Text of the determination
Determination | Case number: 519338 Page 1 of 19
Determination
Case number: 519338 30 January 2019
1 Determination overview
1.1 Complaint
The complainant lodged a claim with the financial firm (insurer) under her landlord
insurance policy for water and cracking damage to her home. She says this damage
was caused by a leaking pipe (escape of liquid).
Mould was identified at the property and the insurer has completed removal and
decontamination of this, the complainant is happy with this outcome and the mould
will not be considered further in this determination.
Both parties have provided multiple engineers reports and several areas of damage
have been identified, these are:
foundation movement
internal cracking and water damage
separation of the roof trusses.
The complaint also seeks further loss of rent payments.
The insurer says:
its liability for the internal cracking and water damage is limited to the amount in the
scope of works ($16,402.32)
it is not liable for further loss of rent
the roof trusses are not covered.
1.2 Issues and key findings
Is the insurer liable for the water damage and foundation movement?
On the balance of probabilities, there are two proximate causes of the foundation
movement:
escape of liquid
ground movement.
Determination | Case number: 519338 Page 2 of 19
Escape of liquid is covered by the policy whilst ground movement is not.
It is fair in all the circumstances for the insurer to contribute 20% of the cost of
rectifying the foundation slab movement and $4,000 to the cost of repairing the
internal cracking damage. The insurer should also pay the complaint $20,000 for the
water damage caused by the escape of liquid.
Is the insurer liable for the damage to the roof trusses?
On the balance of probabilities, the damage to the roof trusses was caused by
mechano-sorptive back-out. I am satisfied mechano-sorptive back-out is gradual
deterioration for the purposes of the policy. The policy excludes gradual deterioration.
Therefore, the insurer is entitled to deny the damage to the roof trusses.
Is the complainant entitled to any further amounts?
I am not satisfied the complainant has suffered additional stress and inconvenience
due to the actions of the insurer during the claim. I am also not satisfied the insurer‟s
management of the claim was unreasonable in the circumstances.
Accordingly, I am not satisfied the complaint is entitled to any compensation.
The complaint is however entitled to 8 weeks further loss of rent and reimbursement
for the cost of the reports she obtained up to $3,000 in total.
1.3 Determination
This determination is partially in favour of the insurer and partially in favour of the
complainant.
The insurer is required to:
contribute 20% towards the cost of rectifying the foundation slab movement
pay the complaint $24,000 for the water damage caused by the escape of liquid
and the internal cracking damage
pay a further 8 weeks loss of rent
reimburse the complainant for the cost of the reports she obtained up to the total
sum of $3,000, subject to the complainant providing invoices and proof of payment
for the fees.
The insurer is entitled to deny the damage to the roof trusses and is not required to
pay any compensation or other amounts.
Determination | Case number: 519338 Page 3 of 19
2 Reasons for determination
2.1 Is the insurer liable for the water damage and foundation movement?
Complainant must establish a valid claim
The complainant is required to show, on the balance of probabilities, she has suffered
a loss caused by a risk insured against under the policy.
This is known as a prima facie claim.
Once the complainant establishes a prima facie claim, the insurer is liable for the loss
unless it shows an exclusion applies. The insurer has the onus of proof in establishing
the application of the exclusion.
The complainants‟ policy provides cover for „Escape of liquid‟.
The parties accept there was a damaged pipe in the wall behind the bath which
caused an escape of liquid each time the bath was used. They also accept this
caused damage to the kitchen, bathroom, hallway, and toilet areas of the house.
Extent of damage covered by the policy is not agreed
The parties disagree about the extent of the damage covered by the policy. Broadly
the damage can be broken into three areas:
Water and cracking damage to internal areas
foundation movement
separation of the roof trusses.
As above, the parties agree the water damage to the kitchen, bathroom, hallway, and
toilet is covered by the policy.
The insurer says the remaining damage is not covered by the policy.
Parties agreed to appoint further engineer
When this complaint was first lodged with the predecessor scheme to AFCA (the
F inancial O mbudsman S ervice (FOS) ) the insurer offered to arrange soil testing and
another engineer to provide a final a scope o f works.
The complainant agreed to this and the engineer (FE) inspected the property on 14
May 2018 and provided its report on 24 August 2018.
Foundation movement caused by water leak and ground movement
The various experts who inspected the property identified a hole in the foundations
under the bath. They agreed this allowed water from the pipe leak to go under the
property.
