Determination 517960
Claim denied for ceiling damage caused by atmospheric or climatic conditions
Summary
The applicant claimed for ceiling ghosting, cornice cracks and undulations and said cracked roof tiles let in rain. AFCA found the damage was caused by atmospheric or climatic conditions and the FSP was entitled to deny the claim.
The proximate cause of the ceiling damage was condensation and thermal movement rather than rainwater entry, which the policy's atmospheric and climatic conditions exclusion covers.
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
Case No: 517960 Determination Page 1 of 5
Case number: 517960 21 June 2018
1 Overview
1.1 Dispute
The applicant holds an insurance policy with the financial services provider (FSP) to
cover her home against accidental damage, subject to certain exclusions (such as
mildew, atmospheric or climatic conditions).
On 15 December 2017, the applicant lodged a claim for ceiling damage following
ghosting stains, cracked cornices, and undulations to the ceilings in various rooms of
her home. On 12 February 2018, the FSP declined the claim on the basis that the
ceiling damage was caused by mildew, atmospheric or climatic conditions.
The applicant says that the roof has a dislodged ridge tile cap and cracked roof tiles
which makes it susceptible to letting in rain water. If water entered the roof cavity, it
either contributed to or directly caused damage to the ceiling.
1.2 Issue and key findings
Is the FSP entitled to deny the claim?
The applicant has not raised concerns about roof damage in this dispute.
The FSP is entitled to deny the ceiling damage claim because regardless of whether
the roof tiles are cracked, the proximate cause of the ceiling damage was
atmospheric conditions and not entry of any rainwater.
1.3 Determination
This determination is in favour of the FSP.
The FSP is not required to pay any amount to the applicant.
Case No: 517960 Determination Page 2 of 5
2 Reasons for determination
2.1 Is the FSP entitled to deny the claim?
The policy covers accidental damage, subject to exclusions
The applicant, through her representative, has stressed the policy is not a listed
events policy, despite the FSP’s initial error in referring to listed events. I accept that
the policy provides accidental damage cover for buildings and contents.
The damage to the ceiling is unintended and unexpected. It is not in dispute the
policy responds to cover the ceiling damage, subject to any exclusions which may
apply.
The FSP has accepted part liability for roof damage
The roof damage appears to be limited to one broken or dislodged ridge cap and
several cracked tiles. The FSP has accepted liability for the $220 cost of replacing or
repairing the roof ridge capping, and noted that this is less than the $550 applicable
excess.
The applicant has not raised concern about damage to the roof during the course of
the dispute. Her primary concern has been about her ceiling damage.
There is no information to show that rainwater entry caused ceiling damage
The applicant has provided no reports to show that the roof was damaged, but
instead relies upon a report prepared for the FSP by builder B&P, which says that
there was one missing ridge cap and several cracked tiles. The applicant says it is
beyond reasonable to assume that because of these defects, water would enter the
roof cavity when it rained.
I accept the applicant’s position that rainwater may have entered through the cracked
tiles. I do not consider it necessary, as the FSP requires, for the applicant to obtain a
report asserting that cracked tiles would allow rainwater entry into the roof cavity.
The cracked roof cap and tiles do not affect the entire roof, and yet the ceilings are
affected even where there are no cracked tiles overhead. One would reasonably
expect water stains in the roof cavity in the vicinity of cracked roof tiles if the entry of
rainwater had caused damage to the ceiling. The applicant has provided no
information to show that openings in the roof caused the ceiling damage where the
roof was cracked. The FSP engaged engineer C to inspect the property, who
reported nothing unusual and no water stains in the roof cavity. I am not satisfied that
the ceiling damage was caused by rainwater entry.
The applicant says it is not necessary to determine whether the water entry
contributed to, or directly caused, the ceiling damage because the policy covered
accidental damage. However, it is not enough that the ceiling damage was
unintended and unexpected if an exclusion operates to defeat accidental damage.
Case No: 517960 Determination Page 3 of 5
The proximate cause of ceiling damage was atmospheric conditions
The policy does not cover claims for loss, damage or liability arising from mildew,
atmospheric or climatic conditions. That is, if the proximate cause of the ceiling
damage was mildew, atmospheric or climatic conditions , the FSP would be entitled to
deny the claim. The proximate cause is the effective, dominant or operative cause of
the loss. It is not necessarily the first or last or the sole cause of the loss.
The applicant’s plasterboard ceilings are affixed to steel roof trusses by way of steel
ceiling battens. Dark stain lines (known as ghosting) have appeared along the length
of these battens where the plaster ceiling was attached. Engineer C says that
condensation would form along the plasterboard which was fixed against metal and
so was colder than the warm room temperature. Dust and other airborne particles
would then adhere to the condensation causing stains to form along the battens. The
ghosting is caused by atmospheric conditions.
The ceiling also had cornice cracks and undulations. Engineer C says that this was
caused by temperature changes combined with a lack of joints over time because of
changes in humidity and temperature throughout the year. The cracking and
undulations are caused by climatic conditions.
The applicant has provided no information to say that atmospheric or climatic
conditions did not cause the ceiling damage. The ghosting, cracks, and undulations
appear in rooms and hallways where there are no roof cracked tiles overhead, which
supports the expert view that atmospheric or climatic conditions caused the ceiling
damage.
I am satisfied that proximate cause of ceiling damage was atmospheric or climatic
conditions. On this basis, the FSP is entitled to deny the applicant’s claim.
Case No: 517960 Determination Page 4 of 5
3 Supporting information
3.1 Summary of reports
Record Key points
FSP’s expert (B&P)
Assessment report
20 December 2017
Cracking to the cornice is due to water/moisture in the roof cavity
reacting with the steel roof trusses and plaster.
The ceiling is covered in dark lines called “ghosting”, where moisture
in the roof cavity creates dark lines across the cei ling.
Damage has occurred over a period of possibly six to 12 months.
Ghosting is generally related to poor ventilation in the roof cavity,
along with condensation and high moisture levels.
Maintenance required: replace missing roof cap tile, replace any
cracked tiles, check and repair pointing and installation of at least two
whirly bird roof vents.
FSP’s expert (C)
Engineer ’ s report
25 January 2018
No water stains were observed in the ceiling space.
The cornice cracking was caused by water/moisture in the ceiling
space reacting with the steel trusses/plasterboard.
The ceiling contains dark lines called ghosting.
The damage may have occurred over a period of 6 to 12 months.
Generally, ghosting is caused by inadequat e ventilation, condens ation
and high moisture levels.
We observed no evidence to support a theory that the ghosting was
caused by water ingress into the ceiling space due to a storm, a
leaking pipe or other insurable event.
Cracks/undulations to the zone 1 ceiling lining have occurred as a
result of expansion and contraction of the plasterboard ceiling lining,
as a result of change in humidity and temperature throughout the
year.
The cracks have occurred due to the absence of expansion and
contraction joints.
The damage occurred due to tem perature changes combined with
lack of joints.
As the ceilings have expanded and contracted in the horizontal plane,
stresses have been induced along the cornices, resulting in cracking
and stretching of paint.
3.2 FOS approach
This dispute has been determined based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous FOS decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
Case No: 517960 Determination Page 5 of 5
raised by the other. All material provided by the parties has been reviewed and
considered.
While the parties have raised numerous issues in their submissions, for the purposes
of this determination, commentary has been restricted to those issues which are
considered directly relevant to the outcome only. The applicant was concerned that
the FSP appointed engineer C without consultation. The FSP is entitled to investigate
the claim to determine the extent of its liability (if at all) . I am satisfied the FSP’s
handling of the claim is reasonable in the circumstances.