Home / Financial Firm (Unknown - Insurer) / Determination 618063
Determination 618063
Claim declined for garage ceiling collapse under gradual deterioration exclusion
Summary
The complainant claimed under her home building policy after her garage ceiling collapsed. The insurer declined the claim under the gradual deterioration and wear and tear exclusion, and AFCA agreed.
On the balance of expert evidence the proximate cause was long-term factors, which fall within the policy exclusions for gradual deterioration and wear and tear.
Issues
- Claim denial primary · not upheld“The insurer was entitled to decline the claim because ... the failure was due to a combination of factors, all of which were long term in nature.”
Subjects and remedies
no remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination | Case number: 618063 Page 1 of 7
Determination
Case number: 618063 17 July 2019
1 Determination overview
1.1 Complaint
The complainant holds a home building insurance policy underwritten by the financial
firm (the insurer) covering her home address.
On 3 June 2018, the garage ceiling collapsed, and the complainant subsequently
lodged a claim under the policy for the repairs required. The complainant stated the
high winds present on the day of the loss was the cause of the ceiling failure.
After considering the claim, the insurer concluded the collapse of the ceiling was due
to a combination of factors, all of which were long term. As loss of this nature is
specifically excluded from cover under the policy, the insurer declined the claim.
1.2 Issue and key findings
Was the insurer entitled to decline the claim?
The insurer was entitled to decline the claim because the material shows that, on
balance, the failure was due to a combination of factors, all of which were long term in
nature.
As the policy specifically excludes loss or damage arising from gradual deterioration
and wear and tear, the exclusion operates to defeat the claim.
1.3 Determination
This determination is in favour of the insurer.
The insurer was entitled to decline the claim and is not required to take any further
action.
Determination | Case number: 618063 Page 2 of 7
2 Reasons for determination
2.1 Was the insurer entitled to decline the claim?
Complainant has established a prima facie claim
It is accepted insurance law that the complainant carries the initial onus of proving
that an insured event has occurred. This is known as a prima facie claim.
The insurer’s policy is an accidental damage policy. However, coverage is subject to
exclusions and limitations. Accidental damage is generally held to be damage which
is sudden and unforeseen.
It is only once the complainant has established a prima facie claim, that the onus
shifts to the insurer if it wishes to deny the claim by way of an exclusion under the
policy or on some other basis.
There is no dispute the garage ceiling collapsed, which was sudden and unforeseen.
Accordingly, the complainant has established a prima facie claim under the terms of
the policy and the insurer must now establish it is entitled to decline the claim.
Proximate cause of the loss must be a covered event
When considering whether a policy exclusion applies to defeat the claim, or there is
some other basis on which a loss is not covered, it is appropriate to first determine the
proximate cause of the loss. The proximate cause of the loss is a question of fact
depending upon the circumstances in each case.
It is well established at law that a proximate cause is not necessarily the first or the
last or the sole cause of the loss. It is the effective or dominant or operative cause of
the loss. If there are several causes operating contemporaneously, then each must be
examined for the qualities of predominance and efficiency as the active, efficient
cause that sets a relevant train of events in motion.
Courts have said that if one cause would have resulted in the harm in any case and
the other would not have done so in the absence of the first, then the first is the
proximate cause.
Insurer says loss caused by long term factors
The insurer appointed builder ‘UB’ to inspect the property and provide an opinion as
to the cause of the loss. Details of the expert reports provided are contained within
section 3.2 of this determination.
UB considered the cause of the failure was due to the faulty installation of the
plasterboard. UB noted there was no sarking, moisture barrier paint or insulation
used. This meant the ceiling was subject to moisture absorption, which led to its
eventual collapse. UB considered the cause of the failure was due to the faulty
Determination | Case number: 618063 Page 3 of 7
installation of the ceiling, which did not comply with the building standards applicable
at the time.
The insurer also appointed building consultant ‘CR’ to comment on the cause of the
loss. CR considered the damage was due to a combination of factors, all of which had
acted in conjunction to cause the failure.