Determination | Case number: 519338 Page 4 of 19
The complainant engaged a building consultant (AA) to assess the property. AA said:
Water discharging from bath tap breach has entered founding soils under the home
via a recess formed in the concrete slab. This may be a significant contributing factor
resulting in structural movement as evidenced by extent of damages to internal linings
in proximity of Bathroom
In relation to the foundation movement FE says:
settlement of the house has been occurring since construction due to the
consolidation of inadequately compacted fill under the slab and the recent leak has
amplified this consolidation and consolidated an unconfirmed up to 50mm thick
layer of sand blinding
the lack of heave after the addition of water to the soil indicates inadequate initial
compaction of founding soils if sand blinding is not present
the leak from the bath tap has consolidated the unconfirmed presence of up to
50mm of sand blinding under the slab since construction but has not been
significant enough to heave the foundation soil
the settlement has occurred due to the gradual consolidation of inadequately
compacted fill and possibly the consolidation of up to 50mm of sand blinding solely
because of the infrequent addition of moisture which has increased significantly
with the change of tenancy in 2015.
The complainant‟s building consultant (AA) says cracking had been noted to the
property within three months of completion of construction as noted on the three-
month defect form. He also recommended an engineer be engaged to determine the
cause of the cracking.
The complainant engaged an engineer (FM) to provide a report. FM concluded a
water leak has likely caused the movement of the slab. However, FM‟s report is only
three pages long and does not provide detailed discussion on how the conclusion was
reached.
Overall, I am more persuaded by the report provided by FE.
The complainant must show, on the balance of probabilities, the proximate cause of
the damage (that is, the real, effective or dominant cause) is covered by the policy, in
this case an escape of liquid.
It is well established at law that the proximate cause of a loss is not necessarily the
first (or the last) or the sole cause of the loss. It is the effective or dominant or
operative cause.
In any particular case, the proximate cause of the loss is a question of fact to be
determined based on the surrounding circumstances. Where there are several causes
Determination | Case number: 519338 Page 5 of 19
operating, each must be examined for the qualities of predominance and efficacy in
relation to the resultant damage.
Having considered the information provided, I am satisfied, on the balance of
probabilities, the escape of liquid has caused foundation movement. This proximate
cause is covered by the policy.
However, I am also satisfied, on the balance of probabilities, ground movement as
described by FE has caused foundation movement. Damage caused by ground
movement is not a listed event under the policy and is also excluded by the policy.
Therefore, this proximate cause is not covered by the policy.
Two proximate causes are independent of each other
The two proximate causes (escape of liquid and ground movement) are independent
of each other. That is, one did not cause or contribute to the other. They are also both
capable of causing foundation movement in the absence of the other.
In situations where there are two independent proximate causes operating
concurrently and one is insured, while the other is not, the portion of the claimed
damage caused by the insured cause is covered whilst the rest of the damage is not.
Insurer is liable for all water damage
The insurer has agreed it is liable for the water damage to the kitchen, bathroom,
hallway, and toilet.
The insurer has provided a scope of works and quote totalling $16,402.32 for the
repair of the water damage it agrees it is liable for.
The complainant has provided two scopes of works and quotes totalling $77,658.95
and $83,787. These quotes appear to include repair of the cracking damage to the
property as well as the water damage. They do not separate the costs out so it is not
possible to say how much of each quote is for the water damage.
I have considered the three quotes and after making allowance for:
the possibility of variations and other unknown costs
interest
the cost to the complainant of undertaking the repairs, given her lack of access to
the volume discounts and rebates provided by the insurer‟s contractors
the additional risks assumed by the complainant due to the absence of any repair
guarantee.
I consider it fair in all the circumstances for the insurer to cash settle the complainant
$20,000 for the water damage caused by the escape of liquid.
Determination | Case number: 519338 Page 6 of 19
It is fair for the Insurer to contribute to foundation and cracking repairs
The insurer‟s first expert IL said the water leak increased the cracking damage and
foundation movement by about 20%. However, FE says it is not possible to apportion
the damage between the two causes.
As above, I am satisfied some of the foundation movement is covered by the policy.
Having considered the information provided, I am satisfied it is fair in all the
circumstances for the insurer to contribute 20% of the cost of rectifying the foundation
slab movement. For the avoidance of doubt this also includes required professional
fees such as engineers.
The insurer should also contribute towards the cost of repairing the internal cracking
damage as this was contributed to by the foundation movement. This work will most
likely be completed at the same time as the water damage which will make it difficult
to separate out from the water damage. Therefore, I do not consider it appropriate for
the insurer to contribute a percentage instead, I am satisfied it is fair in all the
circumstances for the insurer to contribute $4,000 towards the cost of repairing the
cracking damage.
