Home / Financial Firm (Unknown - Insurer) / Determination 546552
Determination 546552
Diesel fire pump engine failure claim declined as wear and tear
Summary
The company's diesel fire pump engine failed and the insurer declined the equipment breakdown claim. AFCA found the damage was worn piston rings and bearings, not sudden and accidental, and that recommended repairs were not shown to have been done, so the decline stood.
Breakdown must be sudden and accidental and excludes wear and tear, and the complainant failed to establish a covered sudden breakdown.
Issues
- Claim denial primary · not upheld“The loss was caused by wear and tear, which is excluded, and the complainant has not established a sudden and accidental breakdown.”
Subjects and remedies
no remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination | Case number: 546552 Page 1 of 11
Determination
Case number: 546552 3 June 2019
1 Determination overview
1.1 Complaint
The complainant holds a business equipment breakdown policy with the financial firm
(insurer). The complainant lodged a claim following the failure of diesel water pump
no. 2.
The insurer denied the claim on the basis the complainant failed to establish a valid
claim. Additionally, the insurer says the loss has occurred from wear and tear, which
is excluded under the terms of the policy.
The complaint disputes the insurer‟s decision to decline the claim.
The recommendation was in favour of the insurer. As the complainant does not
accept the recommendation, the complaint has been referred to me for determination.
1.2 Issues and key findings
Is the insurer entitled to decline the claim?
The available material establishes on the balance of probabilities the loss was not
sudden and accidental. The available material also establishes on the balance of
probabilities the loss was caused by wear and tear. In the circumstances, the
complainant has not established a valid claim. As wear and tear is excluded from
cover, the insurer is entitled to deny the claim.
1.3 Determination
This determination is in favour of the insurer.
The insurer is entitled to decline the complainant‟s claim and is not required to take
any further action in relation to the claim or the complaint.
Determination | Case number: 546552 Page 2 of 11
2 Reasons for determination
2.1 Is the insurer entitled to decline the claim?
I have decided this case on its merits, having regard to the relevant law, good industry
practice, codes of practice and previous decisions. I have considered all the material
submitted by the parties, both before and after the recommendation. I am satisfied the
documentation I have relied on has been provided to both parties.
While the parties have raised numerous issues in their submissions, for the purposes
of this determination, commentary has been restricted to those issues considered
directly relevant to the outcome only.
The complainant is represented by a director. Any reference in this determination to
the complainant includes a reference to its representative.
No new material provided after recommendation
After the recommendation was rejected, the complainant made further submissions in
which its position was essentially reiterated. No new material was provided by either
party.
Policy provides cover for equipment breakdown
The complainant must establish on the balance of probabilities it has suffered a loss
caused by an event to which the policy responds. This is known as a prima facie
claim.
The policy provides cover if during the period of insurance , a breakdown occurs to
equipment which is in use or connected ready for use at the insured premises.
The relevant policy terms are set out in supporting section 3.3 of this determination.
The onus is on the complainant to first establish on the balance of probabilities the
breakdown of the diesel pump was sudden and accidental. The complainant contends
the cause of the damage was a faulty thermostat.
It is only after this onus is met the insurer must show an exclusion (such as wear and
tear) applies to defeat the claim.
2015 service report notes engine breathing to excess
I have considered all relevant material provided by the parties including invoices,
service schedules, tests, maintenance reports, emails and other expert reports. A
summary of the material is set out in supporting section 3.4 of the determination.
Since about 1995, there were two identical diesel engine powered water pumps at the
insured premises.
Determination | Case number: 546552 Page 3 of 11
On 20 May 2015 an annual service of both engines was conducted by „SE‟. This
report identified pump no. 2 was breathing to excess .
Further documents by SE dated 10 June 2015 recommended an overhaul of both
pumps. The complainant says it maintains the engines and pumps and makes repairs
as necessary.
However, while the document is noted as an invoice, having considered the tenor of
the document, I am not satisfied the identified work was carried out. The document
identifies the work which needed to be done rather than work which was done. No
proof of payment was provided. Further, the expert engaged by the insurer (HG) says
in an email dated 9 October 2018 the documents provided by the complainant do not
show repairs were done to the engine to fix the breathing to excess problem.
The following year during the annual service on 17 August 2016, pump no. 2
overheated.
In October 2016 a maintenance report confirmed the cooling system was pressurised
and issues with the bottom end of engine were suspected. At the same time, DFP
provided a pump maintenance report indicating there was a piston/ring problem.
