Text of the determination
Determination | Case number: 531388 Page 1 of 12
Determination
Case number: 531388 12 March 2019
1 Determination overview
1.1 Complaint
The complainant lodged a claim under his insurance policy with the financial firm
(insurer) for damage to his tenanted investment property, following storms associated
with Cyclone Debbie in March 2017.
In April 2018, the parties negotiated to cash settle the claim for $84,950. However, the
complainant says he agreed to the cash settlement under duress. The complainant
seeks payment of a further $48,000 for additional damage he says was caused by the
storms.
In January 2018, the complainant lodged a separate claim, after the ducted air
conditioning system at the property broke down. The complainant says the damage
was caused by a power surge.
The insurer denied the claim on the basis the damage to the air conditioning system
was caused by corrosion, which is excluded from cover under the policy.
The complainant disputes th e insurer’s decision and seeks cover for the cost of
replacing the ducted air conditioning system.
1.2 Issues and key findings
Should the cash settlement for the storm damage claim be increased?
The cash settlement amount is fair and reasonable. The insurer is not liable for the
additional amount sought by the complainant for damage to the top deck, as this
damage was caused by gradual deterioration which is not covered under the policy.
Accordingly, the insurer is not required to increase the settlement amount.
Is the insurer liable for the damage to the air conditioning system?
While the available information establishes that the larger condenser unit failed due to
corrosion, there is conflicting information about the condition of the smaller unit . As
the insurer did not fully investigate this aspect of the claim, it should contribute to the
cost of repairs.
Determination | Case number: 531388 Page 2 of 12
1.3 Determination
This determination is partially in favour of the complainant.
The insurer is not required to increase the cash settlement amount for the storm
damage. However, the insurer is required to pay the complainant the amount of
$10,000 as a contribution to the cost of replacing the air conditioning system.
Determination | Case number: 531388 Page 3 of 12
2 Reasons for determination
2.1 Should the cash settlement for the storm damage claim be increased?
Cash settlement amount was negotiated by the parties
The complainant lodged a claim for storm damage in July 2017, approximately two
months after the storm occurred. The insurer appointed an engineer (IE) to inspect
the property and determine the cause of the damage claimed.
Based on IE’s report, the insurer accepted liability for the internal water damage to the
property. However, the insurer denied liability for other damage which IE advised had
been caused by factors which are excluded under the policy (such as gradual
deterioration and faulty construction).
The insurer’s builder prepared a scope of works for the repair of the internal water
damage and quoted $28,702 to complete the works. After the complainant raised
concerns about various items, the scope of works was expanded and the quotation
was increased to $53,178.
The complainant expressed concern that the amount offered would not allow him to
engage his own contractors to undertake the works. In response, the insurer
subsequently increased the cash settlement offer to $67,370.60. This amount
included allowances for contingencies, including an additional 10% for unforeseen
damage.
In early March 2018, the complainant requested that the cash settlement amount be
increased by an additional $48,000 to cover external damage to ‘the top deck’. This
amount was based on a report and quotation provided by the complainant’s builder
(NC).
The insurer advised the complainant that NC’s report di d not alter its position that the
damage to the top deck had been caused by excluded factors. However, the insurer
advised it was willing to increase the cash settlement offer to $80,000 for a limited
period, in order to finalise the dispute.
The complainant sought a further increase in the cash settlement amount to $90,000.
However, in mid-April 2018, he agreed to accept a cash settlement of $84,950 (which
included costs incurred in obtaining expert reports). The cash settlement amount was
paid shortly thereafter.
Settlement was not entered into under duress
Where the parties have reached a settlement to resolve a dispute, AFCA will
generally be reluctant to depart from the terms of that settlement.
Determination | Case number: 531388 Page 4 of 12
However, there are certain circumstances which will jus tify doing so – for example, if
the complainant was not fully informed or misunderstood the terms of the agreement
or if the settlement was entered into under duress.
In the present case, the complainant says he entered into the settlement under
duress. However, the history of the negotiations between the parties does not support
his position.
The cash settlement amount was agreed after protracted negotiations between the
parties, involving several offers and counter-offers.
The complainant was represented by his broker, who was fully involved in the
negotiation process. Further, the complainant is a qualified lawyer, who could be
expected to understand the implications of agreeing to cash settle his claim for an
agreed amount.
For the reasons outlined above, I am not satisfied that the complainant was acting
under duress when he accepted the insurer’s offer to cash settle the claim for
$84,950.