2.2 Is the insurer liable for the damage to the roof trusses?
Insurer says roof truss damage is excluded
The insurer says the damage to the roof trusses was not caused by the foundation
movement but instead by a process known as mechano-sorptive back-out. The
insurer says mechano-sorptive back-out is excluded as it is gradual deterioration and
refers to IL‟s report date d 25 October 2017.
IL describes mechano-sorptive back-out as a long term process caused by the
repeated swelling and shrinking of the wood due to moisture level changes in the roof
space. IL says the damage to the roof trusses was caused by mechano-sorptive
back-out.
I am satisfied, on the balance of probabilities, mechano-sorptive back-out is a gradual
process and is gradual deterioration for the purpose of the policy.
The question therefore, is whether the proximate cause of the roof truss damage is
mechano-sorptive back-out or some other cause.
The complainant says the damage is caused by the foundation movement and refers
to FM‟s report of 2 February 2018.
Cause of roof truss damage is excluded
In its report of 2 February 2018 FM says the damage to the roof trusses could be
caused by:
Determination | Case number: 519338 Page 7 of 19
foundation movement
fluctuation in moisture levels in the roof space
poor timber properties.
FM also says it could be a combination of all three causes.
Other than the foundation movement the causes of the roof truss damage listed by
FM is consistent with IL‟s description of mechano-sorptive back-out. FM says the roof
truss damage is likely due to the foundation movement but in the next sentence says
it could also be due to moisture levels and low material strength.
Having considered the two reports, FM‟s lack of a definitive conclusion, and the other
information provided, I am more persuaded by IL‟s report. I am therefore satisfied, on
the balance of probabilities, the damage to the roof trusses was caused by mechano-
sorptive back-out.
As above, I am satisfied mechano-sorptive back-out is gradual deterioration for the
purposes of the policy. The policy excludes gradual deterioration. Therefore, the
insurer is entitled to deny the damage to the roof trusses.
2.3 Is the complainant entitled to any further amounts?
Complainant is not entitled to compensation
Under paragraph 9.3 of the FOS Terms of Reference (TOR), we may award
compensation for non-financial loss (capped at $3,000) where there has been an
unusual amount of:
physical inconvenience
time taken to resolve the situation
interference with the complainant‟s expectation of enjoyment or peace of mind.
We take a conservative approach to compensation and expect a complainant to bear
a normal degree of inconvenience during a claim.
Under the TOR, a complaint may also be awarded compensation (capped at $3,500)
for indirect financial (consequential) loss incurred in connection with their claim.
The claim which is the subject of this complaint is complex in nature and multiple
experts were required to determine the nature and extent of the damage, and the
cause of the damage.
In this case, I can appreciate the complainant has had the worry and inconvenience of
the mould and other matters which gave rise to their claims as well as the
inconvenience of a claim denial and having to bring a complaint.
Determination | Case number: 519338 Page 8 of 19
As outlined above, the parties agreed to appoint an engineer in May 2018. I
acknowledge it took over three months from when the engineer inspected the
property until the report was provided to the insurer. However, this report included
both structural and geotechnical investigation. I am not satisfied three months is too
long given the nature of the claim and damage.
Overall, I am not satisfied the complainant has suffered additional stress and
inconvenience due to the actions of the insurer during the claim. I am also not
satisfied the insurer‟s management of the claim was unreasonable in the
circumstances.
In the circumstances, I am not satisfied the complaint is entitled to any compensation.
Complainant is entitled to further loss of rent
The policy provides cover for loss of rent following an insured event. This cover is
limited to the lesser of 52 weeks or 20% of the property sum insured.
The insurer has paid loss of rent from 30 October 2017 until 1 November 2018. This
is the full amount payable under the policy.
As above, I am not satisfied the insurer‟s management of the claim was unreasonable
in the circumstances. However, I am satisfied the insurer‟s actions have increased the
time taken to resolve the situation.
Accordingly, I am satisfied the complainant is entitled to 8 weeks further loss of rent.
Complainant is entitled to reimbursement of fees
The complainant seeks reimbursement of fees paid to their building consultant (AA)
and engineer (FM) for inspecting the property and preparing their reports.
Under the TOR, we may require and insurer to reimburse legal or professional fees
incurred by a complainant in connection with their complaint.
I am satisfied the information provided in AA and FM‟s reports was of limited
assistance in making this determination. In these circumstances, the insurer is
required to reimburse the complainants professional fees to the sum $3,000 in total,
subject to the complainant providing invoices and proof of payment for the fees.
