Text of the determination
Determination | Case number: 533773 Page 1 of 6
Determination
Case number: 533773 31 December 2018
1 Determination overview
1.1 Complaint
The complainant holds a home and contents insurance policy with the financial firm
(insurer). The insurer accepted a claim in relation to storm damage to the
complainant‟s home. The repairs included a replacement of his roof. H owever, the
complainant subsequently expressed dissatisfaction with the repair of the roof, such
as the product used, amongst other matters. He also made allegations about the
conduct of the builder surveyor and the insurer‟s contractor.
The case manager provided the parties with a recommendation on the issues in
dispute. The recommendation was partially in favour of the complainant. A copy of the
recommendation is attached to this determination.
The recommendation was issued by the Financial Ombudsman Service (FOS)
Australia. The Australian Financial Complaints Authority (AFCA) has replaced FOS.
AFCA is responsible for managing FOS complaints lodged prior to 1 November 2018.
While this determination is issued by AFCA we have applied the FOS Terms of
Reference.
1.2 Issues and key findings
Were the findings of the recommendation correct?
The findings contained in the recommendation were correct and are adopted in this
determination. Further submissions provided after the recommendation have been
considered, but these do not warrant a change in the outcome.
Were the repairs carried out to the required standard?
The insurer is required to provide the complainant with a roof of „Colorbond Ultra‟ and
a downpipe in the same material.
Determination | Case number: 533773 Page 2 of 6
Was there any misconduct by persons involved in the repairs?
There is no probative evidence of inappropriate or fraudulent conduct alleged by the
complainant. If the complainant believes he has evidence of criminal activity he
should be taking the matter to the police.
1.3 Determination
This determination is partially in favour of the complainant.
I agree with the case manager‟s reasons for the recommendation and the
recommended outcome.
The insurer is required to replace the roofing material with „Colorbond Ultra‟ roof
sheets, provide a new downpipe in the same material and ensure the repairs fully
comply with the relevant building standards.
Determination | Case number: 533773 Page 3 of 6
2 Reasons for determination
2.1 Were the findings in the recommendation correct?
I have decided this case on its merits, having regard to the relevant law, good industry
practice, codes of practice and previous AFCA decisions. I have taken into account all
the material submitted by the parties, both before and after the recommendation. I am
satisfied the documentation I have relied on has been provided to both parties.
I am satisfied the case manager‟s recommendation contains an accurate summary of
the complaint, the issues to be determined, any applicable paragraphs of the Rules
and any relevant law.
2.2 Were the repairs carried out to the required standard?
Complainant expressed dissatisfaction with repairs
The insurer accepted the complainant‟s claim after a storm had caused damage to his
house. The insurer arranged repairs to be carried out, which included replacing his
roof. However, the complainant later contacted the insurer because he was
dissatisfied with the roof repairs, saying the entire roof sheeting was inappropriate for
his house‟s location (within 50 metres of the sea). He also raised other issues about
the repair work.
Insurer asked experts to examine repairs
The insurer asked RC, a roof tiling and roof plumbing consultant of more than 35
years‟ experience , to examine the roof. RC attended the property on 20 February
2018 and concluded (report dated 12 March 2018) the minimum acceptable roof
cladding for a house positioned within 100 metres of a benign marine environment
would be „Colorbond Ultra‟. RC could not determine the material type the insurer‟s
repairers had used.
RC also said there were a few minor installation shortfalls and faults. These included
non-compliant flashing lap join assemblies, insufficient mechanical fastenings of
barge end flashings and sheet turn down issues. RC also suggested using
„Colo r bond Ultra‟ instead of a „galvanised‟ product for the downpipe.
PB, a plumber, attended the property on 29 April 2018 and concluded the roofing
system had been installed to an overall high standard. PB said a visual inspection
found no evidence of debris blocking the flow of water, so it was not likely any water
ingress resulted from that cause (an issue which the complainant had raised). PB also
provided reasons why there would be no gutter overflows.
