Determination 522070
Condenser breakdown claim declined on exclusions
Summary
The complainants' dairy plant condenser broke down and the insurer declined the machinery breakdown claim as caused by corrosion or wear. AFCA ordered the insurer to cash settle the replacement cost with interest from 6 March 2018 to payment.
Once a prima facie breakdown claim was established the insurer had to prove an excluded proximate cause, and its own expert could not rule out impact damage from animals or birds.
Issues
- Claim denial primary · upheld“The insurer has not shown that, on the balance of probabilities, the damage which necessitated the replacement of the condenser was caused by factors which are excluded from cover.”
Subjects and remedies
small businesspay claimpay interest
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination | Case number: 522070 Page 1 of 7
Determination
Case number: 522070 20 December 2018
1 Determination overview
1.1 Complaint
The complainants lodged a claim under their farm insurance policy with the financial
firm (insurer) after the condenser on their dairy plant stopped working in November
2017.
The insurer denied the claim on the basis that the damage to the condenser was
caused by factors which are excluded from cover under the policy, s uch as wear and
tear, corrosion and gradual deterioration.
The complainants dispute the insurer’s decision and seek cover for the cost of
replacing the condenser.
1.2 Issues and key findings
Is the insurer liable for the damage to the condenser?
Based on the available information, the complainants have established a prima facie
claim under the policy for mechanical breakdown.
The insurer has not shown that, on the balance of probabilities, the damage which
necessitated the replacement of the condenser was caused by factors which are
excluded from cover under the policy.
1.3 Determination
This determination is in favour of the complainants.
The insurer is required to cash settle the complainants for the replacement cost of the
condenser, in accordance with the terms and conditions of the policy.
The insurer is to pay interest on the settlement amount at the rate calculated in
accordance with section 57 of the Insurance Contracts Act 1984 (Cth) (the Act) for the
period from 6 March 2018 until the payment date.
Determination | Case number: 522070 Page 2 of 7
2 Reasons for determination
2.1 Is the insurer liable for the damage to the condenser?
Complainants have established a prima facie claim for mechanical breakdown
The complainants are required to show that, on the balance of probabilities, they have
suffered a loss caused by a risk insured against under the policy. This is known as a
valid (or prima facie ) claim.
If the complainants are able to establish a valid claim, then the onus shifts to the
insurer to show that, on the balance of probabilities, it is entitled to rely on an
exclusion under the policy or is otherwise entitled to deny the claim.
The complainants’ policy provides cover for machinery breakdown of t he dairy plant.
For the purposes of the policy, ‘breakdown’ is defined to mean unforeseen and
unexpected physical damage to the machinery, which requires repair or replacement
to allow normal working to continue.
After the roof mounted condenser unit broke down on 30 November 2017, the
complainants’ refrigeration mechanic (MW ) identified a mechanical fault. MW noted
there was a refrigerant leak in the condenser coil and damage to the cooling fans.
Based on the available information, I am satisfied that the damage to the condenser
was unforeseen and unexpected (from the complainants’ perspective). Accordingly,
I am satisfied the complainants have established a prima facie claim for mechanical
breakdown under the policy.
Insurer says damage was caused by excluded factors
As the complainants have established a prima facie claim, the insurer bears the onus
of showing that, on the balance of probabilities, it is entitled to deny the claim based
on a policy exclusion.
The policy excludes cover for the replacement of machinery where parts wear out due
to ordinary use, gradual deterioration or corrosion. The insurer says this is how the
damage to the condenser occurred.
In order to be entitled to deny the claim, the insurer must show that the proximate
cause of the damage (that is, the real, effective or dominant cause) was one or more
of these excluded factors.
Consultants have provided differing views about cause of damage
After the complainants lodged their claim, the insurer sought information from the
complainants ’ refrigeration mechanic (MW) about the cause of the damage. However,
MW advised he was unable to provide any explanation.
Determination | Case number: 522070 Page 3 of 7
The insurer’s loss adjuster (JD of CL) reviewed photographs of the damaged
condenser and concluded that the damage had been caused by corrosion. JD
recommended that the claim be denied on that basis.
However, as the mechanic (MW) had been unable to identify the cause of damage,
the insurer decided to appoint a refrigeration specialist (CT) to inspect the condenser.
In his report, CT confirmed there was damage to the copper coil and aluminium fins
on the underside of the condenser unit. A section of the aluminium fins in the affected
area were missing, while the remaining fins had started to decay.
CT identified the following possible explanations for the missing fins:
the fins had become so brittle over time that they simply fell off
MW had removed the fins to try and locate the leak in the coil, or
the condenser had suffered physical damage – eg from an animal or bird.
Likewise, CT was unable to conclusively identify what had caused the condenser to
leak. He considered the leak could have been caused by:
physical damage to the coil (possibly sustained at the same time as the fins were
damaged)
a copper pipe having cracked or rubbed thro ugh the aluminium housing, due to
vibration of the motors or movement of liquid and gas inside the refrigeration
system, or
the copper having become pitted and porous due to the age and condition of the
unit.
Following the issue of the Recommendation by the FOS Case Manager, the insurer
arranged for its mechanical engineer (GC of CL) to carry out a desktop assessment of
the reports and photographs obtained during the course of the claim.
In his report, GC concluded that the proximate cause of the damage to the condenser
was the lack of adequate maintenance required to prevent the development of
corrosion.
