Text of the determination
Determination | Case number: 522881 Page 1 of 12
Determination
Case number: 522881 18 December 2018
1 Determination overview
1.1 Complaint
The complainant lodged a claim on her home building policy in April 2017 after her
property suffered extensive cracking due to a leaking storm water drain.
The financial firm (insurer) accepted the claim in part, however, a complaint has
arisen on the basis the insurer has only agreed to pay for a proportioned amount of
the internal damage to the building, and has declined any liability for damage to the
external areas. The insurer says the external cracking is due to factors such as
ground movement and inadequate footings.
The complainant does not agree with the insu rer’s decision and seeks a review.
1.2 Issues and key findings
Has the insurer correctly assessed its liability under the policy?
The complainant has established a prima facie claim under the policy.
The insurer has not established, on the balance of probabilities, that an exclusion
applies or that it can limit its liability to 70% of the internal damage only. Accordingly,
the insurer is required to settle the claim in accordance with the terms of the policy.
1.3 Determination
This determination is in favour of the complainant.
The insurer is required to settle the claim in accordance with the policy terms and
conditions.
Determination | Case number: 522881 Page 2 of 12
2 Reasons for determination
2.1 Has the insurer correctly assessed its liability under the policy?
Policy provides cover for insured events subject to exclusions
The complainant is required to show, on the balance of probabilities, she has suffered
a loss caused by a risk insured against under the policy. This is known as a valid (or
prima facie ) claim.
If the complainant is able to establish a prima facie claim, then the onus shifts to the
insurer to show, on the balance of probabilities, it is entitled to rely on an exclusion
under the policy or is otherwise entitled to decline the claim.
The complainant’s policy provides cover for damage cau sed by the events listed in
the policy (including water leaking or escaping from house gutters, drainpipes or pipes
and sanitary fixtures such as bathtubs and toilets), subject to the conditions and
exclusions set out in the policy.
Complainant has established a prima facie claim
The reports prepared by both the insurer’s and complainant’s experts confirm the
complainant’s property has sustained cracking damage. Both parties’ experts
concluded the cracking damage was caused by water escaping from a defecti ve
stormwater drain. The experts also concluded that water had escaped from other
defective areas such as the bathroom vanity, the bath trap waste, and the shower
recess.
In these circumstances, I am satisfied the complainant has established a prima facie
claim.
Accordingly, the insurer bears the onus of establishing that, on the balance of
probabilities, it is entitled to rely on a policy exclusion or is otherwise entitled to
reduce its liability for the complainant’s claim.
Insurer’s interpretation of exp ert evidence is not persuasive
The insurer does not dispute the property sustained cracking damage or that there
was a water leak. However, it says it is only liable for 70% of the internal damage
based on its interpretation of the findings of its expert report:
Subsidence and cracking local to the bathroom and study areas has only been
exacerbated by the water escape from defective stormwater drain and bathtub
waste drain (70%).
Initial movement and cracking to this area and elsewhere in the dwelling can be
attributed to combined effects of uncapped perimeter soil, the prolonged drought
period, and seasonal movement of the reactive clay bearing strata (30%).
Determination | Case number: 522881 Page 3 of 12
It is not clear to the panel why the insurer believes it is only liable for 70% of the
internal damage, and has no liability whatsoever for any external damage, as its
expert report does not appear to support this position. The cracking ‘local to the
bathroom and study areas’ would include both internal and external cracking, as the
report does not state internal only.
Furthermore, the cracking visible inside the bathroom is the very same cracking that
is visible on the external wall. There is no feasible explanation provided as to why
only half of the same crack is attributable to the water leak. The pa nel’s view is that
the 70/30 proportional split speaks to the engineer’s interpretation of how much of the
overall damage was caused by the water leak, and how much damage was caused
by other factors.
The insurer was provided the opportunity to comment further on this aspect, and said
it would conduct a re-inspection of the property.
Re-inspection revealed further leaks and ongoing building distress
On reattendance the insurer’s expert (IL) noted that there was new cracking to the
building’s interior, the f loor levels had changed significantly, and there was water
damage to the plaster on the western wall of the property. TB were re-engaged to do
further leak detection testing.
TB reported that the storm drains were no longer leaking, however, they had
discovered a significant leak in the shower and noted that the water was escaping
quicker than the shower could fill. TB noted that the caulking at the base/wall of the
shower had detached, which was likely due to building movement.