Determination | Case number: 519338 Page 9 of 19
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has comme nced managing
disputes previously lodged with F inancial O mbudsman S ervice (FOS) .
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applicant complainant
financial services provider financial firm
dispute complaint
3.1 Our approach to this complaint
We have considered it appropriate to expedite this complaint in accordance with the
Operational Guidelines to the FOS Terms of Reference, due to the nature of the
complaint. Accordingly, this complaint has not been the subject of a preliminary
assessment and has proceeded directly to determination.
This complaint has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other. All of the material provided by the parties has been reviewed and
considered.
3.2 Proximate cause
Case law establishes:
the proximate cause of loss is the dominant (or effective or operative) cause of the
loss, whether or not the cause is last in time or the sole cause.
where several causes operate at the same time, each cause must be examined for
the qualities of reality, predominance and efficiency as the active, efficient cause
that sets a relevant chain of events in action.
Determination | Case number: 519338 Page 10 of 19
If one cause results in harm in any case, and the other would not in the absence of
the first, the first is the proximate cause.
a common-sense approach is taken to determine proximate cause.
3.3 Relevant policy wording
Subject Terms
Glossary of important words
and phrase s
Loss or damage
means physical loss or physical damage.
What you are covered for –
Insured events
… we cover your property for loss or damage at the insured address
caused by an ins ured event during the period of insurance.
There are some things we do not cover and these are shown in the
„We do not cover‟ section of the following tables on pages 26 to 40
and in the „General exclusions‟ on pages 61 to 67.
Escape of liquid
We cover
Loss or damage caused by liquid leaking, overflowing or bursting
from any of the following:
…
• any drain, fixed pipes, roof gutters or guttering and rainwat er
d ownpipes, drainage and sewage systems (not forming part of a
shower cubicle wall, floor or base);
…
• baths, sinks, toilets and basins (but not showers);
…
We do not cover
…
• broken, worn or aged tiles or grouting in walls in bat hrooms,
kitchens or laundries unless the damage is caused by liquid leaking
from pipes in walls or floors (but not forming part of a shower cubicle
wall, floor or bas e);
Additional features Additional features
If we accept your claim for loss or damage due to an insured event,
we will also provide the following additional features. The additional
features and their limits are paid in addition to the cover provided
under your property and/ or contents insurance.
…
Loss of rent following an insured event
We cover
When you have property cover
If we accept your claim for loss or damage to your property due to
an insured event occurring during the period of insurance and we
agree it cannot be lived in, we will pay the weekly rental amount for
the reasonable amount of time we d ecide it should take to
repair or rebuild the property so it can be lived in again.
…
Limit
The longest period we will provide cover for is 52 weeks and the
most we will pay under the feat ure is the great er of:
• 20% of the property sum insured if you have property cover …
Determination | Case number: 519338 Page 11 of 19
Subject Terms
General exclusions You are not covered under any section of this policy for damage,
loss, cost or legal liability that is caused by, arises from or involves:
…
Consequential losse s or extra costs following an incident
covered by your policy
consequential loss (financial and non - financial loss) or extra costs
following an incident covered by your policy, such as:
• loss of rent except as expressly covered by this PDS;
…
• loss or costs, including the cost of your time (e.g. inconvenienc e) to
prove your loss or to help us with your claim (e.g. telephone calls,
postage);
…
• professional, expert, legal, consulting or valuation costs unless you
obtained our prior written authority to incur these costs;
…
• any costs related to stress or anx iety;
• any costs not covered by your policy.
…
Ground movement
erosion, vibration, subsidence, landslip, landslide, mudslide,
collapse, shrinkage or any other earth movement, but we will cover
landslide or subsidence that is specifically covered under the
following insured events:
• „Storm‟;
• „Flood‟;
• „Earthquak e and tsunami‟;
• „Explosion‟.
…
Wear, tear, mould, gradual deterioration and other conditions
wear, tear, rust, fading, rising damp, mould, mildew, corrosion, rot,
action of light, atmospheric o r climatic conditions or gradual
deterioration such as, but not limited to:
• tiles and their adhesive or grouting breaking down;
• weathering of roof tiles or roof ridge capping;
• gradual weathering and breakdown of bricks, mortar or concret e.
3.4 Expert reports
Record Key points
Complainant’s expert ( A A )
Report
27 July 2017
4. Conclusion
All evidence available at time of inspection suggests as follows:
The home has sustained damages resulting from structural
movement as evidenced by:
> Fracturing to plaster wall and ceiling linings
> Misalignment of doors within their frames
> Deviations within floor heights
Vast majority of structural movement had occurred in proximity to
centre of the home and where bath waste was located.