Waterproofing failure was caused by excluded factors
As outlined above, the complainant is seeking an additional amount of $48,000 for the
repair of damage to the ‘top deck’ of the property, which includes an in -ground
swimming pool.
This amount of $48,000 was identified in NC’s report as the cost of replac ing the
waterproof membrane on the top deck, including removing and replacing paved areas
so these works could occur.
The insurer denied liability for the repair of waterproofing to the top deck. The insurer
says the issues with the waterproofing have been caused by gradual deterioration
and/or faulty construction and maintenance, which is excluded from cover under the
policy.
The insurer’s engineer (IE) reported that the waterproofing of the top deck was
inadequate, due to the use of incorrect methods and non-compliant installation. IE
confirmed that the intensity of the rain experienced during the storm would not have
caused the waterproofing to fail.
The building consultant (DB) appointed by the complainant also identified defects in
the waterproofing which he considered had allowed rainwater to enter during the
storm. DB advised that:
the construction of the top deck and wall junctions was not consistent with best
industry practice at the time of construction
Determination | Case number: 531388 Page 5 of 12
waterproofing protection was provided by the use of a cosmetic sealer applied to
the deck (instead a proper water barrier), which DB described as an ‘unacceptable
construction methodology’
the cosmetic sealants had deteriorated and were nearing the end of their useful life
at the time of the storm.
In his report, the complainant’s builder (NC) noted that the waterproofing of the
property relied on coatings and sealants, which would deteriorate over time following
exposure to the elements.
NC commented that further leaks may have occurred following the storms. However, I
am not satisfied that his report establishes that the storms caused the waterproofing
to fail, given the nature and extent of the pre-existing issues identified.
Based on the reports and photographs provided, I am satisfied that the waterproofing
issues affecting the top deck were caused by gradual deterioration and faulty
construction. While the complainant may have carried out maintenance to this area,
these works were not sufficient to ensure the waterproofing remained effective.
Damage caused by gradual deterioration and faulty construction is excluded from
cover under the policy. Accordingly, the insurer is not liable for the additional amount
of $48,000 incurred in replacing the waterproof membrane.
Insurer not required to increase cash settlement amount
The policy provides cover for loss which occurs subsequent to damage caused by
excluded factors. Accordingly, the insurer is liable for damage caused by water
entering through the failed waterproofing membrane (even though damage to the
membrane itself is excluded).
The cash settlement paid by the insurer includes the cost of repairing internal water
damage to the property. As outlined above, the settlement amount for the internal
repairs was negotiated by the parties.
For the reasons outlined above, the insurer is not liable for the damage to the top
deck. There is no information to show that the settlement is otherwise unfair or
unreasonable.
Accordingly, the insurer is not required to increase the cash settlement amount.
2.2 Is the insurer liable for the damage to the air-conditioning system?
Policy provides cover for physical damage subject to exclusions
The complainant is required to show that, on the balance of probabilities, he has
suffered a loss caused by a risk insured against under the policy. This is known as a
valid (or prima facie ) claim.
Determination | Case number: 531388 Page 6 of 12
If the complainant is able to establish a prima facie claim, then the onus shifts to the
insurer to show that, on the balance of probabilities, it is entitled to rely on a policy
exclusion or otherwise deny the claim.
The complainant’s policy provides cover for ‘physical loss or damage’ to the insured
property, subject to the conditions and exclusions set out in the policy.
The policy contains a general exclusion for damage caused by wear and tear, gradual
deterioration, rust and corrosion.
Complainant says air conditioning system was damaged by a power surge
The complaina nt’s cla im is for the replacement of a multi inverter, ducted air
conditioning system (AC system) which cooled the top floor of his property.
The system comprised two outdoor condenser units located on the rooftop (with
capacity of 19.9kW and 12kW respectively), together with seven ceiling mounted
ducted evaporators located in various rooms of the property.
The complainant lodged a claim for the breakdown of the AC system in January 2018.
In his claim form (signed on 20 January 2018), the complainant described the cause
of damage as ‘fusion of motors’.
The claim form attached a brief report and quotation from the complainant’s air
conditioning specialist (AA) dated 4 January 2017. AA confirmed the ‘air conditioning
systems’ had failed and noted that the entire system needed to be replaced because
the existing internal units were not compatible with newer condensers.
