaporative air-conditioning unit
located on the roof of the insured building. I accept this was an unintended and
unexpected event, therefore, a valid claim has been established under the policy.
Determination | Case number: 630135 Page 4 of 7
The insurer has sought to limit its liability under the claim to what it would cost to
repair the water ingress damage in the upstairs office only. The insurer says the
damage to the sewing room ceiling is not the result of the water ingress event
resulting in the claim.
Accordingly, the onus rests with the insurer to establish, on balance, the damage to
the ceiling in the sewing room is excluded from cover.
The parties to this complainant have sourced and rely on reports from various
consultants who have assessed the insured property over the years. These reports
have made this information available for AFCA’s consideration.
I have considered these reports and the relevant information from these reports has
been summarised in section 3 of this determination.
The damage to the sewing room ceiling existed prior to the water ingress event
I have carefully considered the information provided by the parties in support of their
respective positions relating to the damage to the ceiling in the sewing room at the
insured property.
I am of the opinion this information shows, on balance, the insured building has been
experiencing water ingress issues since at least 2015. With respect to the damaged
ceiling in question, I am satisfied it has been shown, on balance, this damage was not
the result of the more recent evaporative air-conditioning and box gutter water ingress
event.
The available information includes a dilapidation report completed by consultants’ ‘S’
in March 2016. This report includes very helpful photographic evidence that shows
cracking to the cornice/ceiling around the downpipe as well as sagging air-
conditioning vents.
A quote for repairs completed by consultant’s ‘M’ in April 2017 sourced by the
complainant, again identifies the dame damage noted in the S report a year prior as
well as identifies 3sqm of sagging ceiling which it recommends required replacement.
It is clear the damage to the sewing room ceiling had increased from what was noted
in the dilapidation report some 12 months prior.
Despite requests by the insurer, the complainant has not made available any
evidence which establishes the repairs recommended and quoted by M in 2017, were
completed to the sewing room ceiling . Further, I accept the damage noted in 2016
and later in 2017, is in the exact same location as the damage subject of the claim
giving rise to this complaint before AFCA.
Without evidence to the contrary, I accept the available information establishes on
balance that the damage noted in 2016, has gradually continued to deteriorate and
increase to the point where in 2019, the sagging increased to 75% of the ceiling. This
Determination | Case number: 630135 Page 5 of 7
being due to the complainant’s failure to address the concerns identified in 2016 and
2017.
Given this, I do not accept the complainant has been able to show, on balance, the
damage to the sewing room ceiling subject of the claim is the result of the water
ingress event which caused damage to the office.
Rather, the damage to the sewing room ceiling has been present since as early as
March 2016 and has continued to gradually increase due to wear, tear and a failure to
maintain, which are circumstances clearly excluded from cover under the policy.
I acknowledge the complainant’s reference to the fact the insurer’s appointed
assessor, after the initial assessment, accepted there was damage to the sewing
room ceiling consistent with the claimed water ingress event. However, this was
based on what he was informed of at the time and not having had the opportunity to
review the dilapidation report, M’s quote and other relevant information.
Accordingly, I determine the insurer is entitled to decline cover for the damage to the
sewing room ceiling under the claim in line with the policy exclusions specified in the
policy.
3 Supporting information
3.1 Relevant policy wording
Section 1- Insured Property
We will not pay:
(i) if gradually operating causes (such as but not limited to Wear, Tear, gradual
corrosion, gradual deterioration, wet or dry rot, rust, vermin or insects) primarily
contribute towards the Loss or Damage
3.2 Consultants’ evidence provided by th e parties
Record Key points
S Dilapidation Report
18 March 2016
the purpose of this report was to show the present condition of the
property (insured building)
the survey giving rise to the report was completed on 14 March
2016 (the sewing room subject of this complaint bet ween the
parties is referred to as the storage area in this report)
photographic evidence in this report shows damage in the form of
a crack to the ceiling cornice around the downpipe and sagging
air - conditioning ducts in the storage r oom.
Determination | Case number: 630135 Page 6 of 7
Record Key points
M’s Quote for repairs
16 March 2017
source and supply two side by side plastic air - conditioner vents,
located next to the internal downpipe in stock room (s ewing room)
disconnect light, remove 3msq section of sagging gyprock ceiling
in the stock room, scrape back existing glue and remove fixings.
Inspect adjoining sheets to see if further sections of ceiling
requires repair…
W Air - conditioning and
refrigeration report
15 January 2019
found water had leaked into the building from evaporative air -
c onditioning due to the drains being blocked from leaves and dirt
As Roofing quote damage to upper room ceiling, extensive area of water damage
due to water ingress from evaporative air - conditioning unit located
above
lower floor ceiling damage, wat er ingress damage has caused
water staining and sagging of the ceiling
TS First Report
2 February 2019
attended insured property on 29 January 2019
two evaporative air - conditioning compressor units are installed on
the roof of the insured property
TS was informed on 14 January 2019, the complainant discovered
the plasterboard ceiling in the sewing room had been damaged by
water as the cornice next to the main roof downpipe had cracked
and the ceiling panels had dropped
an inspection by consultants ‘W” appo inted by the complainant
had found the box gutter rainwater sump was blocked with debris
preventing water from evaporative air - conditioning compressors
draining into the downpipe
the following day the complainant also discovered wat er damage
to the ceiling of the middle office of three located on the upper
level of the insured property
TS concluded, based on the site visit and information from the
complainant, the damage sighted was consistent with water
overflowing a box gutter and drainage pipes from the air -
conditioning compressor units
TS Second report
19 February 2019
recently reviewed dilapidation report from 2016
the inspection of the ins ured property on 14 March 2016 show the
damage to the sewing room ceiling cornice at the edge of the
downpipe (ex act same position as it is now)
TS formed the view the damage existed before the claimed date of
loss subject of the claim
Point 2
Point 3
Email from consultant JG
18 October 2019
JG was the consultant that attended the insured property on behalf
of the TS to undertake the assessment in January 2019
JG only became aware after having submitted his first report that
the informed provided to him by the complainant was inaccurate
he reviewed the dilapidation report completed in 2016 which
Determination | Case number: 630135 Page 7 of 7
Record Key points
showed damage to the same area as claimed under the current
claim
JGT noted the quot e sourced by the complainant from M dated 16
March 2017
this quote also notes the presence of the same damage in the
sewing room as well as removal and replacement of 3msq of
sagging ceiling
given this additional information, JG from the opinion the
complainant’s failure to rectify the fault with the ceiling despite
being informed of it in 2016 and 2017, has led to further
deterioration and more noticeable sag
when ceiling fixings start to fai l, this places/passes additional load
bearing on the adjoining fixings – these adjoining fixings then
begin to fail under the inc reased load until a section of the ceiling
collapses.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.