In later correspondence, DFP said the engine overheated quickly because of the
stuck thermostat.
DFP said the engine required reconditioning. The engine was stripped for rebuild. The
repairer found cylinder bores to be glazed and scored. While the repairer provided a
later email saying the engine presented in such a way indicating it had been hot at
some stage, the repairer‟s earlier invoice dated 8 November 2016 described the
cause of the damage as “excessive blowby.”
The engine was inspected by the insurer‟s automotive engineer. There is a dispute as
to when the inspection took place, but I accept the automotive engineer inspected and
photographed the partly stripped and partly repaired engine. The complainant
criticises the assessment because it took place after repairs commenced. However,
having read the report and considered the photographs, I accept the opinion has
weight even though the engine was partly stripped and partly repaired.
The automotive engineer noted the slight scoring on pistons and cylinders but could
not find evidence of overheating or detonation on the piston crowns. He concluded
the bearings were worn excessively because of regular cold starting and running. He
said the damage to the engine was consistent with wear and tear.
Damage not sudden and accidental
The insurer also arranged for a chartered loss adjuster/engineer (HG) to provide a
report. HG did not inspect the engine, but reviewed documentation and photographs
Determination | Case number: 546552 Page 4 of 11
taken by the automotive engineer and discussed the cause of the failure with the
repairer, the automotive engineer and DFP.
On reviewing the photographs, HG could see no sign of overheating or damaged
parts of the engine. HD also points out there is no mention of thermostat failure in any
of the early reports or invoices. HG agrees with the automotive engineer that
mechanical parts of an engine can get damaged by cold starts during periodic testing.
These pumps were periodically tested.
HD considered the repairs undertaken as well. He concluded it was most likely the
engine blew excessive smoke due to general wear and tear on its pistons and rings
and issues with its injectors rather than damage caused by overheating because of
lack of cooling water due to a faulty thermostat.
Having reviewed the available information, I am satisfied on the balance of
probabilities the complainant was aware of or should have been aware of issues with
the engine which were probably not rectified. While the engine overheated in August
2016, it was recommended repair work be done in June 2015. On balance, the
available information does not establish this recommended work was done.
Damage caused by wear and tear
Further, the repairer‟s invoice described the cause of damage as excessive blow by
and the May 2015 service showed the engine was breathing to excess. These are
signs of wear.
Taking all matters into account I am not satisfied there was sudden and accidental
damage to the pump number 2. This is because relevant issues with the pump were
identified over a year before the pump overheated.
Further, I am satisfied the available information establishes on the balance of
probabilities the damage to the engine was caused by wear and tear. Although DFP
indicated the engine overheated because of stuck thermostat, DFP‟s
contemporaneous pump maintenance report indicated there was a piston/ ring
problem. There is no mention of the stuck thermostat being the cause of damage in
any of the contemporaneous material. The repairer does not identify this as the cause
of damage in contemporaneous material. When the repairer later identified there was
signs of heat at some stage, this is contrary to contemporaneous material and the
email is not from the person who carried out the actual repairs.
An automotive engineer inspected the engine. He could not find evidence of
overheating. HD, a chartered loss adjuster and engineer inspected the photographs
taken by the automotive engineer and found no evidence of overheating or damage to
the engine.
Determination | Case number: 546552 Page 5 of 11
Having considered the available material, I am satisfied on the balance of probabilities
the engine was damaged because of worn out piston/rings. This cause of damage is
excluded from cover.
In the circumstances I am satisfied the insurer is entitled to deny the claim.
Determination | Case number: 546552 Page 6 of 11
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with F inancial O mbudsman S ervice (FOS) .
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
3.2 Our approach
It is an accepted principle of general insurance law that an insured bears the onus to
establish on the balance of probabilities that they have suffered a loss caused by an
event to which the policy responds. This is known as a prima facie claim. Once so
established, the onus shifts to the insurer to prove on the balance of probabilities that
an exclusion applies if it seeks to deny or limit its liability for the loss.
3.3 Relevant policy extracts
The relevant policy extracts are referred to in the correspondence between the parties
and in the insurer‟s Notice of Response dated 19 October 2018. Both the policy
document and the Notice have been exchanged with the applicant.