AA’s initial report did not identify the cause of damage to the AC system. However in
an updated report provided in late February 2018, he stated that the systems were
reported to have failed from a power surge to the property.
In a further report provided in early March 2018, AA stated that:
the 12kW condenser had failed due to the fusion of the AC compressor
he was unable to provide the model number as the unit had been removed from
the site, and
the damage to the condenser had been caused by a power surge that had also
damaged the other (19.9kW) unit.
The complainant says both the 12kW unit and the 19.9kW unit were damaged by a
power surge.
Insurer’s experts say damage was caused by corrosion
The insurer’s loss adjuster (PG) and air conditioning technician (EE) attended the
property in April 2018 to determine the cause of the breakdown. They inspected the
19.9kW condenser and reported that:
Determination | Case number: 531388 Page 7 of 12
the AC system was showing a fault code indicating low gas pressure
testing identified that the unit had very low pressure (30psi) and a gas leak
the condenser unit was extremely deteriorated due to severe corrosion
testing of the AC system did not identify any other issues.
EE concluded that the failure of the AC system had been caused by a gas leak from
the unit coil, which had been damaged by severe corrosion as a result of long-term
exposure to severe weather conditions.
EE advised that the failure was not consistent with having been caused by a power
surge, as the PCBs and compressors remained functional. Further, there was no
evidence of damaged components or wiring in the unit (as would be expected had a
power surge occurred).
The complainant disputes PG and EE’s findings. He has provided a further report
from his air conditioning specialist (AA) prepared in May 2018. In this report, AA
states that the PCBs wer e found to be ‘locked up’ after the power surge. While AA
acknowledges the system was low on gas, he says this was not the cause of the
failure.
However, AA has also provided a subsequent report dated 10 December 2018 which
states that the damage to the A C system occurred ‘due to general operation’ (and
does not refer to a power surge).
While AA confirmed he had carried out regular maintenance to the condenser units, I
am not satisfied this was sufficient to prevent corrosion developing, given the
environment to which the units were exposed. AA noted that, while he carried out
electrical testing of the units, he was unable to identify whether internal components
of the refrigeration system might fail.
Air conditioning system was not damaged by power surge
Having carefully reviewed the available information, I consider it is inconsistent with
the damage to the AC system having been caused by a power surge.
The testing carried out by the insurer’s contractors (PG and EE) establishes the
presence of a gas lea k. Further, the close up, colour photographs included in PG’s
report support their statements about the extent of the corrosion to the unit and the
absence of damage to the wiring.
While AA states that the damage was caused by a power surge, he has provided
relatively little information to support his conclusions.
During the course of the claim, the insurer asked the complainant to provide evidence
that a power surge had occurred. In response, the complainant provided a letter from
Determination | Case number: 531388 Page 8 of 12
his energy supplier (EE) confirming there was storm related damage affecting the
electricity supply the property on 26 February 2018.
However, the claim for the damage to the AC system was lodged on or after 20
January 2018 (and AA provided his initial quotation on 4 January 2018). Accordingly,
the incident referred to in EE’s letter cannot have caused this damage.
The complainant has not provided any information from his energy supplier which
indicates there was a power surge to the property around the time the damage
occurred.
The complainant says the fact the insurer accepted his claim for damage to the
internal lift at the property establishes there was a power surge.
However, the insurer’s contractors found no evidence that the lift had been damaged
by a power surge. The insurer accepted the lift claim on the basis the damage had
been caused by water entry during the storms in March 2018 (which occurred after
the failure of the AC system).
Damage to 19.9kW unit was caused by corrosion
Based on the available information, I am satisfied that the damage to the 19.9kW
condenser unit was caused by a gas leak due to corrosion (as identified by PG and
EE).
PG and EE’s reports provide a logical and rational explanation of how the damage
occurred, which is consistent with the observed facts. EE’s testing revealed a gas
leak from the corroded condenser and did not identify any other issues which might
have caused the failure.
Condition of 12kW unit is unclear
There is conflicting information about whether (and if so, how) the 12kW condenser
unit was damaged.
As outlined above, the complainant’s air conditioning specialist (AA) advised that both
condenser units had been damaged by a power surge. However, there is no evidence
of a power surge around the time the AC failure occurred.
It is also unclear whether the damaged 12kW condenser unit remained available for
inspection when PG and EE attended the property in April 2018.
In March 2018, AA advised that the damaged 12kW unit had already been removed
from the property.
