Home / Search / Determination 538265
Determination 538265
claim_denial
Summary
A member claimed for storm damage to a business building after roof trusses and walls failed. AFCA decided the mutual society was entitled to deny the claim because the evidence did not show a protected storm event caused the damage rather than long-term deterioration.
Cover applies only to damage caused by a protected event, and the wear, tear and gradual deterioration exclusion applies where the evidence points to gradual deterioration.
Issues
- Claim denial primary · not upheld“The financial firm can deny the claim because the evidence does not show the damage to the complainant's property was caused by a storm.”
Subjects and remedies
home or building damageno remedy
Related
Text of the determination
Determination | Case number: 538265 Page 1 of 8
Determination
Case number: 538265 4 April 2019
Determination overview
1.1 Complaint
The complainant is a member of the financial firm, which is a discretionary mutual
society. Membership of the financial firm confers on its members the right to claim for
the benefit of certain „protections‟.
The complainant lodged a claim for damage to his building. The damage comprised of
the failure of roof trusses and other structural damage. The complainant says this was
caused by a significant storm event with high winds on 19 December 2017.
The financial firm, relying on expert reports, said the damage did not arise from a
„protected event‟. Instead, the financial firm says the damage arose from exclusions in
its protection cover. Namely, the damage to the building was due to long term gradual
deterioration. On this basis, the financial firm exercised its discretion to deny the
complainant‟s claim.
The complainant disputes this and maintains the damage was caused by the storm.
1.2 Issues and key findings
Can the financial firm deny the claim?
The financial firm can deny the claim because the evidence does not show the
damage to the complainant‟s property was caused by a storm.
1.3 Determination
The determination is in favour of the financial firm.
The financial firm was entitled to deny the complainant‟s claim. The financial firm is
not required to take any further action.
Determination | Case number: 538265 Page 2 of 8
Reasons for determination
2.1 Can the financial firm deny the claim?
Policy provides cover for protected events subject to exclusions
The rights of members are set out in the Product Disclosure Statement (PDS) dated 1
December 2015. The operation of the scheme is also governed by the financial firm‟s
constitution and rules.
There is no dispute the complainant is a member and is entitled to the protection
cover issued by the financial firm. The PDS says the financial firm will consider claims
for damage to the building caused by a „protected event‟ during the „period of
protection‟.
A „protected event‟ includes ten „perils‟. Relevant to this is „storm, wind, rain or snow‟.
The PDS also says the financial firm will not pay for damage caused directly or
indirectly by wear, tear or gradual deterioration.
There is no dispute the financial firm exercised its discretion to deny the
complainant‟ s claim on either of the following bases:
the damage was not caused by a „protected event‟
the cause of damage falls within the exclusion for wear, tear or gradual
deterioration
Information does not show the storm damaged the property
Both parties have provided a report from engineers. IM was engaged by the insurer
and T by the complainant.
Neither of these experts concluded that the damage was caused by the storm. In the
first report, IM concluded the damage was caused by footing movement of the
eastern wall.
T disagreed. T said the damage was due to the failure of the roof trusses. This was
caused by the failure of the masonite connection plates at the bottom chord join in the
centre of the trusses. Given the age of the building, he said „the failure of t he
masonite plates is possibly due to long term fatigue from cyclic wind loading ‟.
As evident, neither engineer says the cause of damage was the storm. Further, if I
accept T‟s opinion, the damage is consistent with wear, tear or gradual deterioration.
The complainant has provided other opinions in support. These are from R, C, K and
W. These experts disagreed with IM‟s opinion that there was footing movement. This
is consistent with T‟s evidence that footing movement was not a cause. However, only
Determination | Case number: 538265 Page 3 of 8
R and K were prepared to say the wind caused the damage. The other two provided
no opinion as to the possible cause.
In his conclusion, K simply said „the only other factor would be wind‟. K did not appear
to take into consideration T‟s opinion of the masonite plates failing. Therefore, K‟s
opinion is not persuasive.
R (a builder) does say that in his opinion, the plates looked to have been broken by
sheer force. However, this is inconsistent with T‟s evidence who provided no such
conclusion. It is also inconsistent with the fact:
the highest recorded wind speeds from the nearest weather station was about
70km/hr – this would not be enough to cause such structural damage
there is no evidence of such significant damage in the neighbourhood that day
Therefore, I am n ot persuaded by R‟s opinion.
Given all this, I am not satisfied the available information shows the storm damaged
the property.
Financial firm entitled to deny the claim
The financial firm exercised its discretion to deny the claim on the basis the evidence
did not show the storm cause the damage.
I am satisfied the financial firm‟s conclusion was reasonably open to it based on the
available information. Therefore, I accept the financial firm is entitled to deny the
complainant‟s claim.
