Text of the determination
Determination | Case number: 539673 Page 1 of 13
Determination
Case number: 539673 13 December 2018
1 Determination overview
1.1 Complaint
The complainant lodged a home building claim in regard to cracking and movement
damage. The financial firm (insurer) declined the claim based on its view the
complainant did not establish a valid escape of liquid claim, but rather inadequate
underpinnings and not leaks caused the damage. The insurer also says a policy
exclusion for ground movement defeats the claim.
1.2 Issues and key findings
What is the extent of the insurer’s obligations to the complainant under the
terms of the policy?
The panel is satisfied that the complainant has established a valid claim under the
policy.
However, the panel is also satisfied that the insurer has established that part of the
damage was caused by circumstances not covered by or excluded from coverage
under the policy.
The insurer is to meet 50% of the complainant’s claim for da mage.
1.3 Determination
This determination is partially in favour of the complainant.
The insurer is required to accept part of the claim in line with its policy terms and
conditions. As set out in section 2.1, the insurer is required to pay the complainant:
50% of the repair quotes, with statutory interest, within seven days of the
complainant accepting this determination
costs of soil testing, within seven days of the complainant providing an invoice to
the insurer.
Determination | Case number: 539673 Page 2 of 13
2 Reasons for determination
2.1 Is the insurer entitled to decline the claim?
The complainant bears the onus to establish a valid initial claim
General insurance policies provide cover with conditions and exclusions. The policy
wording and certificate of insurance outline the cover provided by the insurer and any
applicable exclusions.
When lodging a claim with an insurer, the insured must establish a valid claim. That
is, on the balance of probabilities, an event covered by the policy must have caused
the loss.
Once a valid claim is established, the insurer must show, on the balance of
probabilities, it is entitled to rely on a policy exclusion or otherwise is not required to
cover the loss.
The parties dispute the policy responds to the damage
In this complaint, the complainant holds home building cover for damage caused by
insured events, including the escape of liquid. The complainant lodged an escape of
liquid claim for structural and wall cracking damage. The insurer declined the claim
based on its views:
the complainant did not establish a valid claim, because inadequate underpinning
works (not a leak) caused the damage
even if an insured event was established an exclusion (earth movement) would
defeat the claim.
The complainant disagrees with the decision and argues a broken and leaking
stormwater pipe and drain caused the damage. She wants the insurer to pay the
claim based on repair quotes for $10,285 (tiling) and $154,000 (slab, masonry, walls
and windows).
As the parties dispute the cause of damage, the proximate cause must be
considered.
The proximate cause is the dominant or operative cause
Damage can have more than one cause. When deciding whether the policy covers
the damage, the proximate cause of the damage must be identified.
This is a question of fact depending on the circumstances in each complaint. The
proximate cause is not necessarily the first or last or the sole cause of the loss. It is
the effective, dominant or operative cause of the loss. If there are several causes
operating at the same time, AFCA considers each one to determine which cause set
the train of events in motion.
Determination | Case number: 539673 Page 3 of 13
Courts have said that if one cause would have resulted in the harm in any case and
the other would not have done so in the absence of the first, then the first is the
proximate cause.
The property experienced leaks under the ground
The panel has closely reviewed the parties’ materials, which confirm:
Date Action
2011 Underpinning works (south, west, east sides) occurred after the
complainant’s building experienced cracking/movement damage.
18 - 05 - 2016 The complainant contacted the engineer who designed the underpinning
works (DP), aft er she noticed building cracking.
04 - 06 - 2016 DP inspected the underpins and said he found the material underneath very
wet and soft. He estimated a leak had co mmenced aft er 2012 and had been
occurring over a period of years. He suggested the complainant lodge an
insurance claim for a leak.
25 - 11 - 2016 The complainant lodged a claim with the insurer.
21 - 12 - 2016 The insurer’s builder (OP) provided a report confi rming several stormwater
drain/pipe leaks (west side), including a large void/sinkhole (south west side)
caused by water discharging into soil instead of pipe connection.
25 - 01 - 2017 The insurer’s engineer (HC) inspected the property and recommended further
investigation into the effect of the leaks, and into the underpinnings.
10 - 04 - 2017 The insurer’s engineer (HC) again provided a report based on his second
inspection of the property and plumbing test results. He concluded the
underpinnings were of inadequate depth and the leak(s) did not cause
damage.
