Home / Financial Firm (Unknown - Insurer) / Determination 613189

Determination 613189

Claim for switchboard electrical damage and generator hire declined under wear and tear and electrical breakdown exclusions

FirmFinancial Firm (Unknown - Insurer)
Decided2019-07-02
ProductGeneral Insurance · Home building and contents
OutcomeFor the firm
Amount awarded—
Non-financial loss—
Amount claimed—
SourceAFCA PDF

Summary

A company that owns a commercial building claimed for switchboard damage and generator hire after a power loss. AFCA found the damage was more plausibly caused by gradual cable deterioration, which the policy excludes, so the decline stood.

Once a prima facie claim is established the insurer must show an exclusion applies, and on balance the evidence favoured gradual deterioration over the earlier vehicle collision.

Issues

Subjects and remedies

home or building damagemotor vehicle collisionno remedy

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Determination | Case number: 613189 Page 1 of 7 Determination Case number: 613189 2 July 2019 1 Determination overview 1.1 Complaint The complainant held an insurance policy with the financial firm (insurer). When the main switchboard to her property lost power, the complainant lodged a claim for electrical repairs and the cost to hire generators for the property. The insurer declined the claim, saying the cause of damage to the main switchboard was electrical breakdown, wear and tear and/or gradual deterioration, which are exclusions under the policy. 1.2 Issue and key findings Was the insurer entitled to decline the claim? The insurer was entitled to decline the claim. This is because:  there is no dispute the property sustained damage from the incident, therefore the complainant has established a prima facie claim  however, the information provided indicates the switchboard failed due to electrical failure caused by gradual deterioration of the cabling  damage caused in this manner is excluded under the policy. 1.3 Determination This determination is in favour of the insurer. The insurer was entitled to decline the claim and is not required to take any further action. Determination | Case number: 613189 Page 2 of 7 2 Reasons for determination The complainant is a company, which was represented during the course of the dispute. References throughout the determination to the complainant include reference to the representative. 2.1 Was the insurer entitled to decline the claim? Complainant has established prima facie claim The initial onus is with the complainant to establish the loss is covered by the policy. This is known as a valid, or prima facie , claim. Once the complainant has established a prima facie claim, the onus shifts to the insurer to establish, on balance, the application of a policy exclusion or that it is otherwise entitled to decline the claim under the policy. The complainant holds an insurance policy for a co mmercial building and contents. The complainant says her main switchboard lost power and had to arrange for electrical repairs to restore power to the tenants at the property. The complainant claimed for the electrical repairs and the cost of the hire of generators for a four-day period. The policy covers physical loss, destruction or damage to the property and there is no dispute the building suffered damage due to the incident. The complainant has therefore established a prima facie claim and the onus therefore shifts to the insurer to show an exclusion applies or that it is otherwise entitled to decline the claim. Conflicting expert reports on cause of damage The complainant provided a report from an electrician (ET), which undertook a make safe to the property. It says due to a loss of mains power, it caused a surge and short within the main switch, which resulted in the burn out of both the mains supply into the switch, and metering tails out of the main switch. ET stated in the week before this incident, there was a motor vehicle incident which disconnected power to the whole city block and demolished a power pole. It says whilst this incident cannot be wholly attributed to the motor vehicle accident, it considers this was a contributing factor to the power surge which caused the damage to the cabling at the main switch. The complainant says a power surge occurred on 7 September 2018, as a direct result of the motor vehicle incident, which went through the TN fuse, but did not activate until seven days later. The complainant’s power supplier (TN) provided a report on the incident , confirming it responded to a fault call on 14 September 2018 and determined the main switch had Determination | Case number: 613189 Page 3 of 7 burnt out. It stated the sub-board was old and would need replacing at some stage in the future. The insurer sought further information from ET in resp onse to TN’s report. ET stated it was unable to provide a definitive answer in the report and ascertain the cause but provided a possible cause only. ET also stated it is plausible for there to be more than one cause for the resulting fault on site, or contributing factors working together to result in the fault. The insurer appointed a loss adjuster (C) to report on the cause of damage. C stated the main electrical isolation switch in the switchboard suffered a failure as a result of an electrical burnout, caused by an overloading of the mains supply cable and the switch. C says there is no information regarding damage to equipment or plant installed within any of the tenancies, which would be expected in a power surge. It states a power surge would have caused more damage to the property. The complainant says C only completed a desktop assessment and a qualified electrician on its behalf never attended the property. ET then provided a further report, in respo nse to C’s report, which states a tenant experienced issues with their equipment due to the motor vehicle incident on 7 September 2018, including a circuit tripping that needed to be reset. ET also states the consumer mains cabling complies with the relevant Australian Standard and is sufficient for the load drawn. ET says the cause of the damage is therefore not directly related to the existing installation of cabling. Insurer says costs are excluded The insurer declined the claim, saying the cause of damage to the main switchboard was electrical breakdown, wear and tear and/or gradual deterioration, which are exclusions under the policy. The insurer says C only completed a desktop assessment because the repairs had already been undertaken, however it says the photographs are very clear. The insurer says the information provided does not support the claim that a motor vehicle incident caused the damage. The insurer says if the motor vehicle incident caused the damage, it would have caused the damage