Home / Financial Firm (Unknown - Insurer) / Determination 618638
Determination 618638
claim_denial
Summary
The insurer accepted part of the movement damage claim to the home but disputed the extent, attributing the brick wall damage to inadequate brick ties. AFCA found the leaking pipes were the proximate cause and ordered the insurer to accept the disputed damage, with no cash figure fixed.
Where a covered leak is an effective cause of damage, the insurer is liable for it, and an unknown defect such as inadequate brick ties is covered under the policy's unknown defect provision.
Issues
- Claim denial primary · upheld
“The insurer is liable for the disputed damage to the property because the available information shows the cause was ground movement due to leaking pipes.”
- Product terms interpretation secondary · upheld
“even if the inadequate brick ties were a cause, this is still covered on the basis it was an unknown defect”
Subjects and remedies
home or building damagepay claim
Text of the determination
Determination | Case number: 618638 Page 1 of 9
Determination
Case number: 618638 11 September 2019
1 Determination overview
1.1 Complaint
The complainant lodged a claim with the financial firm (insurer) under his policy for
movement damage to his home caused by an escape of liquid.
The insurer agrees this caused some damage. However, the insurer disputes it
caused the extent of the damage claimed. In particular, the insurer says the damage
to the brick wall was due to inadequate tie fixing.
The complainant disagrees with the insurer’s decision and maintains the leaking pipes
caused the movement damage.
1.2 Issues and key findings
Is the Insurer liable for the disputed damage to the property?
The insurer is liable for the disputed damage to the property because the available
information shows the cause was ground movement due to leaking pipes.
1.3 Determination
This determination is in favour of the complainant.
The insurer is required to accept the claim for the disputed damage.
Determination | Case number: 618638 Page 2 of 9
2 Reasons for determination
2.1 Is the Insurer liable for the disputed damage to the property?
Complainant established a valid claim
The complainant has the onus to establish any loss or damage arises from an event
covered by the terms and conditions of the policy. This is known as a valid ( prima
facie ) claim.
The complainant’s policy is a defined events policy. This means the policy only
responds where one or more of the listed events causes damage to the complainant’s
property, subject to any exclusions.
The complainant’s claim relates to damage to his property. He says this was caused
by foundation movement from leaking pipes.
There is no dispute the complainant has suffered some loss due to the leaking pipe,
for which the insurer has partially accepted cover. Given this, the complainant has
established a prima facie claim.
Accordingly, it falls to the insurer to demonstrate on the balance of probabilities that
the disputed damage was caused by a policy exclusion or is otherwise entitled to
deny the claim.
Property has been subject to movement and cracking damage
The complainant contacted the insurer to lodge the claim on 18 January 2017. In
doing so, the complainant told the insurer that sections of the home were starting to
move . The complainant understood stormwater and sewer pipes were cracked,
causing foundations to become weak.
The cracking and movement damage which is the subject of the claim occurred to the
rear external and i nternal parts of the property. The cracked pipes were also around
the rear of the property.
Proximate cause of damage must be determined
For the disputed damage, it is necessary to determine the proximate cause of the
loss. What is the proximate cause of the loss is a question of fact depending upon the
circumstances of each case.
It is well established a proximate cause is not necessarily the first or last or the sole
cause of the loss. It is the effective or dominant or operative cause of the loss. If there
are several causes operating contemporaneously, then each must be examined for
the qualities of predominance and efficiency.
Determination | Case number: 618638 Page 3 of 9
Courts have said that if one cause would have resulted in the harm in any case and
the other would not have done so in the absence of the first, then the first is the
proximate cause.
Experts have provided differing opinions
The experts agree the property is built on highly reactive clay soils. These are
reactive to changes in moisture. They also agree there is movement and cracking
damage to the rear property attributable from the leaking pipes.
A site investigation report was conducted by geotechnical consultants HG. HG took
bore samples from the front and rear of the property. The samples at the rear showed
the clay soils below the footing were ‘extremely moist’. This shows the leaks have
affected the moisture content of the foundation.