Structural m ovement had been occurring to the home for an
extended duration and in all probability since the home was
completed. This is evidenced by information contained wit hin the
„Three Mont h Defects Form‟ provided by the original building
Determination | Case number: 519338 Page 12 of 19
Record Key points
contractor and filled in by [complainant] on 12 June 2008 which
makes reference to “Small cracks in Kitchen ceiling‟ (Refer
Appendix A).
Structural movement had significantly increased in severity in
recent years. This is evidenced by information contained within
emails sent to the original building contractor during notification of
fractures to Kitchen ceiling in September 2016 which also makes
reference to fractures which existed in Dec ember 2015 (Refer
Appendix B).
Water was found to be leaking from a breach contained within a
wall cavity adjoining North side of Bath recess with South side of
adjacent Kitchen. This is evidenced by photographs and plumbing
report provided to the writer (Refer Appendix C).
Extent of damage resulting from water discharging from the
breach could not be categorically determined however latent
damages will in all probability extend into nearby wall cavities and
cabinetry resulting in extensive repairs to be undertaken.
Water discharging from bat h tap breach has entered founding soils
under the home via a recess formed in the concrete slab. This
may be a significant contributing factor resulting in structural
movement as evidenced by extent of damages to internal linings in
proximity of Bathroom (Refer sections 3.1 to 3.4).
5. Recommendations
The w riter recommends the following courses of action:
A thorough structural assessment is undertaken to establish cause
of structural movement including removal of Bath and inspecting
recess and if possible soils under the home.
Further mould assessment is undertaken to establish a protocol
for undert aking remediation processes.
After remediation is complete and post remediation verification
certificate provided, a scope of works document is compiled for the
purposes of returning the property to a pre - event condition.
financial firm ’s expert ( IL )
Report
6 October 2017
4.0 Conclusion
4.1 Cause of damage
Based on the visual inspection and information obt ained to date,
we confirm the movement and cracking to the dwelling has been
exacerbated by a leaking water pipe in the bat hroom. However,
initial movement and cracking to this area can be attributed to the
on - going and pre - existing subsoil conditions of the highly reactive
clay soils. Cracking in the kitchen identified in the three month
defect form confirms movement has been an ongoing issue for the
life of the structure as similar cracks local to the area were sight ed
again by the tenant upon moving in during December 2015. The
on - going and long term movement may have also contributed in
the shower breach cracking and leaking.
Clay soil is notoriously reactive to an increase in moisture content,
and can either compress (due to attainment of the plastic limit and
weight of structure above) or expand (depending on the formation
and type of clay). Based on the cracks recorded it is evident that
Determination | Case number: 519338 Page 13 of 19
Record Key points
the dwelling is exhibiting cracks local to areas wit hin proximit y of
the leak. This is also evident with the movement recorded local to
the central area of the dwelling where floor level measurements
indicate that the highest footing subsidence has occurred within
this area. The localised nature of the damage would sug gest that
natural seasonal movement in conjunction wit h a leaking wat er
pipe has exacerbated the subsidence and as a res ult caused
cracking.
Based on our loc al knowledge of soils in this area typically have
the classification of Class H, highly reactive cl ay site. Class H soil
is a highly reactive clayey soil that between wet and dry soil
moisture conditions can produce very high ground movement of
between 40 - 60mm of vertical movement. Movement and cracking
cannot be entirely prevented in the State of Victo ria and this is
evident by initial movement and cracking documented in the Three
Month Defect Form.
4.2 Expected Movement
Referencing AS 2870 - 2011 Residential Slabs and footings clause
B3 Performance of walls states:
It is acknowledged that minor foundatio n movements occur on
nearly all sites and that it is impracticable to design a footing
system that will protect the building from movement under all
circumstances. The expected performance of footing systems
designed in accordance with the Standard is defi ned in terms of
the damage classifications in Table C1. (See table in the
recommendations of this report)
Crack width is used as the major criterion for damage assessment,
although tilting and twisting distortions can also influence the
assessment. For mos t situations Category 0 or 1 should be the
limit; however, under reactive soil conditions, Cat egory 1 & 2
should be expected with a rare chance of category 3 damage.
(Refer to table 2.2)
It should be noted in this case that the overwhelming majority of
cra cks would be classified as category 1 to 2, very slight to slight
and such cracks would be considered normal on all reactive sites
across Victoria.
