Text of the determination
Determination
Case No: 503020 Determination Page 1 of 7
Case number: 503020 27 July 2018
1 Overview
1.1 Dispute
The applicant holds a home building policy with the financial services provider (FSP)
covering his home address.
On 11 September 2017, the applicant lodged a claim under the policy for water and
wind damage caused during a storm. After considering the claim, the FSP partially
accepted it.
However, the FSP considered most of the claimed items did not relate to this e vent
but were caused by factors such as wear and tear, faulty installation and gradual
deterioration. As loss from these causes are specifically excluded from cover, the
FSP declined the majority of the applicant’s claim.
1.2 Issue and key findings
Was the FSP entitled to limit its liability for the claim?
The FSP was entitled to limit its liability for the claim because:
the policy is an insured events policy;
the damage excluded by the FSP did not arise as a result of an insured event
as defined;
the likely causes of this damage are specifically excluded from cover; and
the FSP was therefore entitled to limit its liability for the claim to the storm
damaged items.
1.3 Determination
This determination is in favour of the FSP.
The FSP has fulfilled its obligations under the policy terms.
If it has not already done so, then it is to cash settle the applicant the amount of
$1,299.10 (less policy excess) plus the cost of the two tiles in settlement of his claim,
within 14 days of the applicant’s acceptance of this determination.
Case No: 503020 Determination Page 2 of 7
2 Reasons for determination
2.1 Was the FSP entitled to limit its liability for the claim?
Applicant has the onus to establish a claim
It is established insurance law the applicant carries the initial onus to show that the
terms and conditions of the relevant insurance policy covers the loss. This is known
as a prima facie claim. This entails showing both the cause and extent of the loss.
Once the applicant establishes a prima facie claim, the onus then shifts to the FSP to
demonstrate the loss is not covered, either by way of one of the policy exclusions or
on some other basis.
The FSP’s policy is an insured events policy. Therefore, th e policy only responds
where one or more of the listed events causes the damage, subject to any
exclusions. One of the listed events is storm.
The FSP has accepted the damage to the TV aerial and two cracked tiles under the
claim. Therefore, those issues are not in dispute and will not be addressed during
this determination, although they may be referenced where necessary.
Applicant must show all claimed items were damaged by the storm
The applicant also seeks the cost of repairing the roof, guttering, and garage to be
covered under the claim. The applicant says the wind and rain on the day cracked
tiles which caused water entry (in part due to the aerial cracking tiles where it fell)
and caused the roof to sag. It also ripped guttering from the fascia and shifted the
freestanding garage on its axis.
In order for these costs to be brought in under the policy terms, the issues must have
arisen as a result of an insured event. That is, the roof was damaged by a storm as
defined. For example, roof tiles blown off in heavy wind or tiles cracked by hailstones.
Simply because the roof started to leak during a period of rainfall or guttering
detached during heavy winds does not, of itself, satisfy this onus.
FSP’s evidence
The FSP arranged for claims management f irm “CC” t o inspect the property in order
to determine if there was any storm damage. CC accepted the TV aerial as being
damaged by the storm, however considered the rest of the items claimed were
unrelated and due to long standing issues. Full details of the expert reports are found
within section 3.2 of this determination.
The FSP also appointed building consultant “SB” to provide a forensic report as to
causation. For the sake of clarity, I will address each item separately below.
House roof
SB noted the property was approximately 90 years old and in poor condition for its
age. SB considered the roof framing rafters are inadequate, as are the purlins, struts
Case No: 503020 Determination Page 3 of 7
and battens. These were not compliant with the building standards at the time, which
came into effect in 1919. No sarking was installed and the wire ties holding the tiles
to the battens had perished on approximately 50% of the area. What was left was
brittle and disintegrated on touch. SB considered these were no longer adequate to
tie the roof tiles down.
There was no rotting to the hardwood timber frame, but there was cracking and
sagging to the underpurlin and struts, which has resulted in a wavy appearance on
the roof plane. This was due to the inadequacies of the framing, rather than the
claimed event.
SB also noted that in historical satellite images of the property dating from 2015, the
roof was noticeably wavy. Therefore, this issue pre-dated the storm and is unrelated.
SB considered the terracotta tiles were in poor condition, being faded, discoloured
and covered in organic growth. There were chipped and cracked tiles visible. The
ridge and hip capping was poor with cracked and dislodged cement bedding evident.
This was all long-term damage.
SB noted there were no signs of storm damage to the roof and all of the issues were
long term and maintenance related issues.