When the insur er’s contractors attended the property in April 2018, they only
inspected one condenser unit (which appears to have been the larger, 19.9kW unit).
Determination | Case number: 531388 Page 9 of 12
However, photographs taken at the time show a smaller unit alongside the larger one
(although the smaller unit appears to have been disconnected from the power
supply). It is unclear whether this is the damaged unit referred to by AA.
Insurer’s failure to inspect 12kW unit has prejudiced claim
As outlined above, the complainant’s policy provides cover for physical damage to his
property. To establish a valid (or prima facie ) claim, the complainant need only show
damage has occurred – he is not required to establish the cause of the damage.
If the complainant can establish there is physical damage to the propert y, the insurer
is required to show that, on the balance of probabilities, the damage was caused by
excluded factors.
The available information establishes that the 19.9kW condenser unit was damaged
and was not capable of being repaired. The damage to this unit was caused by
corrosion and therefore is excluded from cover under the policy. The damage to this
unit is sufficient to necessitate the full replacement of the AC system.
There is insufficient information to determine whether the 12kW unit has been
damaged (and, if so, to identify the cause of the damage). While AA stated the unit
had been damaged, his report is unreliable as he wrongly identified the cause of the
damage and was apparently mistaken as to whether the unit had been removed from
the property.
Further, AA later advised the unit had failed due to normal operation, which is
suggestive of the cause being general wear and tear.
Nevertheless, while AA’s advice was confusing, the insurer was clearly made aware
of the complainant’ s belief that there was damage to both of the condenser units.
PG’s report dated 12 March 2018 noted that both units were reported to have failed
due to a power surge.
In these circumstances, the insurer’s contra ctors should have confirmed whether the
12kW unit was available for inspection when they attended the property. The
contractors’ failure to do so has potentially prejudiced the complainant’s ability to
claim for damage to this unit (in the event the damage was not caused by excluded
factors).
Insurer is required to contribute $10,000 to cost of repairs
The complainant has provided invoices totalling $30,000 for the replacement of the
ducted AC system. He has advised he spent an additional $10,000 on building works
required for the installation. While the complainant has not substantiated these costs,
they do not appear unreasonable, given the previous quotations provided.
Given the insurer’s failure to fully investigate the condition of the 12kW condenser
unit, I consider it should be required to contribute to the cost of the repairs.
Determination | Case number: 531388 Page 10 of 12
However, in considering the amount of the insurer’s contribution, I have had regard to
the known damage to the 19.9kW condenser, as well as the uncertainty resulting from
the inconsistent information provided by the complainant and his repairer.
In the circumstances, I consider the insurer should be required to contribute $10,000
to the cost of the repairs. The insurer is not required to pay interest on this amount.
Determination | Case number: 531388 Page 11 of 12
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with Financial Ombudsman Service (FOS).
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
3.2 Our approach to this complaint
We have considered it appropriate to expedite this complaint in accordance with the
Operational Guidelines to the FOS Terms of Reference, due to the nature of the
complaint. Accordingly, this complaint has not been the subject of a preliminary
assessment and has proceeded directly to determination.
This complaint has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other. All of the material provided by the parties has been reviewed and
considered.
The complainant has been represented by his broker. For the purposes of this
determination, submissions made by the complainant’s broker have been treated as if
they had been made by the complainant himself.
3.3 Scope of this determination
Insurer accepted liability for lift claim
During the course of this complaint, the complainant referred to a separate claim
lodged in May 2018, following the breakdown of an internal lift at the property. The
complainant said the lift was damaged by a power surge.
Determination | Case number: 531388 Page 12 of 12
Based on the findings of its consultants, the insurer disagreed that the damage had
been caused by a power surge. However, the insurer settled the claim on the basis
that the damage had been caused by water entry during the storm in March 2018.
The complainant has confirmed that his claim for the lift has now been resolved.
Accordingly, it is unnecessary to consider this aspect of the complaint any further.
Loss of rent claim is outside scope of determination
During the storm damage claim, the complainant advised the insurer he had reduced
the rent payable by his tenant as a result of the damage to the property. However, a
claim for loss of rent did not progress at this time.
After this complaint was lodged with AFCA, the complainant confirmed that he wanted
to pursue his claim for loss of rent. The insurer agreed to consider the claim, subject
to the complainant providing further information. The parties agreed that the claim for
loss of rent would be treated as outside the scope of this determination.