Following receipt of HG’s findings, engineer H provided a report dated 1 June 2017. H
concluded that the cracking and movement was due to the extreme change in the
moisture content of the foundation material due to the leaking pipes.
Engineer S said the leak did exacerbate the typical ongoing building movement
caused by seasonal moisture changes to the footings. S, however, believed that the
movement of the rear brick wall was likely due to inadequate brick ties to the upper
section.
Engineer M, in a report dated 9 July 2019, believed the proximate cause was the
inadequate footing system. M did not believe the leak or the ‘purported insufficient
b rick ties’ is the proximate cause. In a subsequent report dated 21 August 2019, M
said the damage was directly caused by the defective brick tie installation.
Proximate cause of the damage was the leaking water pipes
On balance, the panel accepts the available information shows the proximate cause
of the movement damage was the leaking pipes.
The floor levels show heave in the region of the water leak. HG’s report showed the
foundation soils were extremely moist. Given their reactive nature, it is plausible to
accept that this leak would have resulted in abnormal changes.
H and S also agree the leaking pipes would have affected the soils and caused some
damage. S appeared to indicate the damage to the brick wall was more likely due to
the insufficient brick ties.
M’s reference to the footing system being inadequate appears to be based on current
standards rather than the time of construction. S, in his report dated 9 August 2018,
acknowledged the footing system was adequate for the standards at the time of
construction.
No policy exclusion is engaged for this factor.
Determination | Case number: 618638 Page 4 of 9
Even if the panel accepts the inadequate brick ties are a cause of the damage, it is
not the proximate cause. It is clear the leak was enough to affect the wall. The
complainants note that the adjoining property was built in the same manner and
shows no signs of movement damage. This supports the fact the leak was a
proximate cause.
Further, the policy contains the following provision where an unknown defect was the
cause, or part of the cause, of damage:
If an incident covered by your policy damages your property and an unknown
defect was the cause or part of the cause, we will pay for the resulting damage. If
the unknown defective part of your property is also damaged by the same
incident, we will fix this as well.
It is clear this defect was hidden from view and would not have been apparent.
Therefore, even if the inadequate brick ties were a cause, this is still covered on the
basis it was an unknown defect.
Insurer liable for all the disputed damage
The insurer is liable for repair of the entire movement damage.
Prior to this, the complainant must repair defective pipes and plumbing identified by
the latest leak detection report (LV) before the insurer is required to repair the
property.
If the parties agree to a cash settlement, it must be based on an actionable quote and
on an agreed scope of works. These scope of works should include the brick wall and
be compiled by an engineer.
Further, if the property cannot be tenanted due to the works, or has not been tenanted
because of the damage (or both), then the insurer must consider a loss of rent claim.
Determination | Case number: 618638 Page 5 of 9
3 Supporting information
3.1 Terms of the policy
Record Key points
What you are covered for -
Insured events
Escape of liquid
Loss or damage caused by liquid leaking, overflowing or bursting
from any of the following:
Any drain, fix ed pipes, roof gutters or guttering and rain water
downpipes, drainage and sewage systems .
Fixed tanks
Water main, fire hydrant or water supply pipe.
We do not cover
The cost of repairing or replacing the item from which the liquid
escaped.
General exclusions You are not covered under any section of this policy for damage,
loss, cost or legal liability that is caused by, arises from or
involves:
Ground movement
Erosion, vibration, subsidence, landslip, landslide , mudslide,
collapse, shrinkage or any other earth movement, but we will
cover landslide or subsidence that is specifically covered under
the following insured events:
Storm .
Flood
Earthquake and Tsunami
Explosion
Dealing with defects If an unknown defect is the cause of the damage
If an incident covered by your policy damages your property and
an unknown defect was the cause or part of the cause, we will
pay for the resulting damage. If the unknown defective part of
your property is also damaged by the same incident, we will fix
this as well.