Guttering and fascia
SB noted the gutters were in poor condition with advanced corrosion and peeling
paint evident. There were downpipes missing from the exterior. Some sections of
guttering were also missing. Again, historical satellite images show this to pre -date
the event.
The fascia boards were rotted and deteriorated throughout, with the exception of the
rear of the property. SB considered it likely the strong winds had contributed to the
dislodging of the gutters, however, the lack of maintenance was also a contributing
factor.
Freestanding garage
SB recorded the garage was leaning to the North West between 1.2° and 1.6°. The
wall framing and roof rafters of the garage showed the spacing was outside the
requirements of the building code.
Accordingly, SB concluded the garage was defective from construction and this
damage has occurred over time and is unrelated to any storm event.
Photographs provided by the parties are generally supportive of SB’s conclusions as
to the pre-loss condition of the property, and the maintenance issues evident.
Applicant’s evidence
In support of his position that the roof, garage and guttering was damaged by a storm
event, the applicant has presented a report from building consultant “MB” .
Case No: 503020 Determination Page 4 of 7
MB considered the roof, despite the tiles being unglazed and covered with lichen,
was still in good condition and had many more years of life left in it. He did not
observe any evidence of brittle tiles or fretting to the watercourse.
However, crucially for the applicant, MB does not reference any damage to the roof
which is as a result of the claimed event. In addition, MB flatly disagrees with the
applicant about the cause of the wavy appearance of the roof, stating the roof purlin
support struts exceed the required span, which is the cause of this issue. This is
supportive of SB’s c onclusion.
MB was not prepared to form any conclusion as to the cause of the gutters being
blown off or the rotation of the garage.
Although the applicant states the house was built before the standards quoted by SB
came into effect, he has not provided a ny evidence of this. MB is silent on this matter
in his report. The applicant also maintains the TV aerial cracked tiles when it fell in
the high winds. However, photographs show no broken tiles around that area.
Accordingly, MB’s report is of limited as sistance to the applicant in establishing the
claimed items were damaged from the storm. After considering all of the available
evidence, the evidence of the FSP is preferred.
Policy excludes damage arising from wear and tear and where there is no
storm created opening
The policy contains a number of exclusions from cover. In particular, the policy
specifically excludes loss or damage caused by lack of maintenance, rust, corrosion,
deterioration, wear or tear.
The policy also provides that where there is no storm created opening, then any
resultant water damage is not covered by the policy. Therefore, in the absence of a
storm created opening, the loungeroom ceiling water damage is not covered under
the policy terms.
Damage not as a result of an insured event as defined
In order for the policy to respond, the damage must have arisen from event as
defined by the policy. The onus to ensure the property is watertight and
weatherproofed does not transfer to the FSP simply because it has insured the
home.
The evidence presented by the various experts is not supportive of a finding that the
damage arose as a result of a storm event, or any other event which would be
covered under the policy. Rather, the damage appears to be the result of long
standing issues with the property caused by wear and tear, a lack of maintenance,
faulty design or workmanship and gradual deterioration. Loss of this nature is
specifically excluded from cover.
Therefore, I do not accept the applicant has established a valid claim for the
excluded damage in the circumstances. On this basis, the FSP was entitled to limit
its liability for the claim.
Case No: 503020 Determination Page 5 of 7
3 Supporting information
3.1 FOS approach to this dispute
A full exchange of the relevant information has taken place between the respective
parties. Each party has had the opportunity of addressing any issues raised.
All of the provided material has been reviewed and considered. The parties have
raised numerous issues in their submissions to FOS. However, commentary in this
determination is restricted only to those issues considered relevant to the outcome.
3.2 Relevant expert reports
Record Key points
FSP’s expert ( CC )
Assessor’s Report
15 September 2017
the building is approximately 70 - 80 years old and is
maintained in poor condition
the gutters to the main home were in poor condition with
signs of severe and long - term rust and corrosion present
the gutters had detached from the fascia board
the fascia boards were deteriorated and rotting
this is all long term and not due to a single event
guttering to t he whole of the home and garage requires
replacement
water staining was evident to the loungeroom ceiling
there is peeling paint the ceiling and walls of lounge
this was due to paint preparation failure and not this event
the terracotta tiled roof was in p oor condition
evidence of fretting and deteriorated tiles was evident across
the roof
there were approximately 30 broken tiles visible
the resultant damage is due to recent wind gusts, wear and
tear and gradual deterioration over a significant period of time
the TV aerial has become detached from the chimney due to
strong winds, and this is consistent with storm damage
a roofing specialist was engaged to comment on the roof
the specialist gained access to the roof and conducted a
visual inspection
the til es were in poor condition and the water courses were
starting to fret
the roofer was of the view the broken tiles were due to a
failure of the tile and not any storm event
the roof had reached the end of its expected lifespan and
required replacement
no st orm damage or storm created openings were visible
water has ent ered due to the poor condition of the tiles
the resultant damage to the ceiling appears to be long term
and gradual, and not from a single event.
