Declined claim for subsidence and cracking caused by septic tank leak, and mould remediation
Text of the determination
Determination | Case number: 507388 Page 1 of 14
Determination
Case number: 507388 29 November 2018
1 Determination overview
1.1 Complaint
The complainant lodged a claim on his policy with the financial firm in November 2016
after he noticed extensive cracking to his home.
The financial firm initially declined the claim on the basis the dominant cause of the
loss was due to normal and expected differential ground movement due to tree roots,
rather than the water leak from the complainant ‟s septic tank which it argued was not
the primary cause of damage.
In March 2018 the financial firm revised this position and agreed to pay for 30% of the
damage. To date the financial firm has not established the quantum or made any
attempt to remediate mould from the complainant ‟s home.
1.2 Issues and key findings
Is the financial firm entitled to decline the complainant ’s claim?
The complainant has established a prima facie claim for escape of liquid. The
financial firm is not entitled to decline the complainant ‟s claim in full. It must, in
addition to the mould remediation, prepare a scope of works for the other claimed
damage and pay 50% of the cost of the rectification of such damage .
Is the complainant entitled to compensation for non-financial loss?
The financial firm is to pay the complainant compensation for the stress and
inconvenience suffered during the claim process and a contribution towards the cost
of their expert reports.
1.3 Determination
This determination is partially in favour of the complainant.
Within seven days of the complainant accepting this determination, the financial firm
is to:
Determination | Case number: 507388 Page 2 of 14
immediately commence the rectification works to the damage to the complainant ‟s
property
should the financial firm have not obtained a scope of works which includes the full
underpinning of the premises, it will promptly do so and include this in the
rectification works
pay for the mould remediation and 50% of cost of the rectification of the damage
provide the complainant and his family with temporary accommodation for the
duration of all repairs and mould remediation works, irrespective of any policy limits
should the complainant agree to a cash settlement of 50% of the building repairs,
the quotation should include a margin of 12.5% to cover the transfer of the risk to
the complainant of finding unexpected damage in the course of the rectification of
the damage and the loss of the lifetime guarantee for repairs
pay up to a maximum of $3,000 towards the complainant ‟s expert reports, subject
to the complainant providing appropriate receipts or invoices
pay the complainant $3,000 compensation for non-financial loss
Determination | Case number: 507388 Page 3 of 14
2 Reasons for determination
2.1 Is the financial firm entitled to decline the complainant ’s claim?
Events leading up to the claim
In November 2016, the complainant lodged a claim with the financial firm after he
discovered water was leaking from his dishwasher. During a site inspection for this
claim, the complainant notified the financial firm ‟s agent that there were large cracks
in the dwelling. The agent advised the complainant to lodge a separate claim for this
damage.
A subsequent claim was lodged. The financial firm sent its agent C, who also
engaged a plumber (TBP). TBP‟s investigation no ted that the entire subfloor was
damp and there was mould on the external walls. However, they were unable to find
any leaking water pipes and the stormwater drains appeared to be in good condition.
CRD was then engaged, who provided a report in February 2017 stating the
dishwashing leak would not have caused the cracking, and the likely cause of the
problem was due to the following factors:
differential ground movement
normal surface rainwater runoff
the close proximity of mature trees.
The CRD report also made a recommendation that the complainant should check his
septic tank.
The complainant then engaged a plumber, who discovered there was a leak in the
septic tank. This was immediately repaired. The complainant then requested the
financial firm review its decision on the basis the septic tank leak had caused the
damage to his property.
The financial firm reverted to CRD with the new information on the leaking septic.
However, CRD did not re-attend the site. Instead he confirmed his previous view that
there would have been minimal damage from the leaking septic tank, and the problem
was still the trees. The financial firm relied on its expert‟s opinion that the septic tank
leaks would have only contributed 5% to 10% to the loss, and as such nothing was
payable.
The complainant brought his complaint to us for review. The Panel finds that there are
two separate issues in relation to the causation of damage claimed. The complainant
has the onus of proof of establishing that the damage was caused by a defined event
in the face of expert evidence which indicates that there were, at least, two causes –
the leaking septic tank and nearby trees.