3.2 Expert reports
Record Key points
financial firm’s expert
(HCE)
Report
02 - 03 - 2017
Along the rear wall there is tapering vertical crack along the
articulation joint near the south west corner
The eaves lining at this corner has cracked.
The broken sewer pipe is adjacent to this articulation joint.
Determination | Case number: 618638 Page 6 of 9
Record Key points
The inspection of rear wall showed brickwork is out of plumb with
rotation occurring towards the rear r esulted in gaps around the
window frames.
There is an articulation joint in the brickwork close to the nort h
west corner.
This articulation joint showed negligible movement along the
articulation joint.
The movement of the brickwork is limited to the rear elevation.
The shearing right through of the stormwater drain indicates that
settlement of the ground around the drain has occurred.
An internal inspection showed at ground level there are horizontal
cracks of the wall lining along the rear wall of the kit chen and
meals area at the rear.
First floor level showed there is a crack evident of the wall lining
of the south wall above the meals area.
There is a large Cypress tree growing within the adjoining west
property near the fence line.
Soil is classified as highly reactive.
There is a council stormwater drain and reticulated sewer pipe
within the easement along the rear of the property.
The cracking and movement is typical of problems that can occur
due to differential settlement of the footings.
Differen tial settlement of the footings can occur due to seasonal
changes in the moisture content of the foundation mat erial which
can be accentuated by tree root drying and wat er escaping from
leaking plumbing pipes.
Tree root drying from the Cypress tree wit hin the rear adjoining
property close to the fence line has accentuated the season
changes in moisture content of foundation material, resulting in
differential settlement of footings and cracking.
The cracking and movement is a result of differential settleme nt
of the footings due to seasonal changes in the moisture content
of the foundation material and accentuated by tree root drying
from the Cypress tree growing within the adjoining rear property
and by water escaping form the leaking plumbing pipes.
it als o our opinion that the cracking and movement has been
contribut ed by the inadequate construction in that the footings are
founded above the angle of the repose line.
financial firm’s expert
(HCE)
Report
01 - 0 6 - 2017
The plumbing investigation identified pro blems with the plumbing
pipes adjacent to and close to the rear wall of the residence ,
allowing water to reach the foundation material below the rear of
the residence.
Water reaching foundation material could be contributing to
extreme changes in moisture cont ent of the foundation due to
saturation of and the subsequent drying out of the saturat ed
foundation material.
The cracking and movement of the residence is a resu lt of
differential settlement occurring of the footings due to an extreme
Determination | Case number: 618638 Page 7 of 9
Record Key points
change in the moisture content of foundation material due to the
leaking pipes and contributed by loss of bearing capacity of
founding mat erial considering the very high moisture con t ent
readings.
financial firm’s expert
( ALD )
Report
12 - 05 - 2017
Visual inspection found breaks to storm water and sewer pipes
where lines penetrat e external brick wall at rear of property.
This allows water to leak to surrounding soil area.
CCTV inspection to below ground sewer line found a break to
PVC pipe below rear grass area.
This is allowing water to leak from line and appears to be on join
where line drops vertically into sewer easement.
CCTV inspection to storm water line from front garage found the
line to run to rear surface drain.
Inspected line fault free.
Unable to access approximately 5m of line below rear concrete
area due to multiple 90 - degree elbow fittings to line prohibiting
access.
Inspection of rear surfac e drain found separati on to pipe just
below ground level allowing small amounts of wat er to leak from
line.
Water found to be holding to remainder of line.
Pipework suspended to subfloor was inspected and was leak
free.
financial firm’s expert
( SE )
Report
09 - 08 - 2018
The insured has owned property for 17 years.
The leaking plumbing pipes to rear of hous e were fixed last
June/July 2017.
Significant fall ac ross property towards the north west.
The following was noted to wall articulation joints in close
proximity to leak:
Ex ternal
South west external corner of the garage has a tapered gap
increasing win width up to 15mm to the top of the first - floor wall.