18 - 04 - 2017 The insurer declined the claim.
14 - 07 - 2017 The complainant completed the boundary trap repairs.
06 - 02 - 2018 The complainant arranged for soil testing.
The relevant reports, tests and photographs, which are contained in section 3.3,
support leaking occurred from the stormwater drain/pipe into the ground under the
property.
The insurer agrees leaks occurred but states the complainant did not establish a valid
claim because HC confirmed inadequate underpinnings, not the leaks, caused the
damage.
Determination | Case number: 539673 Page 4 of 13
The proximate cause of the damage
HC concluded that the leak(s) into the void/sinkhole had little impact upon the
ground’s moisture content, because it was near the footpath and a council boundary
trap.
The panel notes from the photographs and the property survey that the footpath and
therefore the void/sinkhole, appear to be relatively close to the building.
DP advised that at the time of the 2011 underpinning works, the base material was
found to be firm and hard, but since then the base material has become soft and wet.
The complainant’s soil testing details the findings in relation to the moisture content at
the complainant’s property.
Having reviewed all of the exchanged material, the panel is satisfied that the
complainant has established that the property has been impacted by the leaks and
this has contributed to the damage at the property.
However, the panel notes that underpinning works were carried out at the property in
2011, as a result of the complainant having noted cracking prior to the underpinning.
The panel is satisfied that the earlier cracking at the property and the need for the
2011 underpinning establishes that the property was already sinking prior to 2011.
The panel also notes that there is no evidence to establish the length of time that the
ground in the area has been saturated as a result of the leaks.
HC has detailed that in his view, the underpinning is not deep enough and is also not
consistent around the home.
The panel is satisfied that HC has provided a thorough and logical explanation of the
type of underpinning which would have been required to prevent further sinking and
that the underpinning which was provided, is insufficient.
The result is that the panel is satisfied that the insurer has established that the
underpinning carried out in 2011 has contributed to the circumstances of the
complainant’s loss. That is, the 2011 underpinning is also a proximate cause of the
current damage.
Whilst it is not possible to detail the precise contribution of the leaks and the
underpinning to the damage, the panel is of the view that it is fair that the cause of the
damage be apportioned 50-50 between the leaks and the underpinning.
Accordingly, the insurer is required to accept 5 0% of the complainant’s claim in line
with the terms and conditions of the policy.
Determination | Case number: 539673 Page 5 of 13
The insurer is required to pay the complainant 50% of the repair quotes, within seven
days from the date the complainant accepts this determination.
Statutory interest applies in line with section 57 of the Insurance Contracts Act 1984
(the Act), from the date of the quotes until the date the payment occurs.
The insurer is also required to reimburse the complainant the costs of the soil testing,
within seven days of the complainant providing the invoice/receipt to the insurer.
Determination | Case number: 539673 Page 6 of 13
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with F inancial O mbudsman S ervice (FOS) .
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
claim claim
This determination has been made by a panel consisting of the panel chair
ombudsman, a representative with extensive experience in the insurance industry and
a representative with extensive experience in consumer claims.
3.2 Policy
What you are covered for - Insured Events
We cover the building for loss or damage at the insured address caused by an
insured event during the period of insurance. There are some things we do not
cover and these are shown in the ‘We do not cover’ section of the following tables
on pages 16 to 25 and in the ‘What we do not cover - general exclusions’ o n
pages 35 to 40.
Escape of liquid
We cover – Loss or damage to the building caused by liquid leaking, overflowing
or bursting from any of the following: any drain, fixed pipes, roof gutters or
guttering and rainwater downpipes, drainage and sewage systems;
We do not cover – wear and tear, or loss or damage by the escape of liquid
occurring as a result of a gradual process of leaking, splashing, dripping or
overflowing over a period of time when you could reasonably be expected to be
aware of this conditio n …
Determination | Case number: 539673 Page 7 of 13
What we do not cover - general exclusions
You are not covered under any section of your policy for damage, loss, cost or
legal liability that is caused by, arises from or involves:
Ground movement – erosion, vibration, subsidence, landslip, landslide, mudslide,
collapse, shrinkage or any other earth movement …
3.3 Reports
Record Key points
Insurer’s expert (OP)
Leak report
Licensed commercial
builder
Licensed domestic builder
21 - 12 - 2016
We attended the site to pressure test all water lines and report on
the cause of damage to the property.