IL also noted that the compl ainant’s plumber had been unable to find a leak in the
bath waste trap, and as such its previous finding that 70% of the damage was
attributable to water leaks should be revised downwards. Further, IL noted the
complainant’s expert had indicated the existi ng footings were not deep enough to
cope with the consequences of the plumbing problems.
The insurer reviewed the findings of its experts and noted the water leak from the
shower would not be covered under the policy. Additionally, taking into account the
comments made by IL in regard to there not being a leak from the bath as previously
thought and other contributing factors being outside the scope of cover (such as faulty
workmanship), it reduced its liability to 50% - again only for the internal damage.
Proximate cause of damage was the defective stormwater drain
If the insurer is to rely on the exclusions for ground movement, faulty workmanship or
a leaking shower base, it must establish said exclusions are the proximate cause of
damage and not the leaki ng stormwater pipe. The proximate cause of damage is the
dominant or effective cause of damage.
Determination | Case number: 522881 Page 4 of 12
Case law establishes that the proximate cause of loss is the dominant or effective or
operative cause of the loss, whether or not that be the last in time or the sole cause.
If there are several causes operating contemporaneously, each must be examined for
the qualities of reality, predominance and efficiency as the active, efficient cause that
sets a relevant chain of events in action. If one cause would have caused the harm in
any case, and the other would not have done so in the absence of the first, the first is
the proximate cause. This aspect is highlighted in the complainant’s engineer, RC’s,
report of 19 September 2018.
The final report provided by RC has clearly identified this aspect:
The focus of the damage and subsidence is toward the front NW corner, where
the past leaks were reported
My conclusion was that the past leaks were assumed the main cause of
movement and damage to the building
…
If the stormwater leak had not occurred it is likely that the other factors would not
have been enough to cause major movement/damage.
The insurer chose not to respond to RC’s supplementary report. In the panel’s view,
the information provided by the insurer is not sufficient to establish the ground
movement was not caused by the leaking pipe.
Both parties’ experts agree that the concentration of the damage is in the area of the
broken stormwater pipe and the leaking bathroom trap waste and the shower,
however, the insurer has never addressed this finding. Further, whilst the insurer has
relied on its exclusion for shower bases to deny liability for the leak from the shower, it
has failed to consider RC’s discussion on proximate cause:
It is also likely that the minor factors occurred as a result of the primary cause –
that is, the movement caused by the stormwater drain leak caused some of the
minor leaks such as the bath and shower base.
The panel is persuaded by the reports from the complainant’s engineer RC, and is not
satisfied that the insurer has established it can limit its liability or rely on an exclusion
under the policy to deny cover.
The panel is satisfied the proximate cause of the damage to the complainant’s
property was the escape of liquid from the broken stormwater drain, which is an
insured event that falls within the terms of cover under the policy.
Complainant is entitled to costs of engineering report
Under paragraph 9.4 of the Financial Ombudsman Service (FOS) Terms of
Reference, the Service can determine the insurer contribute towards the costs of the
Determination | Case number: 522881 Page 5 of 12
expert reports obtained by a complainant for the purpose of assisting in the complaint
before the Service.
The panel has found the reports of RC to be of help in the complaint, and has been
persuaded by these reports to find in favour of the complainant. In the circumstances,
the panel is satisfied the insurer should contribute to the cost of the complainant
obtaining the reports and should meet the complainant’s claim for costs up to a
maximum of $3,000, subject to the complainant providing a receipt.
Determination | Case number: 522881 Page 6 of 12
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with Financial Om budsman Service (FOS).
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
claim claim
3.2 Our approach to the determination
This complaint has not been the subject of a recommendation. Due to the nature of
the complaint, it has been referred directly to a panel for determination, in line with the
Operational Guidelines to the FOS Terms of Reference. The panel consists of an
ombudsman and two representatives with consumer and insurance experience.
The panel has decided this case based on what is fair in all the circumstances, having
regard to the relevant law, good industry practice, codes of practice and previous
decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other.
The panel has reviewed and considered all of the material provided by the parties.
While the parties have raised numerous issues in their submissions, for the purposes
of this determination, the panel has restricted its commentary to those issues that it
considers directly relevant to the outcome only.