Joint below the dining room sliding door (eastern side) found
negligible movement.
Joint located to the western edge of th e northern living room
window had minor taper.
South west corner (adjoining leak) has tapered width crack
increasing in width up the wall (overall joint estimated to be 50mm
wide).
Only one brick tie noted in the wall segment (over 16 courses )
between the top of living room window and base of bedroom
above.
Horiz ontal crack was noted 2 courses down from the top of the
western wall with brick below the crack moving out ward
(potentially relat ed to inadequat e/defective installation of brick
Determination | Case number: 618638 Page 8 of 9
Record Key points
ties).
Tapered gap formed bet ween the window and the frame nort hern
edge and adjoining brickwork.
Minor surface depression in ground surfac e.
Tree in neighbour’s property removed.
Subfloor
Soil conditions appeared relatively dry below the living room.
Cement sheet packers found under the bearers below living
room.
Ground subfloor framing did not appear to be connected to
western brick veneer wall.
Internal
Horiz ontal wall cracks western wall of living room) adjoining the
leak.
Creaking floors in family room/kitchen unrelated to leak event.
The maximum level difference over the floor of the house was
97mm.
The low point was recorded the north - east of the family room.
The high point was recorded to the south west corner of the living
room (location of previous leak).
A pattern of increasing (rais ed/heaved) floor movements towards
the west in direction of the leak.
Pattern of falls to the front of the house.
No patterns of relative settlement of the western region towards
the previous large tree in neighbour property.
Th e floor level results do not indicate any such movement has
occurred, ie the floors have risen adjoining the leak and not
subsided.
Therefore, bearing failures are not suspected.
Strip footings are undersized and understrength compared to
current standards and these footings are more susceptible to
seasonal/tree drying and leak related foundation movement.
One brick tie was noted in the western wall articulation joint over
a length of 16 courses of bricks which is inadequat e and defective
to relevant standa rd.
The top course of brick veneer is held in position by the roof
trusses/eaves framing, while lower wall brick veneer skin has
pulled away from adjoining timber wall framing. This indicates
potential failure of the brick ties and inadequat e brick tie fix ing .
This is consistent with the lack of damage to internal plasterboard
linings and the adjoining western wall of the southern duplex,
which is close proximity to leak location
If the brick ties to the western wall were correctly installed than
we would e xpect the crack damage would not have occurred. It is
concluded that brick ties have been adequately installed.
Defective brick tie fixings have been present since construction
and is likely that normal seasonal footing movements and that
exacerbated by ne arby trees may have caused cracking,
movement to the top floor prior to the leak.
Determination | Case number: 618638 Page 9 of 9
Record Key points
financial firm’s expert
(HG)
Report
04 - 05 - 2017
Soil profile and climatic zone of the site has been classified class
P due to abnormal moisture conditions, trees and fill.
Stormwater/service pipe outfall is pouring directly above the area
with the most significant movement.
Boreholes revealed that moisture levels of clay soils below the
footing at the rear are extremely moist.
The founding material is completely saturated.
financial firm’s expert
( LV )
Report
05 - 08 - 201 9
A ttend site to conduct a leak detection and CCTV inspection at
the property, to determine whether there were any items still
leaking at the property.
C onducted a pressure test and the hot water held pressure
T he cold water would not hold pressure .
Rear garden tap spindle is leaking.
B asin taps are continually dripping and will not turn off.
CCTV inspection of the stormwater drain conducted.
The surface channels and grat es are in poor condition .
They are not se aled to the concrete, gaps exist that water can
leak into before entering the channel.
S tormwater pipe connections are unsealed and too high.
Water will leak through uns ealed areas before discharging to
drain pipes.
I nspected the drain and could not locate any damage to the pipes
or fittings on this section of the drain .
I nspected the rear section of drain through the garage rain head
and downpipe .
S tormwater fittings and pipe near the rear surface water pit are
broken and leaking.
No damage found to sewer drain.
The drain was free and clear of any debris or blockages.