Case No: 503020 Determination Page 6 of 7
Applicant’s expert
( M B)
Building Consultant’s
Report
23 November 2017
the damage was viewed some months after the loss,
therefore some evidence may not be as it was
the roof tiles are terracotta with lichen growth
there are several deflections in the roof plane, which the
insured believes is due to w ind pressure
at the rear fascia the gutter and downpipes are missing
the freestanding garage presents a rot ation to the north of
approximately 4 °
there were a number of damaged tiles on the roof and these
have been replaced with tiles taken from the outside toilet
plastic sheeting is evident at the south west corner
there is no evidence of brittle tiles, watercourse fretting or that
the roof was in poor condition
although the roof is unglazed, the roof is in good condition
and has many more years of l ife left in it
the roof plane deflection is not due to wind as inspection
within the roof cavity shows the roof purlin support struts
exceed the required span
the cause of the gutters being blown off is not necessarily due
to the poor condition of the gutt ers as the galvanising in most
places is sound
there is possibly come corrosion around the outlets from the
gutter and debris build up at these locations, but the gutters
have come off due to the effects of wind
there is a possibility that wind has caused the garage to
rotate but there is insufficient evidence to form a conclusion
either way.
FSP’s expert ( S B)
Building Consultant’s
Report
14 December 2017
the property is estimated to be 90 years old and is generally
considered to be in poor condition for its age
weat her data showed gusts of wind up to 104km on the date
of loss
there is water staining evident to the lounge room ceiling
which is consistent with wat er ingress from this event
the paint peeling to the walls is unrelat ed to this event
inspection of the roof void showed no sarking installed, and
the roof trusses were of conventional hardwood frame
wire tires between the tiles and battens were only present to
around 50% of the area, and those that were visible
disintegrated upon touch
this is a wear and tear issue and the condition of the wire ties
is inadequate to tie the roof tiles to the battens
for the unsupported length of the rafters, the roof framing
rafters are inadequat e, as are the purlins, struts and battens
therefore, the roof framing was defective at installation and
did not comply with the standards at the time of construction
(whic h date from 1919)
there was no rotting to the roof frame but there was cracking
and sagging the underpurlin and distortion to the struts which
has resulte d in a wave appearance of the south - eastern roof
plane
Case No: 503020 Determination Page 7 of 7
this was evident upon viewing historical satellite images of
the property from December 2015
therefore, this is a long - t erm issue which pre - dates the storm
the tiles are likely to be brittle and crack easily when walked
on, therefore inspection was conducted from the skillion roof
the general condition of the terracotta tiles is poor
the tiles were faded and discoloured due to aging and
covered in organic growth
there were approximately 20 chipped, cracked and slipped
tiles visible
almost all edges pf the chipped and cracked tiles display
evidence of significant aging
the cracking is most likely due to foot traffic, with the
exception of two tiles in the sout h west corner, which was
most likely done during the make safe
the condition of the ridge and hip capping is poor with
cracked and dislodged cement bedding evident
the internal edges were crumbly and discoloured
this is all long - term damage
no evidence of storm damage to the roof was visible
the T V aerial had most likely collapsed due to the high winds
downpipes were missing from the exterior
the gutters were in poor condition with advanced corrosion
and paint peeling
a 6m long section was missing and had been removed prior
to inspection
viewing of historical satellite images showed similar lengths of
gutters missing
this is unrelated to any storm event
it is possible the rear guttering was dislodged by storms as
there was no evidence of rotting to the fascia boards
the guttering along the garage wa s either missing or deflected
corrosion and advanced rotting of the roof framing was
evident
the strong winds would have contribut ed to the failure
however the maintenance issues evident did also
the garage was leaning to the north west between 1.2 ° and
1.6 °
the wall framing and roof rafters of the garage showed the
spacings were outside the requirements of the building code
the garage was defective from construction and this damage
has occurred over time and is unrelated to any storm event.