Insurer required to replace roofing tiles
RC did not recommend the roofing sheets the insurer‟s repairers had used (RC had
not been able to identify the sheeting used, although the product was later identified
Determination | Case number: 533773 Page 4 of 6
as a different product which did not have all the necessary qualities). Instead, RC
recommended the use of „Colorbond Ultra‟, as this was appropriate for a roof that
close to the sea.
RC has the appropriate experience, knowledge and expertise to assess whether the
repairs comply with the required standards and make appropriate recommendations
to correct any issues. Given RC‟s findings, the insurer is required to replace the roof
sheets with „Colorbond Ultra‟ and provide a new downpipe in the same material.
The insurer is also required to ensure these repairs fully comply with the relevant
building standards. In this regard, the insurer should appoint RC to check the repairs
on completion.
Complainant provided further submissions
The complainant rejected the recommendation that was partially in his favour and
provided further submissions in support (some submissions are dealt with in the
following section, 2.3 because they relate to that issue).
The complainant wants the determination to be delayed because he wants an
inspection carried out on his roof. Another reason is there may be criminal
proceedings initiated in relation to the roof repairs, although he has provided no proof
of this. The complainant has provided no compelling reason why the determination
should be delayed.
He also raised the issue about AFCA carrying out an inspection of his roof before
determinin g the matter. AFCA‟s process requires the parties to produce relevant
material in support of their respective positions. In this regard, the complainant would
need to provide a report from a suitably qualified tradesperson (such as a roofer or
similar) to support his assertions.
He said he spoke with a roofing company which indicated the repairers had used the
„wrong grade of roofing‟. He said he should be entitled to „Colorbond Stainless‟
because it provides a 25-year warranty, whereas „Colorbond Ultra‟ only provides a 10-
year warranty. However, PB provided information that indicates „Colorbond Ultra‟ also
has a 25-year warranty.
The complainant commented on why he should be entitled to „Colorbond Stainless‟.
However, he has provided nothing in writing from the roofing company that supports
his comments and has provided no compelling reasons that contradict RC‟s findings.
The compl ainant‟s further submissions do not warrant a change in the outcome in the
recommendation. As such, RC‟s recommendation that „Colorbond Ultra‟ be used is to
apply.
Determination | Case number: 533773 Page 5 of 6
2.3 Was there any misconduct by persons involved in the repairs?
Complainant alleged misconduct by certain persons
The complainant made serious allegations about the building surveyor and the
insurer‟s contractor, using the term „ fraudulent action ‟. He said he had „hard primary
evidence‟, however he has failed to provide it to substantiate these serious
allegations.
Any allegation of fraudulent conduct is a serious matter. Definite proofs should be
provided to making such an adverse finding. The available information shows no
probative evidence upon which I could make a finding of fraudule nt conduct as
alleged by the complainant. If the complainant believes he has evidence of criminal
activity he should be taking the matter to the police.
Complainant provided further submissions
As indicated previously, the complainant provided further submissions after rejecting
the recommendation. He still maintains he has „hard evidence‟ of misconduct but has
not provided it. He also asked whether the determination should proceed, given the
police will want to view the roof for evidentiary purposes. However, there is no
indication the police are involved and actively pursuing the matter.
There are no compelling reasons for holding up the issuing of this determination. The
complainant‟s further submissions on this issue add nothing new and therefore do not
warrant a change to the outcome in the recommendation.
Determination | Case number: 533773 Page 6 of 6
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with Financial Ombudsman Service (FOS).
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
claim claim
Recommendation
Case No: 533773 Recommendation Page 1 of 5
Case number: 533773 24 October 2018
1 Overview
1.1 Dispute
The applicant holds a home insurance policy with the financial services provider
(FSP). The applicant lodged a claim with the FSP for storm damage to the roof of his
house. The FSP arranged for the repairs to be completed, however the applicant was
dissatisfied with the quality of the repairs. The applicant also alleged that the
certificate from the building surveyor is fraudulent and is concerned that criminal
activity has taken place.
1.2 Issues and key findings
Have the roof repairs been completed to the required standards?