CR considered the long-term factors of the exposure of the property to varying
strengths of wind and wind gusts would cause long term residual deflection of the roof
trusses, including the chords to which the ceiling was attached. This deflection
contributed to the failure of the physical connection between the ceiling lining and
fixing points.
Complainant’s expert says loss caused by high winds
The complainant disagrees with the insurer’s experts , saying they did not properly
inspect the property and the conclusions are flawed. She provided her own expert
opinion from builder ‘SH’ in support of her position that th e damage was caused by
high winds. I have considered this report as part of my review.
SH disagreed with UB’s findings and said there was no requirement for there to be
sarking or insulation fitted to comply with the building standards at the time of
construction. SH completed moisture testing to the plasterboard noting it had no
moisture reading, nor were there signs of water or moisture present. SH did not
consider this to be a factor in the collapse.
SH concluded the cause of the failure was the high winds on the day of the loss,
which had caused a pressurised action effectively sucking the ceiling down from its
fixings.
Evidence of CR is preferred
It is always difficult when faced with conflicting expert opinions to determine which
evidence is more persuasive. After careful consideration, I prefer CR’s evidence in
this matter.
There are several reasons for this. Firstly, although SH attributes the damage to high
winds on the day of the loss, the data from the Bureau of Meteorology shows the
maximum wind speed at the nearest weather station was only 17kph. According to
the Beaufort Wind Scale, wind of this speed is not of sufficient velocity to cause
structural damage to a property.
SH says moisture tests were conducted on the plasterboard which showed a zero
reading, proving there was no moisture on the sheets. However, no evidence of these
tests has been provided.
Accordingly, I can place little weight on SH’s conclusions.
Determination | Case number: 618063 Page 4 of 7
Similarly, UB states the cause of the failure was due to faulty installation of the ceiling
and its failure to comply with the relevant building standards at the time. However, this
is refuted by both CR and SH. This means UB’s report also carries less weight as a
result.
Failure was due to long term factors
This leaves the evidence of CR for consideration.
The complainant says her location regularly experiences wind speeds far in excess of
those recorded at the closest weather station, including on the day of the loss. Whilst I
agree the location’s elevated and bayside location mean it may experience wind
speeds in excess of those recorded at the nearby weather station, there is no
evidence before me to suggest what those wind speeds would be.
As the only reliable data given is that from the weather station, which shows minor
velocity winds on the day, there would need to be some compelling evidence
presented to s how the complainant’s location nearby experienced a great variation in
windspeed on the day of the loss. However, there is not.
In my view, that the property is reportedly regularly affected by strong winds tends to
support CR’s conclusion that the cause of the failure was due to long term deflection
on the ceiling trusses, which eventually caused the failure of the attached
plasterboard lining. Photographs supplied by the parties are consistent with CR’s
findings.
Therefore, even if it were accepted there were high winds on the day of the loss, this
would not necessarily be the dominant cause of the loss. The material shows, on
balance, the proximate cause of the loss was the combination of factors at the site
including ongoing wind loads, high humidity build up on the metal roof sheets and the
flexing of the roof trusses. All of these factors were long term factors which eventually
caused the ceiling to detach and collapse.
Long term factors excluded from cover
Even accepting the complainant has established a prima facie claim under the policy,
the policy specifically excludes loss arising from gradual deterioration and wear and
tear. As the proximate case of the loss falls within the exclusions from cover, I am
satisfied the exclusions from cover would be operative in the circumstances.
On this basis, the complainant has not established she suffered a loss which is
covered by the policy terms and the insurer was entitled to decline the claim.
Determination | Case number: 618063 Page 5 of 7
3 Supporting information
3.1 AFCA approach to this dispute
This complaint has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous decisions of AFCA or its predecessor schemes (which are not binding).
A full exchange of the relevant information has taken place between the respective
parties. Each party has had the opportunity of addressing any issues raised.
All of the provided material has been reviewed and considered. The parties have
raised numerous issues in their submissions to AFCA. However, commentary in this
determination is restricted only to those issues considered relevant to the outcome.