Determination | Case number: 522881 Page 7 of 12
3.3 Policy terms
Policy term Key points
Certificate of Insurance
Policy schedule
Valid 15 July 2016 to 15 July 2017
Building cover
AD option not selected
The events we cover
Pages 19 - 25
Water and oil leaks
If loss or damage is caused by water or oil leaking or escaping
from an item shown here:
Covered
water leaking or escaping from:
- house gutters, drainpipes or pipes
- sanitary fixtures, for example baths or toilets
…
costs to locate the cause of the damage (if we agree to pay
these costs before you mak e any arrangements)
Not covered
water leaking or escaping from a shower recess or shower
base
...
General exclusions that
apply to your policy
Pages 45 - 47
Exclusions for all cover
These exclusions apply to all cover under your policy.
What we don’t cover
…
The settling, shrinkage or expansion in buildings,
foundations, walls or pavements
…
Maintaining and occupying your home
We don’t cover loss, damage, injury or death arising from:
faulty design or workmanship
3.4 Key documentation
Record Key points
Insurer’s expert (JPF)
Report
undated
Inspected property on 13 April 2017
Unable to confirm what has caused the damage
Damage has been evident for at least two years
Recommend a leak det ection report
Believe the most likely cause is ground movement
A brief SoW has been prepared for the resultant damage we
can see, however if claim accepted an engineer would need
Determination | Case number: 522881 Page 8 of 12
Record Key points
to be appoint ed
Repairs would need to be in two stages: underpinning and
then internal repairs
Insurer’s expert (P B )
Report
9 May 2017
Reviewed bathroom and external areas of property
Visual inspection found water damages, movement and
cracking affecting the plaster wall, tiled floor, tiled wall
(bathroom) and brick wall (external)
Visual inspection showed the vanity unit was not draining due
to a kinked pipe
Bath test found large amounts of water exiting from the trap
waste – this is causing the wood to rot and is contributing to
the cracking of the wall
Recommend CCTV inspection as we believe there are further
defects in the ground drainage syste m
Pressure testing indicated all domestic lines in serviceable
condition with no current leakage concerns
It is our opinion the wat er damages, movement and cracking
(interior and exterior) is a result of
- large amounts of water exiting the bath waste pipe when in
use
- further defects affecting the below ground waste pipes
Insurer’s expert (PB)
Report
6 June 2017
CCTV inspections of below ground drainage system found 1
x major misalignment affecting the drainage system at the
left - hand side of the dwelling in the direct area of all sighted
cracking and movement
Defect is allowing large amounts of water to exit during
rainfall activity
No issues were found in the sewer drainage system
Recommend the insured engages a qualified trades to carry
out rectificatio n to storm water drainage pipes
Insurer’s expert (IL)
Engineering report
11 October 2017
Purpose of inspection to ascert ain primary cause of reported
damage
Insured advised they first noticed minor cracking to the
external brickwork approx. 2 years ago, but it has become
significantly worse
Dwelling is double story timber frame construction with a
brick veneer
Founded on perimeter strip foundations and internal stumps
Noticed repairs have been made to construction joint
between extension and original dwel ling. Joint had visibly
opened between 10mm – 15mm, and repaired with silicone
Rotation of brickwork was also visible to window frame of the
study where a gap of approximately 10mm had formed
Determination | Case number: 522881 Page 9 of 12
Record Key points
Inspection of southern elevation als o showed movement and
rotati on between the window openings and brickwork. An
extensive amount of expandable filler was installed above
bedroom window in SW corner of dwelling.