I do not consider that the repairs to the roof have been completed to the required
standards:
the roof inspection report completed by the roof tiling and plumbing consultant
commissioned by the FSP (RC) clearly states that “Colorbond Ultra” roofing
material (as opposed to regular Colorbond) needs to be used, given the very
close proximity of the property to a marine environment
the FSP‟s repairer used a different roofing material called Apdeck 700
the FSP has provided specifications for Apdeck 700 and while it may be
somewhat comparable to regular Colorbond material, no evidence has been
provided to support that it is the same as Colorbond Ultra.
Is there any evidence to support that fraudulence has occurred?
I do not consider that there is any evidence to support that fraud or criminal activity
has occurred.
1.3 Recommendation
This recommendation is partially in favour of the applicant.
Should the parties accept the recommendation, the FSP is obliged to replace the
roofing material that was in stalled on the applicant‟s house with genuine “Colorbond
Ultra” roof sheets and also to provide a new downpipie, flashings and eaves gutters
in “Colorbond Ultra” material, as per RC‟s recommendations.
Case No: 533773 Recommendation Page 2 of 5
2 Reasons for recommendation
2.1 Have the roof repairs been completed to the required standards?
FSP’s own expert states that “Colorbond Ultra” roofing material is required
Following the applicant expressing dissatisfaction with the repairs that were carried
out to his roof, the FSP engaged a roof tiling and plumbing consultant (RC) to attend
the property and inspect the repairs. In the report from March 2018, RC clearly states
that Colorbond Ultra roofing material should be used given the proximity of the
property to a benign marine environment (in this case, the ocean). RC states that any
property within 100 metres of the high water line should have Colorbond Ultra fitted.
As part of its inspection, RC lifted several roof sheets but was unable to find any
production stamp to confirm what type of roofing material had been installed. RC
noted that products of a similar type usually have a production stamp.
FSP has been unable to provide evidence that the roofing material is adequate
The FSP confirmed to me that the roofing material that was installed is a product
called Apdeck 700. The FSP provided specifications for Apdeck 700 and while this
confirms the product may be similar to regular Colorbond, there is no evidence that
Apdeck 700 is of equivalent specification to Colorbond Ultra.
The distinction between Colorbond Ultra and regular Colorbond roofing material is a
crucial one. In addition to the report from RC, I have conducted my own online
research and have come to the same conclusion as RC – given the close proximity of
this property to a marine environment (th e applicant‟s house is within approximately
50 metres of the high water line), Colorbond Ultra roofing material should have been
used. Colorbond Ultra possess a thicker zinc coating than regular Colorbond
products in order to provide better corrosion protection in close proximity to marine
environments where there might be salt in the air.
The specifications provided by the FSP for Apdeck 700 make no mention of whether
or not there is a zinc coating, and if so, how thick the zinc coating is. I have
conducted my own online research into this as well, and I have been unable to locate
any evidence that Apdeck 700 possesses the same thickness zinc coating as
Colorbond Ultra.
Page 34 of the product disclosure statement (PDS) states that the FSP will make
“reasonable attempts” to match materials. This means that the FSP is not technically
obliged to match materials but should make the effort to. Given that the original fibro
cement sheeting that was previously fitted to the house could have potentially
contained asbestos, this would not be a suitable material to use in line with current
building codes. Hence, the FSP needs to provide a suitable alternative. It has been
established by the FSP‟s expert that Colorbond Ultra is the most suitable alternative,
and my online research also indicates this to be the case. Online searches confirm
that Colorbond Ultra is currently available. I am therefore of the opinion that it is
Case No: 533773 Recommendation Page 3 of 5
reasonable to request the FSP the replace the roofing material that has been
installed with Colorbond Ultra roofing material, as recommended by RC, in order to
provide adequate corrosion protection. I am also of the opinion that the FSP should
provide a new downpipe, flashings and eaves guttering in matching Colorbond Ultra
material as per the recomm endations in RC‟s report.