Determination | Case number: 507388 Page 4 of 14
Policy covers escape of liquid, subject to exclusions
The policy provides cover for defined events which includes water which escapes
from a pipe or tank. This cover is subject to exclusions for deliberate damage, or
gradual damage (such as splashing or rising damp). The policy also has a general
exclusion for wear and tear, depreciation or deterioration.
The complainant has provided information confirming a leak was found in his septic
tank in March 2017. The complainant has also provided several expert geotechnical
reports confirming the damage to his house is directly related to the defined event of
“escape of liquid”. The financial firm has provided conflicting expert opinion that the
damage was caused by a line of nearby trees.
The Panel is satisfied the complainant has established a prima facie claim, at least in
part. The financial firm has the onus of establishing an exclusion or otherwise
demonstrating it is not obligated to pay the claim.
The financial firm must establish the exclusions relied upon apply
The financial firm initially argued it had no liability for the claim whatsoever, on the
basis its reports indicated the dominant cause of the damage to the property was due
to ground movement, which had occurred due to there being a line of trees in close
proximity to the complainant ‟s property.
The financial firm was of the view that as the damage attributed to the septic tank leak
was less than the damage attributed to the actions of the trees, it did not have any
liability. FOS advised the financial firm that in order to apply a Wayne Tank approach
as to causation and reduce its liability to zero, there needed to be an insured event
operating in conjunction with an excluded event.
We noted that the policy did not contain exclusions either for the actions of tree roots
or for ground movement. FOS advised the financial firm it was unlikely to be
successful proceeding with this argument.
Accordingly, the financial firm advised it would rely on the following exclusion:
Wear and tear, depreciation and deterioration.
The basis for the submission was that “the damage is deterioration due to tree root
drying ground settlement”.
The Panel does not accept this exclusion is relevant in the context the financial firm is
attempting to use it. Nevertheless, the complainant must still establish that the
claimed damage was caused by a defined event.
Determination | Case number: 507388 Page 5 of 14
The financial firm ’s expert evidence is compelling in part
As previously discussed, the CRD engineer opined there was no additional damage
from the septic tank leak, beyond the 5% - 10% he had previously assigned to the
minor leak from the dishwasher.
The Panel is persuaded this opinion has merit, despite the fact the engineer did not
re-attend the property after the septic tank leak was discovered or to undertake any
soil testing.
However, DML did attend the site and undertake soil testing. There is a question as to
why the reports do not provide any conclusion as to why the heritage trees have
coexisted next to the complainant ‟s property for some forty years without causing any
significant movement, but the sudden septic tank leak has only minimally contributed
to the damage.
The financial firm has also represented it is unable to establish which parts of the
property were damaged by water and which parts of the property were damaged by
trees, and has relied on its expert to proportion causation.
The amended report by D, whilst providing a proportional breakdown of the factors
responsible for the loss, also comes with a disclaimer as follows:
it must be understood that, given the nature of the geotechnical field it is not
possible to accurately calculate the percentages to which each factor affects the
performance of a building. As a result of this it must be understood that all
percentage break downs of the causes of distress are estimates only.
The Panel believes, even if it were to accept the tree drying settlements were the
proximate cause of the movement to the building, the 30% amount apportioned by the
financial firm is conservative taking into account its expert‟s clarification that the
percentages cannot be accurately calculated and his findings are estimates only.
Furthermore, the financial firm ‟s own correspondence to us indicates the task to
identify exactly what damage is solely due to the tree roots cannot easily be achieved:
From our enquiries, the task of specifying what each crack was caused by
(whether it was escape of liquid or tree drying effect) is onerous and not
practically able to be performed.
Ultimately, the complainant has suffered a loss to which the policy responds. The
Panel is satisfied, after reviewing all the evidence, it is fair that liability for the claim
should be apportioned, so the financial firm is not liable to the full extent of the claim.