5.0 Summary
5.1 Is the leaking water pipe the primary cause of damage?
We confirm the movement and cracking to the dwelling has been
exacerbated by a leaking water pipe in the bat hroom. (20%)
However, initial movement and cracking to this area can be
attributed to the on - going and pre - existing subsoil conditions of the
highly reactive clay soils. (80%)
Cracking in the kitchen identified in the three month defect form
confirms movement has been an ongoing issue for the life of the
structure as similar cracks local to the area were sighted again by
the tenant upon moving in during December 2015. The on - going
and lo ng term movement may have also cont ribut ed in the shower
breach cracking and leaking.
Determination | Case number: 519338 Page 14 of 19
Record Key points
financial firm ’s expert ( IL )
Report
25 October 2017
Access to the roof truss structure was provided through a personal
access chamber in the laundry ceiling. Our inspection identified
several issues and concerns with the roof trusses that are not
structurally adequate in their current condition.
As observe d on site, several connections along the truss apex
have partially or completely disconnected from the truss member
causing the top chords or the truss and webs to be separated. In
the locations were the gang nail plates have completely
disconnected the we bs and bottom chords of the trusses have
dropped and are now supported on the internal walls.
Based on the visual inspection and all the information obtained to
date we can confirm that this failure mechanism has not been
caused by the leaking water pipe in the bathroom, but instead by a
process called mechano - sorptive back - out.
Mechano - sorptive back - out has been occurring in Australian roof
trusses for several decades. This process involves the long term
repeated swelling and shrinkage of the wood under
moisture/humidity variations in the roof space that causes the nail
plates to be forced out of the timber. It is highly probable that the
timber used in the manufacturing of the trusses in this instant were
green (with a high moisture content) at the time of construction.
The variations in moisture/humidity are also increased by a lack of
roof sarking, which allows air and therefore humidity exchange in
the roof spac e. During inspection it was noted that the roof framing
structure has been installed wit hout the implementation of sarking.
This has a significant effect on roof structures as the timber
framed truss is more susceptible to moisture exposure.
Furthermore, the separation of the nail plat e connections from
their timber truss members can be also be attributed to several
other factors but not limited:
> Lateral movement along the truss joints during handling,
transport and installation.
> Overloading due to implementing additional loads on the
members
> Poor manufacturing when installing the nail plates.
Due to the failure in connections at the apex the trusses are
currently not performing as intended and if left unchecked can
potentially lead to the collapse of the roof structure. For this
reason, urgent make safe works will be required until permanent
re pairs can take plac e.
Qualified and experienc ed contractors must be used to temporally
prop the bottom chords of the trusses in all locations where there
is no internal wall.
Once the roof trusses have been propped all failed gang nail
plates are to be reinstalled as per manufactures specifications.
Where the webs and bottom chords of the trusses have dropped
down from the top chord at the apex, these members will need to
be jacked back up flush before fixing a new gang nail plat e.
Determination | Case number: 519338 Page 15 of 19
Record Key points
Complainant’s expert ( FM )
Report
2 February 2018
3. Engineering perspective
The „A‟ type trusses observed over the mid - section of the dwelling
have deformed due to either movement of the ground slab,
fluctuations in the moisture levels in the roof space, poor timber
propertie s or a combination thereof. It is recommended that a
complete audit of all the roof trusses be undertaken with all
defects (nail plat e movement and inter panel deflection) identified.
Material property should also be verified as at least MGP10 grade.
A rem edial work procedure consisting of nail plate fixing and
strengthening truss chords should be undertaken on the affected
areas.
Complainant’s expert ( FM )
Report
16 April 2018
It is likely that the dwelling is likely to continue experiencing
seasonal movement due to the ground slab beams founding on
clay fill material. The geotechnical investigation specifies a site
movement in the order of 40mm. D amage associated with the
movem ent is likely less severe that the existing damage due to
water leak because movement will likely occur over a larger
distance.
financial firm ’s expert ( FE )
Report
24 August 2018
3.0 Investigation
Site Observations
3.5 Roof Space
> The bracing to the roof trusses is incomplete.
Floor Level Survey Results
3.8 In May 2018 the floor levels varied from - 32mm to +16mm
relative to the datum, giving a total variance in levels across the
entire floor of 48mm. There is an area of settlement located to the
centre of the house.
3.9 In August 2018 the floor levels varied from - 32mm to +22
relative to the datum, giving a total variance in levels across the
entire floor of 54mm. Essentially the general pattern and
magnitude of variance in the floor levels was largely iden tical.
Differences being lower levels recorded in the ens uite to the main
bedroom and a higher level recorded at the northeast corner of the
house.
