Claim for switchboard electrical damage and generator hire declined under wear and tear and electrical breakdown exclusions
Text of the determination
Determination | Case number: 613189 Page 1 of 7
Determination
Case number: 613189 2 July 2019
1 Determination overview
1.1 Complaint
The complainant held an insurance policy with the financial firm (insurer). When the
main switchboard to her property lost power, the complainant lodged a claim for
electrical repairs and the cost to hire generators for the property.
The insurer declined the claim, saying the cause of damage to the main switchboard
was electrical breakdown, wear and tear and/or gradual deterioration, which are
exclusions under the policy.
1.2 Issue and key findings
Was the insurer entitled to decline the claim?
The insurer was entitled to decline the claim. This is because:
there is no dispute the property sustained damage from the incident, therefore the
complainant has established a prima facie claim
however, the information provided indicates the switchboard failed due to electrical
failure caused by gradual deterioration of the cabling
damage caused in this manner is excluded under the policy.
1.3 Determination
This determination is in favour of the insurer.
The insurer was entitled to decline the claim and is not required to take any further
action.
Determination | Case number: 613189 Page 2 of 7
2 Reasons for determination
The complainant is a company, which was represented during the course of the
dispute. References throughout the determination to the complainant include
reference to the representative.
2.1 Was the insurer entitled to decline the claim?
Complainant has established prima facie claim
The initial onus is with the complainant to establish the loss is covered by the policy.
This is known as a valid, or prima facie , claim.
Once the complainant has established a prima facie claim, the onus shifts to the
insurer to establish, on balance, the application of a policy exclusion or that it is
otherwise entitled to decline the claim under the policy.
The complainant holds an insurance policy for a co mmercial building and contents.
The complainant says her main switchboard lost power and had to arrange for
electrical repairs to restore power to the tenants at the property. The complainant
claimed for the electrical repairs and the cost of the hire of generators for a four-day
period.
The policy covers physical loss, destruction or damage to the property and there is no
dispute the building suffered damage due to the incident. The complainant has
therefore established a prima facie claim and the onus therefore shifts to the insurer
to show an exclusion applies or that it is otherwise entitled to decline the claim.
Conflicting expert reports on cause of damage
The complainant provided a report from an electrician (ET), which undertook a make
safe to the property. It says due to a loss of mains power, it caused a surge and short
within the main switch, which resulted in the burn out of both the mains supply into the
switch, and metering tails out of the main switch.
ET stated in the week before this incident, there was a motor vehicle incident which
disconnected power to the whole city block and demolished a power pole. It says
whilst this incident cannot be wholly attributed to the motor vehicle accident, it
considers this was a contributing factor to the power surge which caused the damage
to the cabling at the main switch.
The complainant says a power surge occurred on 7 September 2018, as a direct
result of the motor vehicle incident, which went through the TN fuse, but did not
activate until seven days later.
The complainant’s power supplier (TN) provided a report on the incident , confirming it
responded to a fault call on 14 September 2018 and determined the main switch had
Determination | Case number: 613189 Page 3 of 7
burnt out. It stated the sub-board was old and would need replacing at some stage in
the future.
The insurer sought further information from ET in resp onse to TN’s report. ET stated it
was unable to provide a definitive answer in the report and ascertain the cause but
provided a possible cause only. ET also stated it is plausible for there to be more than
one cause for the resulting fault on site, or contributing factors working together to
result in the fault.
The insurer appointed a loss adjuster (C) to report on the cause of damage. C stated
the main electrical isolation switch in the switchboard suffered a failure as a result of
an electrical burnout, caused by an overloading of the mains supply cable and the
switch.
C says there is no information regarding damage to equipment or plant installed
within any of the tenancies, which would be expected in a power surge. It states a
power surge would have caused more damage to the property.
The complainant says C only completed a desktop assessment and a qualified
electrician on its behalf never attended the property.
ET then provided a further report, in respo nse to C’s report, which states a tenant
experienced issues with their equipment due to the motor vehicle incident on 7
September 2018, including a circuit tripping that needed to be reset. ET also states
the consumer mains cabling complies with the relevant Australian Standard and is
sufficient for the load drawn. ET says the cause of the damage is therefore not
directly related to the existing installation of cabling.
Insurer says costs are excluded
The insurer declined the claim, saying the cause of damage to the main switchboard
was electrical breakdown, wear and tear and/or gradual deterioration, which are
exclusions under the policy.
The insurer says C only completed a desktop assessment because the repairs had
already been undertaken, however it says the photographs are very clear.
The insurer says the information provided does not support the claim that a motor
vehicle incident caused the damage. The insurer says if the motor vehicle incident
caused the damage, it would have caused the damage immediately, rather than one
week later. It says if a power surge caused the damage, damage to the equipment or
plant installed would have been expected. It says the photographs provided show
damage consistent with electrical overload over a prolonged period of time.