Additional cracking to home most likely caused by building distress
During the complaint, further cracking appeared at the rear of the complainant ‟s
premises. The complainant brought this to the attention of the financial firm, who
Determination | Case number: 507388 Page 6 of 14
immediately requested the service not consider it as part of this complaint as it
considered the cracking to be “separate and unrelated to the issue before FOS” .
The financial firm was advised that the Panel would make that decision when it
reviewed the complaint. As such, the financial firm produced a further report from
DML stating the following:
Based on our recent site investigation, it is abundantly clear that the cracking in
the rear wall of this building is well within the normally “seasonal” expected range
for domestic buildings in Australia.
The report went on to state that the dishwasher leak could not have caused this
problem. Although the report did not comment on whether the damage could have
been caused by the leaking septic tank which is the primary source of water
inundation – and the subject of this complaint, and did not consider the long-term
effects of the overall movement of the building due to the rotation of the saturated
footings, its conclusion is very emphatic.
The Panel Is satisfied that the new cracking to the rear of the premises is a direct
result of the current distress of the building as alleged by the complainant. The Panel
accordingly finds the financial firm is liable for this damage in part.
The financial firm is liable to pay the claimed damage in part
The Panel is satisfied it is appropriate to find from the evidence that there are two
separate causes of damage in the claim and that it is not possible to separate the
impact of these claims. The Panel finds it is fair that the parties bear equal
responsibility for the claimed damage. Accordingly, the financial firm is liable to pay
50% of claimed damage other than the mould.
Financial firm delayed and then declined mould remediation works
The insured building is the complainant ‟s residential premises. The complainant
raised the issue of the negative health effects the mould was having early in the
claims process. Problems with mould growth are identified in several expert reports
provided by the complainant ‟s builder and plumber.
Despite prompting from FOS, the financial firm took the view that it was “premature”
to provide a final position on whether or not it would remediate the mould at the
premises. In April 2018 the financial firm agreed it would remediate the mould.
However, it has twice changed its position since that time, with the last
communication in July 2018 being a “cut and paste” extract from an expert report –
with no accompanying commentary.
The Panel considers this to be a sub-optimal approach by the financial firm, as the
complainant did not undertake the necessary remediation works himself in the
mistaken belief that the financial firm would be doing so. Further, it was more than a
year after the leak was repaired before the financial firm went out to review the mould
Determination | Case number: 507388 Page 7 of 14
damage, and some 18 months post-repair that it sent an expert out to comment on
causation.
The evidence shows that there are potentially very serious health risks associated
with the presence of mould in a residential property. It is unreasonable that there were
delays in the financial firm clarifying the situation for the complainant, and taking
proactive and appropriate steps to resolve the matter.
The mould only exists in the rooms immediately above where the water from the
septic tank pooled. Whilst the financial firm ‟s ex perts have indicated the mould is due
to “environmental issues inside the house”, and is unrelated to the escape of water
from the septic tank, there is no expert commentary discussing why the
“environmental issues” located in the mould affected rooms are not present anywhere
else in the property, and are only present in the areas immediately above the water
affected areas.
The Panel finds that the financial firm is liable for all mould remediation at the
complainant ‟s property.
2.1 Is the complainant entitled to compensation?
The financial firm is to pay the complainant $3,000 compensation
Under paragraph 9.3 of the FOS Terms of Reference, we can award compensation to
complainants when, because of an act or omission of the financial firm, they suffer an
unreasonable degree of stress, physical inconvenience, time taken to resolve a claim
or loss of enjoyment of their asset.
Awards of compensation are limited to $3,000 and are made conservatively. We
expect complainants to bear the usual degree of inconvenience and delay common to
an ordinary insurance claim.
The property remains unrepaired several years after the septic tank leak. It is clear
the complainant ‟s enjoyment of his home was significantly disrupted during this
period. The multiple delays caused b y the financial firm have undoubtedly caused
further damage to the property. Furthermore, living in the home while it deteriorated
around him would have caused the complainant substantial worry.
The Panel considers the financial firm ‟s overall management o f the claim was
extremely frustrating and upsetting for the complainant, who was attempting to work
with the financial firm in good faith to have his claim resolved.