Determination | Case number: 538265 Page 4 of 8
Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with F inancial O mbudsman S ervice (FOS) .
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
3.2 Reports
Re port Key points
financial firm’s expert ( AN )
Report
1 February 2018
We have conducted a review of the Daily Weather Observations
that were rec orded in Mount Gambier on 19 December 2017 and
note that a north westerly wind was recorded at 2:12pm with a
speed of 70km/h. That was the second highest wind speed
recorded in Mount Gambier during that month.
The Beaufort Wind Scale describes wind speed betwee n 63km/h
and 75km/h as „gale force‟ winds with a physical description on
land including the breaking of twigs on trees and walking progress
generally impeded. The scale does not include the likelihood of
any structural damage within that range.
The recorde d wind speed on the date of loss does not appear to
have been sufficient to have caused the extent of damage on its
own however it is possible that stronger wind gusts may have
occurred near your Member‟s premises. We have no means of
being able verify thi s occurring.
financial firm’s expert ( IM )
Report
9 March 2018
Before the roofing was replaced, the roof was clad with c orrugated
iron sheeting that was prone to leakage during rain events
because of corrosion.
There was staining from previous and prolonged moisture ingress
to the roof purlins and trusses throughout the warehouse
(including to the Mas onite connection plates)
Our review of records from the same weather station indicate the
wind speed recorded on 19 December 2017 has been equalled or
exceeded eleven times in the preceding twelve months, reportedly
Determination | Case number: 538265 Page 5 of 8
Re port Key points
without causing damage to the building. This indicates the building
has been subjected to numerous similar wind gusts throughout its
life without suffering damage.
Our review of aerial site i mages from Nearmap.com suggests the
roof sheeting was replaced between 16 October 2017 and 18
January 2018.
[…]
The member advised us the roofing was replaced approximately
five years ago.
We also found evidence which, in our opinion, indicates the
damage is not entirely recent (although it is possible the damage
recently worsened, refer further discussion below).
The bottom chord splice connection included two skew nails that
protruded from the face of one member into the adjoining member.
These nails were corroded [8], with the corrosion being particularly
more severe at the more severe failures. This indicates the nails
have been ex posed to the atmosphere for some time, which
means the splice began to separate some time ago.
The ceiling grid has separated along its junction with the eastern
wall. Based on the accumulation of contaminants between the
separated members (such as dust and cob webs) [9], this
separation has not occurred recently.
On the two southern trusses, where the failure has not been as
se vere, the Masonite splice plate has rupt ured, but the secondary
plate along the chord‟s top face has not (nor has it been pulled out
from the bottom chord or otherwise disturbed) [10]. This may
indicate that this secondary member was retrofitted to the tru sses
after the splices had begun to fail in an attempt to strengthen
them. If the Masonit e‟s failure had occurred recently, we would
expect to observe a failure of this secondary member as well.
financial firm’s expert (IM)
Report
3 July 2018
[…] the most recent failure of the roof trusses had occurred after
previous instances of failure (such as the rupture of the original
M asonite splice plat es).
considerable moisture staining to the roof framing (including
purlins, the truss members themselves a nd the original Masonite
splice plates), which indicates the roof trusses have been
deteriorating from exposure to le ak age in the roof for some time,
and
the tapered gap between the new boundary fence and the eastern
wall, which extends perpendicular to th e eastern wall near the
boundary with S s treet (refer to photo 7 in our p revious r eport ).
The tapered gap indicat es the fence was probably constructed
whilst the wall was already in a rotated position, otherwise the
fence would have been constructed flush against the eastern wall.
( o ur review of aerial site images confirms this fence was
constructed before, at least, October 2017 and, therefore, before
the day the damage to the wall is alleged to have occurred).
Therefore, even if footing movement was not t he caus e of damage
in this instance (which we maintain our opinion that it is), in our
Determination | Case number: 538265 Page 6 of 8
Re port Key points
opinion, there is clear evidence that:
• the damage predates the day the damage is alleged to have
occurred, and
• the structure was in a deteriorated condition and had undergone
structural failures prior to the day the damage is alleged to have
occurred.
financial firm’s expert (IM)
Report
11 July 2018
The R r eport alleges there was no evidence of “moisture or wear
and tear” to the central bottom chord splices. We respectfully
disagree with this finding. As outlined in our original report, we
observed evidence of long - term roof sourced moisture ingress
througho ut the building (including, but not limited to, staining to the
suspended ceiling tiles, timber purlins and truss members, and the
m asonite splice plat es ).
financial firm’s expert (IM)
Report
17 September 2018
The evidence outlined in our p revious r eports shows the damage
was not caused by a single fort uitous wind or storm event, or other
insurable peril.