GC advised that a lack of maintenance had allowed dust and debris to accumulate,
enabling the build-up of moisture on the fins and the copper piping of the coil and
resulting in corrosion. GC considered that the corrosion of the fins and the oxidation
of the copper piping had caused the condenser to break down in November 2017.
Information does not establish breakdown was caused by excluded factors
As outlined above, the insurer is required to show that, on the balance of probabilities,
the damage to the condenser was caused by excluded factors. In this context, it is the
Determination | Case number: 522070 Page 4 of 7
leak in the coil which is the most relevant, as this was the damage which caused the
unit to stop operating, necessitating its replacement.
Having carefully reviewed the available information, I am not satisfied the insurer has
established that the damage to the coil was caused by excluded factors.
While it is apparent that there is corrosion damage to the condenser, it is not clear
that this damage was the cause of the break down in November 2017.
As outlined above, the refrigeration specialist (CT) appointed by the insurer concluded
that the damage could have been caused by any one of several factors. These factors
included impact from animals or birds, which is not excluded from cover under the
policy.
The insurer’s loss adjuster (CL) interpreted CT’s report (and their subsequent
discussions) as establishing that corrosion was the only cause of damage that was
supported by the physical evidence. Accordingly, CL treated CT’s findings as
supporting his own initial assessment.
However, in a subsequent email, CT disagreed that corrosion was the only possible
explanation for the damage (to either the fins or the coil). CT reconfirmed his earlier
view that this damage could also have been caused by animals or birds.
The insurer’s engineer (GC of CL) considered that the area of missing fins in t he
damaged section of the coil indicated that the corrosion was more advanced in this
area.
However, the more severe, localised damage to the fins is also consistent with this
damage having been caused by impact (which may have also damaged the coil, as
noted by CT).
Both JD and GC advised it was unlikely that the condenser had been damaged by
animals or birds. JD stated that the unit was not readily accessible because it was
mounted on the roof. GC considered that, had the damage been caused by animals,
there would have been large areas of flattened fins.
However, photographs of the condenser in situ on the roof indicate that the underside
would have been exposed to damage from birds and/or smaller animals (such as the
rats, possums and feral cats that the complainants have advised inhabit the area).
Given CT considered impact from animals or birds to be a plausible cause of the
damage, I am not satisfied the insurer has shown that the damage was caused by
other factors. CT was appointed by the insurer and was the only one of its consultant
to physically inspect the condenser.
Determination | Case number: 522070 Page 5 of 7
Insurer is liable for replacement of condenser
For the reasons outlined above, the insurer is not entitled to rely on the policy
exclusion for parts wearing out due to gradual deterioration, wear and tear or
corrosion.
In its submissions, the insurer has said it was prejudiced by the complainants
engaging MW to inspect (and replace) the condenser prior to lodging their claim.
However, the policy provides that the usual restriction on replacing damaged
machinery without the insurer’s consent does not apply where immediate action is
required in order to prevent further loss.
I am satisfied that the complainants acted reasonably in replacing the condenser,
given it was required to operate their business effectively. The complainants have
advised that they lodged the claim once they had received the supporting information
from their repairer (MW).
Further, the complainants stored the damaged condenser at their property and made
it ava ilable to the insurer’s consultants for inspection.
The insurer has also suggested that the condenser only needed to be replaced
(rather than repaired) due to the extent of the pre-existing corrosion.
However, it appears that the condenser was fully operational prior to breaking down in
November 2017. Further, the insurer has not provided any estimate of the cost of
repairs (assuming its liability were to be limited to that amount), but instead has
sought to deny the claim entirely.
In these circumstances, I consider the insurer should be required to cash settle the
complainants for the replacement cost of the condenser, in accordance with the terms
and conditions of the policy.
The insurer is to pay interest on the settlement amount at the rate calculated in
accordance with section 57 of the Act for the period from 6 March 2018 until the
payment date.
Determination | Case number: 522070 Page 6 of 7
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with F inancial O mbudsman S ervice (FOS) .
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
claim claim
3.2 Our approach to this complaint
This complaint was the subject of a recommendation issued on 26 September 2018.
The recommendation was rejected by the insurer.
This complaint has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other. All of the material provided by the parties has been reviewed and
considered.
During the course of this dispute, the complainants have been represented by their
broker. For the purposes of this determination, submissions made by the broker have
been treated as if they had bene made by the complainants themselves.
3.3 Key policy terms
Subject Terms
Cover for When we will pay
Determination | Case number: 522070 Page 7 of 7
Subject Terms
Machinery
Breakdown We will pay for destruction, loss or damage to the following property shown in
the Schedule and while at the Situation:
The costs of repair following the Breakdown of Electrical Machinery, Electronic
Equipment, Mechanical Machinery and Specified Items listed in the Schedule
under Machinery Breakdown at the Situation and … where working or at rest
…
Breakdown means unfores een and unexpected physical destruction or damage
to the machinery or Electronic Equipment specified on Your Schedule, which
needs repair or replacement to allow normal working to continue.
Exclusions When we will not pay
We will not pay for claims for the following: …
Repair or replacement
Repair or replacement necessitated by:
wasting or wearing out of parts, caused by or resulting from ordinary use of
working or gradual deterioration, corrosion …
replacement of expendable items including but not limited to … electric
heating elements …
repairs to va lves, fittings, glands, joints, gaskets, pi pes, lines and connections
which are defective, wor n or leaking …
Obligations of
insured
What you must not do when you make a claim
You must not do an y of the following:
repair or replace any damaged property without Our cons ent, unless the repair
is to prevent further loss …
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.