Cracking to concrete lint el also observed to this window
Minor diagonal cracking along mortar joints also si ghted to
top of west facing wall of bedroom in west elevation
No other external effects were sighted or reported during
inspection
Internal inspection revealed cracking to caulking joints along
bathtub, and plasterboard and wall tiling to northern wall of
bathroom
Cracking to ceiling plaster above shower
Study to east of bathroom has long horizontal crack across
west wall and partially to north wall – 5mm in width
Minor cracking along cornice to fireplace flue
No other internal defects sighted or report ed d uring
inspection
Floor levels were slightly uneven throughout the entire
dwelling
Conclusion/ Summary
Subsidence and cracking local to the bathroom and study
areas has only been exacerbated by the water escape from
defective stormwater drain and bathtub wa ste drain (70%)
Initial movement and cracking to this area and elsewhere in the
dwelling can be attributed to combined effects of uncapped
perimeter soil, the prolonged drought period, and seasonal
movement of the reactive clay bearing strata (30% )
Insurer’s expert (JPF)
Cash Settlement SoW
18 October 2017
Study & Office
Bathroom
Recommended cash settlement (70% of overall damage) incl
GST & margins $3,733.93
Complainant’s expert
(RC)
Engineer report
28 February 2018
Property inspected on 28 February 2018
Cracks and gaps observed in walls internally and externally
Damage to front section of hous e is moderate to severe
Externally near the front NW corner there are signs of major
movements suggesting subsidence and pulling towards the
front (nor th and west)
Past plumbing problems were reported in the nort h side
towards the front
Some damage along the south wall
The extension is relatively free of damage
Preliminary investigations suggest the soil type is M
(moderately reactive)
Determination | Case number: 522881 Page 10 of 12
Record Key points
Damage Causes/Con clusions
Existing footings were not deep enough to cope wit h the
consequences of the past plumbing problems and the current
effects of tree root drying
The cause seems to be moisture instability resulting from past
plumbing leaks as well as cumulative move ment of the building
over many years
Main relative causes
Plumbing/drainage problems 60%
Trees and other site conditions 20%
Type of building construction including footings and
foundation soils 20%
Complainant’s expert (I)
Quotation
23 March 2018
Internal & external repairs including underpinning
$50,660.50
Insurer’s expert (IL)
Supplementary report
(email)
3 May 2018
Our report indicates that 70% of the damage has been
caused by defective drains, whereas Insured’s own engineer
has contributed onl y 60%
Our recommendations were specific in that the Insured needs
to fix all of the plumbing issues and allow for a 12 month
drying out period
Property can then be re - inspected to ascertain the exact SoW
At the time of our initial inspection the cracking internally was
not severe. Therefore since that time there has been further
cracking, either due to the drying of the soil (if drains are
fixed) or continual saturation of the soils (if drains are not
fixe d)
Insured’s expert has also highlighted further pre - existing
conditions and other factors that have contributed to the
foundation movement
Insured’s engineer has said that the footings are inadequate
– this has likely contributed to the previous cracks an d
repaired sections of the wall which we have acknowledged in
our report also
Insurer’s expert (IL)
Reattendance Report
26 June 2018
To attend site and comment on current state of damage post
6 month drying out period
Photographs taken of the cracking to the internal and external
walls show the cracks have increased in size
Floor levels have moved since our previous inspection
A large change in the floor level was recorded within the
bathroom with the NW corner subsiding another 15mm, and
SE corner raisin g by approximately 20mm
We also found new cracking to the hallway adjacent to the
Determination | Case number: 522881 Page 11 of 12
Record Key points
bathroom which was not present during our original
inspection
Also of note was water staining and damage to the plaster on
the western wall of the study. This wall backs onto the
shower recess which indicates there is a potential leak in the
shower which has been undetected
Insured has told us his plumber could not identify a leak to
the bathtub waste trap (as identified by PB 09.05.17)
Considering our original report identifi ed 70% of the damage
to be attribut able to the leaking stormwater drain and bathtub
drain, the percentage of the insurable contribution should be
adjusted accordingly as the bathtub was not leaking
Considering the further leaks, another drying out period a nd
further investigations will be required
Insurer’s expert (TB)
Leak detection report
25 July 2018
Confirmed that there are no visible defects to stormwater
drainage system
Confirmed that the shower base leaks
Shower base could not be tested as the wate r leaks out
faster than it can fill
The caulking near the rear wall/ base was detached – this is
most likely due to the building movement
Complainant’s expert
(RC)
Supplementary report
19 September 2018
Stormwater drain was repaired in November 2017
In February 2018 a leak in the shower was observed and the
silicon sealed
During March 2018 (insured) observed the damage appeared
to be stabilising
The focus of the damage and subsidence is toward the front
NW corner, where the past leaks were reported
My co nclusion was that the past leaks were assumed the
main cause of movement and damage to the building
The leaking stormwater drainage line caused movement in
the reactive clay soil
Any minor leaks such as the bath/ vanity would not have been
as significant as the stormwater leak
Any contributing factors such as trees or footings are likely to
be less significant than the stormwater leaks
If the stormwater leak had not occurred it is likely that the
other factors would not have been enough to cause major
movement/damage.
This makes apportioning percentages to various factors
difficult, however it is clear that the main factor is the leaking
stormwat er pipe
It is also likely that the minor factors occurred as a result of
the primary cause – that is, the mov ement caused by the
stormwat er drain leak caused some of the minor leaks such
Determination | Case number: 522881 Page 12 of 12
Record Key points
as the bath and shower base
Both the internal and external damage is relat ed to the same
primary cause, so all movement damage needs to be
included in the scope of necessary repa irs