Moreover, T ‟ s assertion that the damage was caused by material
fatigue from cyclic wind loading is consistent with our assessment
that the damage was not caused by a single wind or storm event.
Material fatigue occurs from the cumulative effects of tens of
thousands (if not hundreds of thous ands or more) of loading cycles
(i.e. innumerable wind gusts), which gradually weaken material
over time. Material fa tigue does not occur from a single excessive
or fortuitous event. Consequently, our understanding is that T also
believe the damage was not caused by a single wind or storm
event.
financial firm’s expert (AN)
Report
18 September 2018
The aforementioned part of the T report highlighted in bold text
above, suggests that the failure of the masonite plates is possibly
due to long term fatigue from cyclic wind loading. The T report is
unable to 'pinpoint a specific cause for the failure' such as a
defined eve nt or covered peril.
Both reports tend to concur that the ultimat e cause of the failure to
your Member's roof is by long term gradual deterioration rather
than it being caused by a single and identifiable peril or event as
has been alleged by your Member.
On that basis, whilst the difference in opinion as to the cause of
the walls rot ation remains, it appears as though the damage to
your Member's building has been caused by long term gradual
deterioration, howsoever caused.
c omplainant’s expert (R)
Report
undated
While inspecting the damage, I noticed that there doesn‟t seem to
be any damage to the limestone foundation buried at the base of
the wall as stated in the engineer‟s report. The stones and mortar
joints show no sign of downward deviation.
The wal l looks to have been damaged by downward motion of the
roof (e.g. wind event) which has cracked a number of the plat es
across the joins in the centre trusses of the building. The centre
Determination | Case number: 538265 Page 7 of 8
Re port Key points
plates show no signs of either moisture or wear and tear and look
to h ave been broken by shear force.
As the top chords of the trusses have pressed downward, they
have caused an outward motion which has pushed on the exterior
wall, and therefore caused it to fail.
complainant’s expert (W)
Report
28 May 2018
It is my opinion that the tilting (leaning) of the masonry wall is not
caused by footing failure, either tilting or subsiding.
There is no horizontal or vertical cracking in the Mt. Gambier stone
wall or the mort ar joints, which would be obvious if footing failure
had occurred.
complainant’s expert (C)
Report
24 May 2018
A visual inspection of the wall does not show any signs of cracking
in limestone blockwork or separation in mortar joints
between blockwork. No indication of any diagonal or vertical
movement of blockwork mortar joints was visible.
The condition of the soil below this point in which the footings have
been placed was moist and firm.
No visual or statistical evidence was found to support the theory
that the walls had been affected by settlement or
s ubsidence.
In conclusion, it is clearly evident that there is no subsidence or
long - term settlement in the footings. Accordingly, it would
be inaccurate to say that the present truss damage was caused by
settlement or subsidence.
complainant’s expert (K)
Report
25 May 2018
It appears that there isn‟t any damage at the base of the stone
walls to suggest movement of footings.
[…]
For the roof ceiling trusses to be damaged as it is the only other
factor would be wind (sic)
complainant’s expert (T)
30 August 2018
We do not agree with the I report that the footing has rotated due
to long term settlement of the foundation soils. The soils
encountered adjacent and below the stone footing appeared
compact.
We are of the opinion that the eastern wall has rot ated due to
failure of the roof trusses. The trusses have failed due to a failure
of the masonite connection plates at the bottom chord join in the
centre of the trusses. The roof trusses have been performing
satisfactorily up until the point of failure. I t is difficult to pinpoint a
specific cause for the failure of the masonite plates, but given the
age of the building, the failure of the masonite plat es is possibly
due to long term fatigue from cyclic wind loading.
c omplainant’s expert (T)
Email
15 November 2018
on review of our site photos and the I report, we don‟t believe that
there is enough evidence to suggest that the masonite plates have
been damaged by moisture. The surrounding timber members of
the truss don‟t appear to be moisture stained s o we highly doubt
that if there was moisture staining that it would be isolated to the
Determination | Case number: 538265 Page 8 of 8
Re port Key points
masonite plates only.
Secondly, we don‟t agree with the I report that the secondary
timber over top of the bottom chord splice was ret ro fitted aft er the
masonite plate s began to fail. More likely the secondary member
was used during construction of the trusses to secure the two
bottom chord members prior to fixing the masonite plates and nails
to the splice connection.
3.3 Relevant policy wording
Record Key points
What is protected
Page28
If 'Business Buildings' is specified in your Schedule of Protection,
we will protect you for loss or damage to your business building(s)
in Australia and caused by a protected event during the period of
protection.
What is not protected
Page 31
Specific exclusions
We will not pay loss or damage to or arising from:
[…]
(d) wear and tear, gradual deterioration or any gradually operating
cause.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.