The Insured has advised that underpinning of the foundation was
undertaken recently.
We noted cracking of the external and internal brick walls of the
property.
Cold water line pressure test; Hot water line pressure tes t; CCTV
inspection of the sewer system: tested; Passed:
Was the cause of the leak found? Yes … CCTV inspection of the
storm water system: tested; Failed
Description of the cause of the leak:
All pressure testing to water supply pipework has passed.
[We] … reattend[ed] and conduct[ed] CCTV inspection of the
storm and sewer systems to determine if these pipes may be
causing any resultant damage. We inspected the sewer drains
from the kitchen sink and toilet and there were no breaks or
cracks.
While visually i nspecting the storm water system we discovered
there are cracks and holes in the top of the PVC surface drainage
system for approximately 10m from the second down pipe
towards the street.
Excess water is able to exit the pipe at these surface areas.
There is subsidence and a pothole in the asphalt footpath at the
front of the property.
CCTV inspection of the storm water drain has indicated cracks
and holes at the surface as mentioned above; however the
bottom of the storm water pipe does not appear to be d amaged.
The pipe was flowing freely to a point where a failure of the joint
between the PVC and a small section of vitrified clay pipe under
the asphalt was identified.
Water discharges the pipe at this t - piece joint failure which may
cause water ingress and deterioration to the integrity of the
surrounding asphalt area.
The asphalt footpath will need to be excavated and the
damaged/faulty sections of storm water pipework will need to be
replaced.
There is a surface grate underneath an external cold water tap
Determination | Case number: 539673 Page 8 of 13
Record Key points
which has been cut over the waste pipe from the kitchen sink.
This is an illegal connection.
Insurer’s expert (HC)
Licensed, chartered
professional engineer
Report
28 - 01 - 2016
Cracking and movement became evident in the house around
2010 and underpinning was carried out of the west, south and
east walls around 2011.
It was indicat ed that 7 underpins were constructed along the west
side, 4 underpins along the sout h side with only 3 underpins
along the east side.
Following the underpinning work renovations and redecorating
were carried out to the interior of the house to repair the cracking.
Following the underpinning, cracking continued to occur along the
west wall over the years and this cracking has been getting
wors e. The owner contacted the original engineer and
underpinning cont ractor to inspect the new cracking and
movement and a test hole was excavated midway along the west
side by the underpinning contractor. It was indicated that
excessive dampness was evident in the ground when the bore
hole was excavated.
Prior to Christmas a plumbing check was carried out of the
property and several problems were found with the stormwater
drains along the west side. During this time a small hole
developed in the footpath area and recently the Council d ug up
the footpath in this area and found a large void underneath the
footpath. It was also found that the stormwater pipe where it met
the Council pipe underneath the footpath area had dislodged and
water was escaping from this area.
Our office carried ou t a site inspection of the above property on
25 January 2017 … Evidence of the previous underpinning was
observed as cut outs have been provided in the original concrete
paving. A stormwater pipe extended along the west side of the
property to the front.
An inspection of the external west wall showed that considerable
amount of cracking and movement was evident of the brickwork
particularly around the middle bedroom and lounge room areas.
This cracking showed weat hered edges which would indicated
that the cracking has been occurring for a very long period of
time.
An inspection of the front brickwork to the south wall showed that
cracking and movement was evident particularly around the
windows to the front two bedrooms.
An inspection of the interior of the house showed that
considerable amount of cracking and movement was evidenc e
particularly to the middle bedroom and lounge room along the
west side. Generally excessive movement was occurring in the
west wall in thes e areas.
An inspection of the dining roo m which is located on the east side
showed that cracking and movement was also evident particularly
where the lounge room meets the dining room area.
Determination | Case number: 539673 Page 9 of 13
Record Key points
An inspection of passageway and two bedrooms along the east
side showed that minor cracking was evident to these areas.
An inspection of the kitchen area showed that cracking was
evident of the walls particularly at the south end.
An inspection of the back porch showed that cracking and
movement was evident with gaps at the plaster ceiling to the brick
wall on the south side. The double doors to the backyard were
out of alignment.
An inspection of the bathroom area showed that mino r cracking
was evident around the south - west corner.