Other issues with the roof repairs
The report from RC also identified several other issues with the repairs that had been
made to the roof. Among these were a lack of a continuous overflow system to the
gutters, non-compliant flashing lap join assemblies, insufficient mechanical
fastenings of barge end flashings and failure to turn down some roof sheets. The
evidence that has been provided, such as the subsequent roof inspection report from
PB, indicates that the FSP has now eithe r rectified or is waiting on the applicant‟s
agreement to rectify these issues (such as in the case of turning down of some of the
roofing sheets). Given that I have recommended that the existing roofing material
needs to be replaced, the FSP will need to ensure that the new Colorbond Ultra
roofing material is installed in line with the recommendations made in RC‟s report.
I note that the applicant said that there was water ingress into his property as a result
of the changes made to his roof plumbing. The applicant has not provided any
evidence to show that there was any water ingress into his property, or that any
water ingress was due to alterations made to his roof plumbing. Therefore, I consider
it reasonable for the FSP to adhere to the recommendations set out in RC‟s report
when replacing the roofing material without the need for any further alterations.
2.2 Is there any evidence to support that fraudulence has occurred ?
Applicant alleged that fraudulence and criminal activity has occurred
The applicant alleged that the certificate issued by the building surveyor is fraudulent
and that criminal activity may have occurred. The applicant indicated that he had
“hard primary evidence” to support this when he lodged his dispute with FOS.
No evidence to support that fraudulence or criminal activity has occurred
The applicant has not provided any evidence to support that fraudulence or criminal
activity has occurred, nor has the applicant provided any of his own reports.
Fraud carries a high burden of proof – the applicant would need to show that a
dishonest act or omission with an intention to deceive to obtain a material advantage
has occurred. The applicant has not been able to show that this is the case, nor do I
consider that there is any evidence to suggest that this is the case. I am therefore
satisfied that the issue of fraudulence and/or criminal activity as alleged by the
applicant does not require any further consideration by FOS.
Case No: 533773 Recommendation Page 4 of 5
3 Supporting information
3.1 Policy wording
Page 34 of the Product Disclosure Statement (PDS)
Buildings – what we will and won’t pay
We will, at our option, choose whet her to:
repair or rebuild your buildings, or
pay the reasonable cost of repairing or rebuilding your buildings.
…
If we choose to repair your buildings, we will:
make reasonable attempts to match the materials used when your buildings were built or last
renovated
…
Where we are unable to match materials, we will use or pay for materials which we believe to
be of a similar kind or quality
3.2 Expert reports
Record Key points
FSP’s expert (RC )
Report
12 March 2018
The house is constructed in very close proximity to a marine
environment, indeed only approximately 50 metres from the high
water line.
The relevant paragraph [of Standards Australia H B 39 the
Installation Code for Metal Roofing and Wall Cladding] specifically
references Port Phillip Bay and requires that a higher performanc e
coating system is required for long - term protection when a house if
constructed within 100 metres of the beach such as this hous e is.
I then refer to *Metal Roof Cladding Manufacturers “technical
manuals”, specifically - *Lysaght / *Bluescope that specify that
“Colorbond Ultra” – should be installed to a building in a benign
marine environment, such as Port Phillip Bay, where this buildi ng is
constructed within 100 metres of the high water line.
I recommend requests are made to the builder and plumbing
contractor to provide documentary evidenc e that Colorbond Ultra
roof cladding, flashings and eaves gutters were installed to the roof
of t his house.
If it is determined that only “standard” Colorbond material has been
installed to the roof of this house then the existing roof cladding
needs to be replaced with Colorbond Ultra mat erials due to the
close proximity to a benign marine environmen t.
Applicant’s expert (PB )
Report
29 May 2018
Visual inspection found no evidence of debris blocking the flow of
water, it is therefore unlikely that any water ingress occurred as a
result of any debris.
Overflows in gutter? No (10mm spacing[s] have been provided at
the back of gutter as per current day standards [and] codes, this
Case No: 533773 Recommendation Page 5 of 5
acts as a breaker to ensure wat er doesn‟t overflow into the
dwelling. Rear right hand stop end of gutter has also been cut lower
than fascia board to ensure wat er will overflow a t this point.)
The roofing system has been installed to an overall high standard.