The Panel is also concerned about the following specific conduct by the financial firm:
During conciliation in February 2018, the financial firm was put on notice that its
argument that it had no liability for the claim whatsoever was unlikely to be
successful. It immediately requested a timeframe extension so that it could
Determination | Case number: 507388 Page 8 of 14
investigate the leaking septic tank, on the basis the cause of the leak might be due
to tree roots, or some other cause which may not be covered.
The Panel finds this strongly implies that the financial firm was actively looking for
a way to decline the claim, and not acting in good faith. The Panel is of this view
because the financial firm could have inspected the septic tank pipe at any time
from July 2017, yet did not make any attempt to do so until advised its then
position was untenable.
In April 2018 the financial firm made a prejudice argument against the complainant
on the basis it had not been able to inspect the septic tank pipe prior to it being
repaired. The Panel points out that the complainant is entitled to authorise
essential repairs under the policy without permission from the insurer. The
complainant is also obligated under the policy to take action to mitigate damage to
his property. Further, and as previously discussed, the financial firm was aware of
the damaged septic tank pipe from July 2017, yet made no attempt to investigate
the cause of the leak until February 2018 when its position to decline the claim in
its entirety was challenged.
The financial firm ‟s failure to take action to address the complainant ‟s ongoing
concerns about mould at the property, in circumstances where it was already
assessing its liability for water damage and when it had accepted liability for water
damage.
At time of writing, the financial firm has not yet provided a formal offer to the
complainant to resolve the complaint. The current position of the financial firm to
pay the complainant 30% is meaningless and unsupported, and this position has
not been expanded or elaborated upon since it was originally proposed on 9 March
2018, which is almost six months ago.
Taking all matters into account, the Panel is satisfied the complainant ‟s claim and
complaint experience warrants an award of compensation of $3,000.
Determination | Case number: 507388 Page 9 of 14
3 Supporting information
3.1 The determination is made under FOS Terms of Reference
The Australian Financial Complaints Authority ( AFCA) has commenced managing
disputes previously lodged with F inancial O mbudsman S ervice (FOS) .
This determination is made under FOS Terms of Reference but has adopted the
following terminology for consistency with AFCA. In this determination the AFCA
terms have the same meaning as the FOS terms defined in paragraph 20.1 and
Schedule 1, 2 & 3 of the FOS Terms of Reference.
FOS definitions AFCA term
applic ant complainant
financial services provider financial firm
dispute complaint
claim claim
3.2 Our approach to the determination
This complaint has not been the subject of a recommendation. Due to the nature of
the dispute, it has been referred directly to a Panel for determination, in line with the
Operational Guidelines to the FOS Terms of Reference. The Panel consists of an
Ombudsman and two representatives with consumer and insurance experience.
The Panel has decided this case based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous FOS decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other.
The Panel has reviewed and considered all of the material provided by the parties.
While the parties have raised numerous issues in their submissions, for the purposes
of this determination, the Panel has restricted its commentary to those issues that it
considers directly relevant to the outcome only.
3.3 Terms of the Policy
Record Key points
Determination | Case number: 507388 Page 10 of 14
Record Key points
Policy Schedule Period of Cover 27.02.2015 – 27.02.2016
Approximate dat e of construction 1960 – 1969
What you are covered
for
Pages 32 - 40
Insured event: Water or other liquid
We will cover damage by:
Water or other liquid which suddenly escapes from your or your
neighbours:
plumbing system
tank
toilet system
a water main or pipe
If this Policy insures your building and we accept your claim,
we will also pay the reasonable cost:
to find the source of the leak
to repair only that section of your building which needs to be
removed to repair the leak
We will not cover :
damage if the cause of the water or other liquid escaping was
a deliberate act by you..