The cracking and movement of the house is typical of problems
that occur due to differential settlement of the footings. Differential
settlement can occur of the footings due to seasonal changes in
the m oisture content of the foundation material.
It would also appear that voids are occurring underneath the
footpath area and maybe extending into the property. The full
extent of thes e voids is not known.
Normally underpinning extends down to a dept h below the
existing footings and in our opinion the depth of the underpins
should be deeper than any of the service pipes including
stormwat er and sewer pipes to the property.
Therefore, even although voids are occurring particularly to the
front section of the p ath along the west side, it would appear that
the voids do not extend down below the level of the underpins.
Therefore, in our opinion, even although voids are occurring
around the front sout h - west corner of the house, in our opinion
the underpinning works carried out should be at a depth greater
than these voids.
We would recommend that further investigation work would need
to be carried out to determine the extent of the voids extending
into the property and whether the underpinning has been carried
out i n accordance with the original design.
Soil testing may also need to be carried out to confirm the depths
of the underpin as well as to confirm in the original underpins
were carried down far enough originally.
HC
Licensed, chartered
profe ssional engineer
Report
10 - 04 - 2017
a second site inspection was carried out of the above property as
well as a plumbing check to determine the reason for cracking
and movement to be occurring to the brickwork to the house
cracking and movement evident particularly the western side of
the house is typical of problems that occur due to inadequate
underpinning of the wall
The recent plumbing check has found that problems are occurring
with both the sewer and stormwater pipes along the west of the
house. The stormwater pipe is a PVC pipe and has been
constructed close to the surface. Due to the pipe being close to
the surface several holes are occurring in the top of the pipe. No
blockages were found in the pipe except for a section of pipe has
Determination | Case number: 539673 Page 10 of 13
Record Key points
been squashed near the footpat h area. This section of pipe was
still allowing water to flow through, however the camera could not
extend through this section of the pipe. Therefore, the stormwater
pipe is not blocked and only has a restriction near the foot path
area due to the squashed section of pipe.
photographs they show the pipe was broken and water was
discharging directly into the void near the footpath area.
Therefore even although the stormwater pipe was broken the
water was discharging into the void near the boundary trap and
w ould not have been resulting in water extending particularly up
to the lounge room area.
A major problem is occurring with the sewer pipes to the property
with the sewer pipes not being connected to the boundary trap
near the front of the house … connectio n to the boundary trap
had failed. It would appear that the sewer is flowing directly into
the void around the boundary trap and not into the sewer pipe.
The [council] sewer is located out in the street and a boundary
trap is provided to connect the house sewer pipes to the [council]
sewer. The sewer pipes to the house are relatively shallow,
however the sewer out in the street is a deep sewer. Therefore, a
vertical drop occurs at the boundary trap bet ween the house
sewer pipes and the [council] sewer out i n the street. The
construction of the boundary trap requires a deep shaft to be
excavated and a vertical section of pipe layed. The area is then
backfilled. Depending on the degree of compaction of the backfill
lower term settlement can occur around the bo undary trap.
Movement can also occur in the vertical section of pipe which can
also result in breaks occurring in the pipe. Therefore it is possible
that material can be washed into the boundary trap vertical
section of pipe and into the sewer creating a v oid around the
outside of the boundary trap.
It would appear in this case that a problem is occurring with the
vertical section of boundary trap which is resulting in both the
sewer and stormwater discharging into the void … recently the
stormwat er pipe co nnection was refitted to the foot path area and
the stormwater is not discharging into the void now. From our
recent plumbing check the void is only occurring around the
boundary trap area whic h is in the front of the property near the
footpath area. This v oid does not extent back up to the rear
lounge room area.
Therefore, in our opinion, the cracking and movement in the
house has resulted due to inadequate underpinning of the house
around 2011 and even or though problems are occurring with
both the sewer sand stormwater pipes these problems would not
be contributing to the movement.
Considerable movement is occurring in the west wall and in
particularly the area around the lounge room area.
It is possible that soil testing could be carried out to determine the
depth of the underpinning as well as the type of existing trip
Determination | Case number: 539673 Page 11 of 13
Record Key points
footing … Therefore, the full extent of the voids around the
boundary trap and where the water is going to cannot be
determined until the area is opened up … The recent video check
of the pipe could not extend into the boundary trap and the top of
the boundary trap is blocked with debris.