Site Geology and Foundation Soil Reactivity
3.10 FE carried out a Geot echnical Site investigation of the sub ject
site on 14 th May 2018 which included:
> The excavation of 2 boreholes to depths of 2m
> The collection of 4 soil samples at 0.5m intervals from each
borehole for moisture content and soil suction testing.
3.12 FE have classified the site as a Problem Site (i.e. class P in
accordance with AS2870 - 2011) due to the presence of
trees/shrubs on the site, adjacent sites and the street frontage and
due to an existing building on the site. In the absence of these
adverse site and building factors, the soil reactivi ty at the site has
been assessed to be Highly Reactive (i.e. class H2 level of
reactivity in accordance with AS2870 - 2011).
3.14 In addition, the Australian Standard AS2870 – 2011
Determination | Case number: 519338 Page 16 of 19
Record Key points
Residential slabs and footings enables assessment of the
foundation soils at a given site by identification of the mapped soil
profile without taking sit e specific soil samples. FE has also
undertaken the following for the subject site:
> Review of the Geological Survey of Victoria maps. These maps
indicate that the subject site is loc ated within the province of
Quaternary Aged Basaltic deposits. Referring to the AS2870 –
2011, Table D1, it is known that this soil profile is reactive.
> Review of the Climatic Zone maps provided in AS2870 – 2011
Figures D1 and D2. These maps indicate that the subject site is
located within Climatic Zone 3. Therefore, referring to AS2870 –
2011 Table 2.5, the depth of soil suction (i.e. the depth of soil
affected by normal climatic moisture variations) for the subject
site is expected to be 2.3m.
3.16 When buildin gs are founded on reactive clay soils, differential
variations in the foundation soil moisture content can result in
building movement related damage i.e. if the moisture content
increases th e clay soils tend to swell resulting in “ heave ” of the
building f ootings, and if the moisture content decreases the clay
soils tend to shrink resulting in “ settlement ” of the building footings.
3.20 In addition to th e classification of the site FE notes the
following obs ervations made during the Geotechnical
Investigati on:
> FE encountered fill to a depth of 400mm at borehole 1 at the
re - entrant corner between the garage and the bathroom.
> Moisture content of the soils were generally higher and soil
suction levels less at BH1 than those at BH2.
> Moisture content values at BH1 diminished with depth (soil
suction values increased).
> Moisture content values at BH2 inc reased with depth (soil
suction values decreased).
3.21 The above measurements indicate that either the moisture
content of the soils in close proximity to the bat hroom (BH1) have
increased as a result of the leak or that the soils at the northeast
corner of the site have decreas ed in the upper 1m of the borehole
due to small shrubs near BH2.
4.0 Di scussion
4.1 F E attended the subject site on the 1 4 th May 2018.
Observations during this initial inspection confirm that the cracking
damage to the int ernal plaster finishes and gaps between the
kitchen furniture and the walls has been caused by the settlement
of the central area of the floor slab. The settlement of th e cent ral
area of the floor slab and poor detailing of the connection bet ween
the non - load bearing walls and the roof trusses has primarily
caused the damage to the roof trusses, possibly with the
assistance of mechano - absorptive back - out in the un - sarked roof
space.
4.2 The absence of movement associated damage to the external
walls of the house indicates that the lower level to the cent re of the
floor has not been caused by a perimeter heave to the footing
Determination | Case number: 519338 Page 17 of 19
Record Key points
despite site conditions which are generally not ed to be conducive
to slab edge heave.
4.5 A cavity has been broken out of the bathroom and kitchen floor
slab as an after - thought to install the waste pipe under the shower
and connect the shower waste to a waste pipe from the kitchen
sink in the central i sland. The cavity has partially cut through a rib
in the waffle - pod slab and the polystyrene void formers to the
north and south of this rib in the bat hroom and kitchen. The cavity
has been filled with sand and screeded over on the kitchen side of
the wall but not on the bathroom side of the wall where the cavity
and sand have been covered by a proprietary shower tray.
4.6 Water from the leak in the breach of the bath tap could readily
track under the bath through the sand in the cavity and to the
upper sid e of the vapour barrier via the damaged void formers
where the water is expected to find its way below the vapour
barrier and into the ground under the slab.
4.8 F E also poured approximately 3 litres of water into the recess
under the bath which the Owner ‟ s Representative initially believed
was the cause of water entering under the footing slab. The water
level initially dropped 10mm but then remained relatively constant
with small bubbles observed in the water. It would appear the
initial drop in level was attributable to porosity in the upper level of
the concrete but the continued bubbling would suggest that some
water was tracking through the slab at this location. Tide marks on
the bath waste pipe observed in photographs by others indicat e
that this rec ess would readily fill due to the leak from the beach
and that the predominant source of water under the slab was the
„ broken out ‟ sand filled cavity created after the constriction of the
slab.