Definitions:
4. Breakdown
`Breakdown means sudden and accidental damage to an item of equipment or
part thereof which
manifests itself at the time of its occurrence by physical damage to an item of
equipment or part
thereof that necessitates its repair or replacement, but breakdown shall not mean:
a) depletion, deterioration, corrosion or erosion of material or the need to
clean any component;
Determination | Case number: 546552 Page 7 of 11
b) wear and tear;
c) leakage at any valve, fitting, shaft seal, gland packing, joint or
connection;
d) vibration or misalignment;
e) the failure of any structure, foundation or setting (other than bedplate)
supporting the Equipment or any part thereof;
f) the functioning of any safety device or protective device; or
g) the cracking of any part of a gas turbine exposed to the products of
combustion
3.4 Expert reports and other material about causation
Record Key points
Invoice
2 April 2014
Annual servicing to the two primary and secondary diesel fire pump
motors.
Fire pumps service
schedule
20 May 2015
Annual service.
The engine is breat hing to excess.
Invoice
10 June 2015
Overhaul of Pumps #1 & #2
Both pumps are leaking water & oil from the head gaskets, rocker
covers & side gaskets. We recommend that the heads are stripped
and removed for inspection. Refit heads, install new gas kets & seals
and test. This price is subject to inspection.
Overhaul of Pump #1 & #2 - Remove Heads, etc
Record of te st
17 August 2016
Number 2 pump set off - line – overheating.
Service cancelled due to overheating. Service report to follow.
Service cancelled – engine overheating – cooling system being
pressuris ed and suspect issue with bottom end of engine. Refer field
service report.
Invoice
10 October 2016
Annual service aborted due to the pump overheating (coolant system
pressuris ed which sugges ted an issue with the bottom end of the
engine).
Further investigation is required. Pump #2 isolated and taken off - line.
Sprinkler system still operational with pump #1 online.
Invoice DFP
20 October 2016
Initial call to investigate diesel engine faults.
24 October 2016 diesel engine removed and delivered to engine
reconditioner.
Pump #2 DFP
maintenance report
20 October 2016
Investigat e diesel engine breathing heavy from engine breather
piston/ring problem – engine requires reconditioning.
Determination | Case number: 546552 Page 8 of 11
Record Key points
Pump #2 DFP
maintenance report
24 October 2016
Strip and quote for repair.
Repair order parts
listing
25 October 2016
Lists required parts.
In shop repair order
8 November 2016
Strip engine for rebuild.
Inspected all parts for reuse. Found cylinder bores to be glaz ed and
scored.
Repairer invoice
8 November 2016
Strip engine for rebuild.
Inspected all parts for reuse.
Found cylinder bores to be glaz ed and scored.
Caus e “excessive blowby”
Insurer’s automotive
engineer (KD)
Report
06 December 2016
Inspected/photographed engine on 6 Dec 2016 at repairers.
E ngine was stripped and partly repaired .
Slight scoring on the piston skirts and worn main and big end
bearings.
Cylinder bores were slightly scored but already repaired.
Couldn‟t find evidence of o verheating/detonation on the piston crowns.
Bearings have most likely worn excessively due to regular cold starting
and running.
Damage to the pistons, bores and bearing is consistent with wear and
tear.
Insurer’s expert
adjuster (CL)
7 February 2017
The re are two pumps and engine assemblies with engine #2 removed
for repair.
Building firefighting services are provided by two identical diesel
engine powered water pumps designat ed pumps #1 and #2.
Number 2 pump is an assembled packaged unit from Ajax Pumps and
comprises a Cummins model dies el engine with the year of
manufacture 1995.
Pump #2 has accumulat ed run hour of 200 hours through regular
routine testing.
First began discussion 28 October 2016 with complainant‟s property
manager, repair company, and automotive engineer.
Requested service records for the 12 mont hs before the loss,
photographs, and repair cost.
Damaged engine #2 had been removed from the pump frame and
forwarded to repairer for strip, check and overhaul.
Told engine had lost coolant water from a damaged coolant hose
which caused overheating to the engine causing damage.
26 March 2015 head gasket, rocker cover and side covers leaking.
Coolant black and contaminated. No evidence of any repair to redress
the se issues.
Determination | Case number: 546552 Page 9 of 11
Record Key points
17 August 2016 engine reported to be smoking badly.
CL engaged the services of an independent automotive engineer
(KD).
6 December 2016 KD inspected the engine at repairers.
Based on advice from KD, CL concluded damage to the engine was
beca use of wear and tear.
Repair costs were high. A more cost - effective repair option would have
been to install a new engine.