the costs to fix the leak
the cost of the lost water
the cost s to repair or replace any defective part or item that
caused the damage or the loss of water as a result of the leak
for example we will not pay for a new dishwasher hos e that
broke
damage which is as a result of a gradual process;
for example we will not pay for damage
- from condensation or rising damp, or
- splashing, or
- where more damage has occurred over time because
the fault was not remedied immediately
Accommodation cost
Page 47
If thi s Policy insure s your building, we will cover:
the reasonable costs you incur for similar accommodation
while your building is being rebuilt or replaced if you live in
your building
…
If we have accepted a claim following damage to your
building and we agree that your building is not fit to live in
Essential temporary
repairs
Page 53
If this Policy insures your building, we will cover:
any essential temporary repairs to your building which are
necessary following damage by an insured event. You are
able to proceed with essential temporary repairs up to the
limits stated below without obtaining our agreement
Determination | Case number: 507388 Page 11 of 14
Record Key points
beforehand
…
$500 any one (1) claim
General Exclusions
Page 66
You are not insured under any section of thi s policy if the
incident arises from or i s connected with:
…
Wear and tear, depreciation, deterioration
…
3.4 Key Documentation
Record Key points
F inancial firm expert
( TBP)
Report
28 November 2016
Confirmed there are no leaking water pipes wit hin the vicinity of the
subsidence
It appears that due to the slope of the block the subsurface water
has made its way to ground level beneath the dwelling
It is noticeably wetter alongside the brickwork beneat h the subfloor
than other areas, however the entire subfloor beneath the dwelling
is damp
There is visible rising damp beneat h the subfloor on the brickwork
and on the concrete stumps
There is evidence of mould on the external walls internal plaster
C omp lainant’s expert
(LP)
R eport
19 January 2018
Confirmed attended complainant‟s premises to investigat e problems
with noticeable dampness around brickwork on southern and
eastern sides of the house
There was a lot of dampness along the footings
Septic tank located at southern side of the house was found to have
water pooling around the connection
Pipe work from septic to house was replaced as the grey water was
leaking through the trench along the pipe and back to the brick work
In my opinion this could be the caus e of the pooling of water under
the sub floor and cause of the dampness under the subfloor, eg:
bricks, stumps and mould
Repair work was carried out i n March 2017
C omp lainant’s expert
(SBS)
Quotation (incl SoW)
21 January 2018
It would appear the septic leak has caused several problems to the
dwelling
Extensive rectific ation works required
Due to the moisture at the base of the footings there are signs of
rising damp and mould to all affected areas
There is a potential healt h risk to you and your family and
recommend someone is engaged to look at this
Estimated costs are between $68k - $79k
Determination | Case number: 507388 Page 12 of 14
Record Key points
(mould remediation works and temporary accommodation needs
have not been included in estimate)
F inancial firm expert
(DML)
Report
16 February 2018
Clay in borehole 1 was considerably dryer than would be expected
for a similar type of soil at this time of year
This is consistent with the drying action of the surroundi ng trees
The clay in boreholes 2 & 3 was found to be considerably wetter
than would normally be expected.
This level of moisture is consistent with leaks or insufficiencies in
nearby plumbing servic es
it is evident that the movement and distress around the front of this
building, and in particularly the most significant cracking near the
north eastern corner, has been caused predominantly by the drying
action of the trees located around the front of this building
it is evident that some of the movement and distress at the front of
this building including the outward rotation of the base brick work
has been caused by an increase in the moisture cont ent of the
reactive clay soil on the inside of the strip footing and bas e brick
work to the east wall.