4.9 As noted above, when the moisture content of highly reactive
natural foundation soils is elevated the soils swell and expand
resulting in a heave to the footings. The same reaction also occurs
in well compacted reactive fill which oft en swells to a larger extent
than the natural soils due to its pre - disturb ed nature. It is highly
unlikely that an intermittent leak from the breach of the bath tap
(whic h only leaks when the tap is running) would supply enough
water to saturate the founding soils to the point of collapse.
4.11 All parties report that the damage associated with the
settlement to the central area of the house commenced
immediat ely after the construction of the hous e but was then
observed to accelerate after a new tenancy started in 2015, in
which the bath was used more frequently, before a leak wa s
discovered in 2017. This timeframe suggests:
> The settlement of the central area of the house has been
occurring since construction due to the consolidation of
inadequately compacted fill under the slab and the recent leak
has amplified this consolidation and also consolidated an
unconfirmed 50mm thick layer of sand blinding. The lack of
heave after the addition of water to the soil indicates inadequate
initial compaction of founding soils if sand blinding is not
Determination | Case number: 519338 Page 18 of 19
Record Key points
present.
> The leak from the bath tap has con solidated the unconfirmed
presence of 50mm of sand blinding under the slab since
construction but has not been significant enough to heave the
foundation soil (this assumes the soil fill was adequately
compacted and that only the sand blinding has consolid ated).
> The settlement has occurred due to the gradual consolidation of
inadequately compacted fill and possibly the consolidation of up
to 50mm of sand blinding solely as a result of the infrequent
addition of moisture which has increas ed significantly wit h the
change of tenancy in 2015.
4.12 In the above scenarios t he non - discovery of the leak until
2017 and the minimal rot and decay to the timber studwork of the
bathroom wall indicates that the leak has not existed since
construction and that settlement w as occurring due to
consolidation of poorly compacted fill prior to the leak. However,
the absence of settlement at the southern end of the house,
despite t he open garden beds and trees and the settlement of t he
site under the external paving, indicates th at the foundation soil in
this location was adequat ely compacted. F E ‟s opinion is that it is
not possible to apportion percent ages of damage to the leak
and/or pre - leak settlement of the footing.
5.0 Conclusion
5.1 F E ‟s opinion is that the observed damage to the internal
cosmetic finishes has been caused by the settlement of the cent ral
floor area. Further damage to the internal cosmetic finishes has
been caused by water from the leak in the breach to the bath tap.
5.2 F E ‟s opinion is that the settlement of the central area of the
floor slab and poor detailing of the connection between the non -
load bearing walls and the roof trusses has primarily caused the
damage to the roof trusses, possibly with the assistance of
mechano - absorptive back - out in the un - sark ed roof space.
5.3 The settlement to the central area of the house commenced
immediat ely after the construction of the hous e but was then
observed to accelerate after a new tenancy started in 2015, in
which the bath was used more frequently, before a leak was
discovered in the breach to the bath in 2017. This timeframe
suggests:
> The settlement of the central area of the house has been
occurring since construction due to the consolidation of
inadequately compacted fill under the slab and the recent leak
has amplified this consolidation and also consolidated an
unconfirmed up to 50mm thick layer of sand blinding. The lack of
heave after the addition of water to the soil indicates inadequate
initial compaction of founding soils if s and blinding is not
present.
> The leak from the bath tap has consolidated the unconfirmed
presence of up to 50mm of sand blinding under the slab since
construction but has not been significant enough to heave the
foundation soil (this assumes the soil fill was adequately
Determination | Case number: 519338 Page 19 of 19
Record Key points
compacted and that only the sand blinding has consolidated).
> The settlement has occurred due to the gradual consolidation of
inadequately compacted fill and possibly the consolidation of up
to 50mm of sand blinding solely as a result of the infrequent
addition of moisture which has increas ed significantly with the
change of tenancy in 2015.
5.4 The leak from the breac h in the bat hroom would not have
contribut ed to the settlement of the floor slab or caused damage to
the roof trusses but for t he poor construction of the house, these
being:
> The „broken out‟ sand filled cavity between the bathroom and
kitchen which was not screeded over under the shower tray thus
allowing water to enter under the house.
> The incorrect connection between the roof t russes and the non -
loadbearing internal walls.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.