Email from DFP to HG
1 May 2017
Initial fault with the engine was excessive fuming from the engine
crank case breather which quickly filled the pump room with smoke
after a short run which indic ated an issue with the piston/ ring area.
Engine overheat ed quickly which was later traced to a stuck
thermostat.
Engine oil badly burnt indicating it had been very hot giving a high
probability of a piston to bore seizure necessitating an engine
replacement or rebuild.
Letter from safety
contractor (SE) to
broker
21 August 2017
Sprinkler system and associated pumps are tested weekly which
includes the cold starting of the engines.
R un for a minimum of 15 minutes per test.
17 August 2016 the annual service for pump #2 was cancelled
because it was overheating
Diesel mechanic (DF) attended to investigate pump #2 and when it
started within minutes the pump house shed filled with exhaust fumes.
Using a thermometer, DF explained the cooling system had not
engaged and let the coolant through to the engine.
Thermostat failed to open.
24 October 2016, engine removed and delivered to repairer for
rebuilding.
8 November 2016 engine returned an d reinstalled on site.
Email from repairer to
broker
14 September 2017
Broker requesting repairer provide a report about the cause of
damage.
Repairer no longer works for the company but as far as the writer
could remember the engine was presented with a high blow by the
bores had signs of scuff marks from signes of then had been hot at
some stage (sic).
Insurer’s expert (HG)
Report
20 Septem ber 2017
After engagement spoke with broker, complainant, building
maintenance company, DF, repairer and KD.
After enquiries, some requested material provided by the broker and
service dockets and tax invoices relating to the general maintenance
of the tw o water pumps in the past few years were provided.
Two diesel engine operated water pumps installed during construction
of the building in 1995.
Complainant had ongoing contract for maintenanc e which included
weekly inspections of firefighting services, and annual ins pection of
Determination | Case number: 546552 Page 10 of 11
Record Key points
the water pumps.
Found no mention on tax invoice 10 June 2015 of any repairs carried
out to the diesel engines of the wat er pumps.
No report or tax invoice in relation to repairs carried out on the diesel
engines bet ween 10 June 20 15 and 17 August 2016 (when #2 engine
blowing smoke).
Reviewed KD‟s report and discussed with KD who said repairer could
not show any evidence of heat damage on engine and engine was
most likely blowing smoke due to worn out rings.
Reviewed photographs at tached to KD‟s report. Could see no sign of
overheating or damaged parts of the engine.
Repairer said they did not investigate the cause of the engine failure
but when asked said usually problem of excessive smoke from an
engine is related to wear and tear on piston/rings and they had no
evidence of heat damage which was contrary to a later email.
DF adamant engine was damaged by overheating when cooling wat er
supply was cut off due to a fault in the thermostat. No mention of
thermostat failure in any of th e previous reports.
During annual service on 20 May 2015, the engine was found
“breathing to excess”.
Water pump rebuilt in June 2015, but no evidence has been provided
of any repairs to its diesel engine at that time.
No documentation provided for any reb uilt or major repairs on the
engine since its installation in 1995.
Even though the water pump has recorded very low hours, the
mechanic al parts of the engine can get damaged by cold start during
periodic tests.
No evidence provided to show heat damage to any part(s ) of the
engine.
Replacement/servic e of injectors, injector pump and turbo assembly
during repairs to the engine suggests their incorrect operation/general
condition may have been the cause of the excessive smoke blown by
the engine.
From the inf ormation received and our enquiries with various service
providers, it appears that the engine was most likely blowing excessive
smoke due to general wear and tear on its piston/rings and issues with
its injectors etc, rather than any damage suffered due t o overheating
caused by lack of cooling water due to a faulty thermostat during
testing of the water pump on 17 August 2016.
No evidence available that the diesel engine of water pump #2
suffered any sudden and unforeseen physical damage on 17 August
2016 .
Insurer’s expert (HG)
Email
9 October 2018
Reviewed maintenance history provided by complainant and could find
no reported repairs done to the engine of #pump 2 to fix the breathing
to excess problem.
Weekly test reports showed no details of test carried out to diesel
engines.
Determination | Case number: 546552 Page 11 of 11
Record Key points
No mention in the October reports issued by DFP about damages to
the engine by thermostat failure.
3.5 Other relevant material considered and relied on
Certificate of insurance.
Policy document.
Parties‟ submissions and emails.
Correspondence between the parties.
Insurer‟s claim file notes.
Expert r eports and all attachments including invoices and photographs.