immediately, rather than one week later. It says if a power surge caused the damage, damage to the equipment or plant installed would have been expected. It says the photographs provided show damage consistent with electrical overload over a prolonged period of time. Insurer entitled to decline the claim Whilst ET states the motor vehicle collision could have contributed to the damage, it says it could only provide a possible cause and could not be definitive. ET does not Determination | Case number: 613189 Page 4 of 7 provide any other possible reasons for the damage. C, on the other hand, provides a definitive opinion on the cause of damage, being the cables had deteriorated over time due to excessive power overload. Whilst ET states the cabling was sufficient for the load drawn, TN confirms the sub- board was old, which does support C’s conclusion. ET also confirms in its report that the establishment was not acceptable nor to current Australian Standards and it needed to upgrade the switchboard. It also confirms the main switch had burnt out. I consider it is possible the motor vehicle collision contributed to the damage; however, it is difficult to reconcile the one week delay between the collision and the damage at the complainant’s premises. Without any further expert evidence to clearly link the events, I am unable to find, on balance , the cause of the damage was the motor vehicle collision. Rather, having considered all of the available information, I consider it is more plausible the damage occurred due to an electrical failure caused by gradual deterioration of the cabling. As this cause of damage is excluded under the policy, the insurer was entitled to decline the claim. Determination | Case number: 613189 Page 5 of 7 3 Supporting information 3.1 Relevant policy provisions Section 1 Property … We cover You for physical loss, destruction or damage to Property that occurs at the Situation during the Period of Insurance. … Specific exclusions We will not pay You under this Section 1 for physical loss, destruction or damage caused by, or as a consequence of: … 10. mechanical, hydraulic, electrical or electronic breakdown, failure, malfunction or derangement of any instrument, machine, device, or temperature controlling equipment; … 13. wear and tear, fading, scratching or marring, gradual deterioration, developing flaws, normal up-keeping or making good; … Section 2 Loss of Income Cover We will cover You if the Business is interrupted or interfered with as a result of physical loss, destruction or damage occurring during the Period of Insurance to: 1. Property insured under any of the following sections of the Policy: a) Section 1 – Property; … for which a claim has been paid or liability admitted, or such claim would have been paid or liability admitted but for the application of an Excess. … Item 2. Additional increased cost of working the cost of further expenditure not otherwise payable under this section, necessarily and reasonably incurred during the Indemnity Period in consequence of the physical loss, destruction or damage, for the sole purpose of avoiding or minimising a reduction in Income (but not exceeding the reduction in Income thereby avoided) or resuming or maintaining the normal operation of the Business. Determination | Case number: 613189 Page 6 of 7 3.2 Summary of relevant reports Record Key points ET 24 - 09 - 2018  it undert ook a make safe to the property due to a tenancy losing power to some equipment  it inspected the main switchboard and found the tails to the main switch had burnt out  temporary power was organised for the three tenancies  it replaced the main switchboard and meter tails and updated the switchboard to meet current Australian Standards  due to the loss of main s power, this caused a surge and short within the main switch, which resulted in the burn out of both the mains supply into the switch, and metering tails out of the main switch . TN 13 - 11 - 2018  its fault crew responded to a fault call on 14 September 2018, who determined the main switch had burnt out  the crew advised the customer the sub - board was old, and it would need replacing at some stage in the future, however it required the main switch to be repaired before supply could be restored  TN received a cal l from another customer on the day from the same building and that fault was linked to the same burnt out main switch . C 19 - 11 - 2018  the main electrical isolation switch in the switchboard suffered a failure as a result of an electrical burnout, caused by an overloading of the mains supply cable and the switch  the mains side and cable to the electrical metering were found to be deteriorated due to overheating caused by the overload of the power circuits  the damage is not consistent with what would be excepted under a power surge and/or short circuit fault condition  it is clearly evident the insulation of the mains cable and cable tails to the supply authority meters has deteriorated over time due to excessive power overload caus ed by the tenancies draw ing power in excess of the power rating capacity of the mains cable and met er tails . ET 23 - 11 - 2018  a tenant on site noted on 7 Sept ember 2018, issues within the tenancy started with their three - phase equipment due to the car accident fault, including a ci rcuit to the three - phas e oven tripping and needing to be reset  ET attended the tenant’s site on 14 September 2018 due to power loss to some equipment  TN does not comment on whether the existing service fuses were to current standards  the current carrying c apacity of the existing consumer mains Determination | Case number: 613189 Page 7 of 7 Record Key points does not exceed the 100A existing main switch  the existing maximum demand per phase and currently installed consumer mains cabling comply with the relevant Australian Standard  the consumer mains cabling complies, is s ufficient for the load drawn, and as such the cause is not directly related to the existing installation of cabling but more contributed to other reasons outlined in its report . 3.3 AFCA approach to this complaint This complaint has been determined based on what is fair in all the circumstances, having regard to the relevant law, good industry practice, codes of practice and previous decisions of AFCA or its predecessor schemes (which are not binding). A full exchange of the relevant information has taken place between the respective parties. Each party has had the opportunity of addressing any issues raised. All of the provided material has been reviewed and considered. The parties have raised numerous issues in their submissions to AFCA. However, commentary in this determination is restricted only to those issues considered relevant to the outcome.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.