… underpinning drawings specify the depth of the underpins to be
1m below the existing footing level … this depth is inadequate as
normal underpinning now specifies the depth to be at least 1.8m
to 2m deep … the underpinning design was carried out by the
design engineer and is not based on any soil testing. If soil testing
had been carried out then the moisture content of the foundation
material would have been specified as well as the depth of the
underpinning. The exact type of existing strip footing underneath
the brick walls is not specified on the design documents, however
due to the age of the house it would appear that the footings to
the house would be either a bluestone footing or rubble footing. In
our opinion continuous underpinning is required of this type of
footing and not hit and miss underpinning as specified on the
drawings. Very little information is available regarding the
underpinning and it is not clear if any further problems were found
with any service pipes including the stormwater and sewer pipes
extending along the west side of the house.
HC
Further comment
05 - 09 - 2017
Major breakage occurred in the pipes near the connection of the
property sewer to the [council] Sewer
The sewer from this property was flowing out of the property
sewer and around and into the [council] connection.
The plumbing reports indicated that the pipes to this property
were repaired as well as the pipes to the [council] sewer.
Therefore problems occurred with both pipes and the excess
sewerage would have been flowing into the [council] Sewer
through the [council] breaks. [CM note – doesn’t follow – as void
at boundary trap is ON app’s property and adjacent to we stern
wall] All of the plumbing checks showed no blockages or
problems with the sewer pipes within this property until around
the connection to the [council] sewer.
The only void found was at the connection of the property sewer
to the [council] sewer and not further into the property.
Even although the pipes were broken the broken pipes have not
resulted in water extending along the west wall to the lounge
room area or any voids further along the west wall.
Complainant’s expert
(DM)
Plumber
Email to the Complainant
13 - 11 - 2017
As discussed on the phone, please see the below information
about the job we complete on behalf of [the water supplier].
29/8/17 – Completed a CCTV inspection of the House
Connection Branch.
14/11/ 17 Attended site but had to re book for the 6/ 10.
6/10/17 – Completed a reline of the House Connection Branch.
Job complete.
Determination | Case number: 539673 Page 12 of 13
Record Key points
The repair works that we complete are only on [the water
supplier’s] sewer drains. We have completed a reline of the
Hous e Connection Branch.
Complainant’s expert
(DP)
… engineer
Email to the complainant
reporting on works and
reattendance
17 - 05 - 2018
I do have the following factual information for you to consider.
The underpin works on your property were carried out in 2011 -
2012.
The works were carried out with t he required Building Permit and
all the required inspections took place.
As part of this process an independent inspector inspected the
works and found the base material to be firm and hard.
As a result approval was given to your contractor to pour the
c oncrete. This is a standard requirement.
If the base material was found to be soft then approval to pour the
concrete would not have been provided to the contractor by the
independent inspector.
In June 2016 investigation works were carried out and a hole was
excavated to the bas e of one the underpins.
During these works your contractor, you, your husband and I
were present.
The material that was encountered at the base of the underpin
was very wet and soft.
This confirmed that over the period of 4 - 5 years the base
material went from being firm and hard to being soft and wet.
You saw the soft material that was excavated and the advice was
provided to you in relation to the defective stormwater system.
Your stormwater system is located on the surface.
This escape of water over a period of several years affected the
performance of the footings.
The base material had gone from firm and hard to wet and soft.
This process was taking place from 2012 to June 2016 which is
several years in the making. Movement of the footings is to be
expected given that there was considerable abnormal moisture
contents changes taking place through these years.
3.4 Other records
Record Key points
The complainant
Email to the insurer
27 - 04 - 2017
Thank you so much for taking the time to call me and giving
me the chanc e to advise you that HC had advised myself
and (my husband), on two separate occasions, that he will
be organising for the side of the house to be dug up /
opened up and have [the water supplier] on standby when
this was to take place
So he could actual see for hims elf, just how deep and how
Determination | Case number: 539673 Page 13 of 13
Record Key points
far into the property the sink hole is / goes. HC explained
that he believes the sewage loss is going directly into this
sink h ole.
DP
… engineer
Email to the complainant
21 - 05 - 2018
… As previously advised I am not responsible for your
property and I do not accept any responsibility due to the
defective stormwater system that affected the work
performed and the movement of your p roperty.