3.2 Relevant expert reports
Record Key points
Insurer’s expert ( UB )
Builder’s Report
5 June 2018
inspection revealed the garage ceiling had collaps ed and
detached from its fixing points
inspection of the ceiling cavity showed no sarking installed to
prevent moisture from dropping onto the plaster sheets
no ceiling ins ulation had been installed either, which also acts as a
mo isture barrier
the ceiling has also been painted with flat paint which is not a
moisture barrier
the damage is consistent with moisture absorption due to high
humidity over time
the plaster has weakened over time due to the moisture
absorption to the point where the plasterboard has softened, and
pulled out the fixtures
as one section fails, additional load is transferred to the remaining
sections, causing them to also fail
the damage is due to faulty workmanship/ poor installation.
Complainant’s expert ( SH )
Builder’s Report
7 July 2018
there were no signs of water ingress to the ceiling which could
have caused the collaps e
there were no other signs of damage to the premis es
there were no humidity damage, condensation or water marks
the stud adhesive had s eparated itself from the roof cavity side of
the plaster
the only possible cause of the failure was due to high winds
causing a low pressure which would suck the ceiling out
this was not caused by a lack of ins ulation.
Complainant’s expert ( SH )
Builder’s Report
25 September 2018
the ceiling was installed correctly
although the standards have since altered, the ceiling was
installed in accordance with the standards applicable at the time
Determination | Case number: 618063 Page 6 of 7
Record Key points
there was no sign of deterioration in the plaster or any signs of
fungus growth that could be caused by humidity
moisture tests on the plaster were performed, which showed a
zero reading
roof trusses are designed to flex as one unit; therefore, the plaster
will move as one and not individually
the movement of th e trusses has not caused the failure of the
ceiling
the cause of the collaps e was due to extremely high winds on the
day which has caused positive pressure in the ceiling space,
resulting in the collapse
even though the garage door opening causes a vacuum reaction,
the high winds were the cause as the ceiling had stood for 15
years prior.
Insurer’s expert ( UB )
Supplement ary Report
28 June 2018
the current building regulations have been in place for 20 years
and there would have been a requirement for sarking in 2002
when he home was constructed
there has been no defined event which has caused the ceiling to
collapse
it is possible if there was sarking in place, moisture absorption
would still occur due to the area being a garage with no insulation
and painted with flat paint which is not a moisture barrier.
Insurer’s expert ( CR )
Building Consultant Report
28 August 2018
the residence is a single story, brick veneer construction on a
concrete slab
it was built in 2003 and is in good condition
the property is located approximately 3km from Port Phillip Bay
the property is located at a high point in the terrain and is often
subject to high winds
inspection of the roof space showed the plaster was fixed to a
metal furring channel, which had been screw fixed to the bottom
chords of the roof channel
inspection of the ceiling lining showed it was deficient in some
aspects however the lack of back blocking had not been a
causation factor in the collapse
condensation was noted on the undersides of the metal roof
sheets however no signs of wat er was noted to the plasterboard
sheeting
no sarking had been installed however this was not a mandat ory
requirement in this instance, nor was the installation of insulation
notwithstanding the above, humidity and conden sation build up in
the roof spac e above the garage can lead to dilapidation of the
ceiling lining and can weaken its structural integrity at the fixing
points
on the date of loss, the humidity was relatively high at 96%
whereas the wind speed was low at 17 kph
given the exposed location of the dwelling and prevalent wind
direction, the garage including the roof frame trusses would be
Determination | Case number: 618063 Page 7 of 7
Record Key points
exposed to varying strengths of wind and gusts
this would cause long term residual deflection of the roof trusses,
including t he bottom chords to which the ceiling was attached
this deflection will contribute to the dilapidation of the physical
connection between the ceiling lining and fixing points
the collapse is consistent with having been caused by the
following contributing factors:
o the plasterboard lining not having been installed strictly in
accordance with the general requirements of the
installation guidelines
o the relative humidity within the roof space including
condensation build up
o residual flexing of the roof trusses which support the
ceiling lining
o the topographical area in which the residence is
constructed and the resultant wind and wind gusts
o the common use of the automatic panel lift door of the
garage
all of which have caused the premature dilapidation of the ceiling
lining leading to its event ual collaps e.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.