It is lik ely that the previous leak in the sewer and the old hot water
service on the south side of the house are the main factors
influencing the water ingress into the sub - floor area beneath the
south eastern section of this building
Once water enters into the su bfloor area of a timber floored building,
it often percolates around the inside edge of the base brick work and
strip footings and becomes trapped against the inside edge of the
perimeter strip footing along the low side of the building. This
localised soi l dampness can lead to swelling or lateral heave of the
reactive clay against the inside edge of the footing
F inancial firm
corre spondence
Email
09 March 2018
[Insurer] agrees to offer to cover 30% of the loss, that which is
attributable to escape of liquid
C omplainant ’s expert
(CEL)
Report
26 March 2018
The rotation of the base brickwork is consistent with the moist soil
on the inside of the footing causing the footing to be rotated
outwards
The appearance of the rotation is consistent with the leaking pipe
into the septic tank system
This water is flowing back under the house via the quarter minus
crushed rock in the trench
Once under the house, the water follow s the footing trenc h around
to the lowest level of the building (sout h east corner) where the
biggest rotation has occurred
The anomaly of the rotation not being present in the front footing of
the extension is explained by the fact the water is following the
Determination | Case number: 507388 Page 13 of 14
Record Key points
original footings and not the extension footings
The diagonal distress to the north east corner appears to be related
to soil drying. This shrub was transplanted app r ox 4 - 5 years ago
and the timing of the cracking tends to support this conclusion
Does not agree with the findings which indicate the trees to the
north and south are contributing to the distress. This is because the
trees have been in existence for over 40 years and have not grown
significantly over the last 10
If they were the main drivers of the most recent distress it would be
expected that signs of distress to the front part of the house would
have occurred earlier.
According to the owner the building has been in good condition up
until the current distress which started in the autumn of 2016 and
has progressed since
F inancial firm
corre spondence
Email
19 March 2018
From our enquiries, the task of specifying what each crack was
caused by (whet her it was escape of liquid or tree drying effect) is
onerous and not practically able to be performed.
F inancial firm
corre spondence
Email
06 April 201 8
We feel it is premat ur e to provide our final res ponse in relation to the
mould issue
F inancial firm
corre spondence
Email
12 April 201 8
There is a policy exclusion for „wear and tear, depreciation,
deterioration „
The member submits the damage is deterioration due to tree root
drying ground settlement
Also argue prejudice as the leak was repaired by the Insured and it
could not engage its experts to investigate the reason the pipe
failed. financial firm feels this investigation was necessary.
Is willing to accept 30%
Is content to cover the mould remediation at the premises
Awaits a quot e for the mould remediation and also the repairs
Accepts it has taken financial firm some time to provide the quote
but expects it to be provided by COB tomorrow 13.04.18
C omplain ant’s expert
(CE L)
Geotechnical report
18 May 2018
Commenting on financial firm‟s supplementary report of 12.04.18
D‟s original report did not log the small shrub in NE corner and relied
on the cause of distress to this part of the building as soil drying due
to the matur e trees
Insured advises the crack in NE corner was not there at purchase of
property
The line of trees have been in existence for the life of the building.
Apart from the transplanting of the small shrub, there are no
significant weat her issues that would suggest why the line of mature
trees to the south would suddenly cause extraordinary drying to
Determination | Case number: 507388 Page 14 of 14
Record Key points
occur
The only event that has occurred is the leaking of the septic tank
causing the soil moisture under the house to increase and cause
heave to occur on the in side of the footing, causing the rotation.
The location of the distress on the building indicat es where there is
a problem. It is clear the base brickwork to the original house has
rotated significantly when compared to the extension.
Very little superstru cture distress to the SE corner of the extension.
My comment on the trees in the SE corner not causing an issue is
based on the lack of any signific ant distress in the building to this
corner, rather than any sophisticated geot echnical testing.
The lack of any significant distress to the SE corner suggests the
mature trees‟ moisture requirements, on a seasonal basis, have
been within a range that has not caused any significant distress.
In summary it is quite clear the leaking pipe has been the main
cause o f the issue. The magnitude of the rotation may have been
made worse by the fact the soil outside the footing is dry, however
without the influence of the leaking pipe the rot ation would not have
appeared.
F inancial firm
corre spondence
Email
26 June 2018
In relation to the mould, the Member will remediat e those areas
which are attributable to the septic tank leak. The Member has new
information to suggest the mould inside the building is not related to
the septic tank leak.
F inancial firm
corre spondence
Email
24 July 2018
…
2. Mould report. Please find same attached. The report states that:
1.7.2 Based on the information provided and evidence sighted,
it is the opinion of VA Sciences that the current fungal
conditions within the home are not related to a water escape
issue associated with the waste water system, but due to
regular condensation forming on poorly insulated surfaces as a
result of at times, elevated indoor humidity.
…
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.