Insurer entitled to decline the claim
Whilst ET states the motor vehicle collision could have contributed to the damage, it
says it could only provide a possible cause and could not be definitive. ET does not
Determination | Case number: 613189 Page 4 of 7
provide any other possible reasons for the damage. C, on the other hand, provides a
definitive opinion on the cause of damage, being the cables had deteriorated over
time due to excessive power overload.
Whilst ET states the cabling was sufficient for the load drawn, TN confirms the sub-
board was old, which does support C’s conclusion. ET also confirms in its report that
the establishment was not acceptable nor to current Australian Standards and it
needed to upgrade the switchboard. It also confirms the main switch had burnt out.
I consider it is possible the motor vehicle collision contributed to the damage;
however, it is difficult to reconcile the one week delay between the collision and the
damage at the complainant’s premises. Without any further expert evidence to clearly
link the events, I am unable to find, on balance , the cause of the damage was the
motor vehicle collision.
Rather, having considered all of the available information, I consider it is more
plausible the damage occurred due to an electrical failure caused by gradual
deterioration of the cabling. As this cause of damage is excluded under the policy, the
insurer was entitled to decline the claim.
Determination | Case number: 613189 Page 5 of 7
3 Supporting information
3.1 Relevant policy provisions
Section 1
Property
…
We cover You for physical loss, destruction or damage to Property that occurs at
the Situation during the Period of Insurance.
…
Specific exclusions
We will not pay You under this Section 1 for physical loss, destruction or damage
caused by, or as a consequence of:
…
10. mechanical, hydraulic, electrical or electronic breakdown, failure, malfunction
or derangement of any instrument, machine, device, or temperature controlling
equipment;
…
13. wear and tear, fading, scratching or marring, gradual deterioration, developing
flaws, normal up-keeping or making good;
…
Section 2
Loss of Income
Cover
We will cover You if the Business is interrupted or interfered with as a result of
physical loss, destruction or damage occurring during the Period of Insurance to:
1. Property insured under any of the following sections of the Policy:
a) Section 1 – Property;
…
for which a claim has been paid or liability admitted, or such claim would have
been paid or liability admitted but for the application of an Excess.
…
Item 2. Additional increased cost of working
the cost of further expenditure not otherwise payable under this section,
necessarily and reasonably incurred during the Indemnity Period in consequence
of the physical loss, destruction or damage, for the sole purpose of avoiding or
minimising a reduction in Income (but not exceeding the reduction in Income
thereby avoided) or resuming or maintaining the normal operation of the
Business.
Determination | Case number: 613189 Page 6 of 7
3.2 Summary of relevant reports
Record Key points
ET
24 - 09 - 2018
it undert ook a make safe to the property due to a tenancy
losing power to some equipment
it inspected the main switchboard and found the tails to the
main switch had burnt out
temporary power was organised for the three tenancies
it replaced the main switchboard and meter tails and updated
the switchboard to meet current Australian Standards
due to the loss of main s power, this caused a surge and short
within the main switch, which resulted in the burn out of both
the mains supply into the switch, and metering tails out of the
main switch .
TN
13 - 11 - 2018
its fault crew responded to a fault call on 14 September 2018,
who determined the main switch had burnt out
the crew advised the customer the sub - board was old, and it
would need replacing at some stage in the future, however it
required the main switch to be repaired before supply could be
restored
TN received a cal l from another customer on the day from the
same building and that fault was linked to the same burnt out
main switch .
C
19 - 11 - 2018
the main electrical isolation switch in the switchboard suffered
a failure as a result of an electrical burnout, caused by an
overloading of the mains supply cable and the switch
the mains side and cable to the electrical metering were found
to be deteriorated due to overheating caused by the overload
of the power circuits
the damage is not consistent with what would be excepted
under a power surge and/or short circuit fault condition
it is clearly evident the insulation of the mains cable and cable
tails to the supply authority meters has deteriorated over time
due to excessive power overload caus ed by the tenancies
draw ing power in excess of the power rating capacity of the
mains cable and met er tails .
ET
23 - 11 - 2018
a tenant on site noted on 7 Sept ember 2018, issues within the
tenancy started with their three - phase equipment due to the
car accident fault, including a ci rcuit to the three - phas e oven
tripping and needing to be reset
ET attended the tenant’s site on 14 September 2018 due to
power loss to some equipment
TN does not comment on whether the existing service fuses
were to current standards
the current carrying c apacity of the existing consumer mains
Determination | Case number: 613189 Page 7 of 7
Record Key points
does not exceed the 100A existing main switch
the existing maximum demand per phase and currently
installed consumer mains cabling comply with the relevant
Australian Standard
the consumer mains cabling complies, is s ufficient for the load
drawn, and as such the cause is not directly related to the
existing installation of cabling but more contributed to other
reasons outlined in its report .
3.3 AFCA approach to this complaint
This complaint has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous decisions of AFCA or its predecessor schemes (which are not binding).
A full exchange of the relevant information has taken place between the respective
parties. Each party has had the opportunity of addressing any issues raised.
All of the provided material has been reviewed and considered. The parties have
raised numerous issues in their submissions to AFCA. However, commentary in this
determination is restricted only to those issues considered relevant to the outcome.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.