Home / Financial Firm (Unknown - Insurer) / Determination 498988
Determination 498988
Storm damage claim declined under structural or design fault exclusion
Summary
The applicant's veranda storm damage claim was declined for defects and structural faults, with the experts agreeing the cause was inadequate waterproofing. He also sought a full premium refund, which AFCA refused.
Inadequate waterproofing membrane is a structural or design fault, which the policy expressly excludes irrespective of when it occurs, and premiums are not refundable merely because a claim is denied.
Issues
- Claim denial primary · not upheld
“The FSP is entitled to decline the applicant's claim as the damage arose from inadequate waterproofing, a defect, structural or design fault excluded from cover.”
- Misleading conduct secondary · not upheld
“There is nothing in the information exchanged to suggest that the FSP misled the applicant on inception of the policy as to the extent of cover.”
Subjects and remedies
no remedy
Text of the determination
Determination
Case No: 498988 Determination Page 1 of 4
Case number: 498988 14 August 2018
1 Overview
1.1 Dispute
The applicant lodged a claim on his Home Building and Contents Policy held with the
financial services provider (FSP) after a storm on 6 March 2017 caused damage to
his property.
The FSP declined the claim and says the damage was caused by defects, structural
or design faults or faulty workmanship (amongst other things) which are excluded
under the terms of the policy.
The Case Manager provided the parties with a recommendation on the issues in
dispute. The recommendation was in favour of the FSP. A copy of the
recommendation is attached to this determination. The applicant has rejected the
recommendation.
1.2 Issues and key findings
Were the findings in the recommendation correct?
The findings contained in the recommendation were correct and are adopted in this
determination. Further submissions provided after the recommendation have been
considered.
Is the FSP entitled to decline the applicant ’s claim ?
I am satisfied the FSP is entitled to decline the applicant‟s claim as on the balance of
probabilities the damage arose due to inadequate water proofing which was a defect,
structural or design fault which is excluded from cover under the terms of the policy.
Should the FSP refund the premiums?
I am not satisfied the applicant has established that he was misled as to the terms
and conditions of cover. In the circumstances, I am not satisfied that the FSP is liable
to provide any premium refund.
1.3 Determination
This determination is in favour of the FSP. The FSP is entitled to rely upon the terms
and conditions of the policy to refuse payment of the applicant‟s claim. It is not
required to provide any premium refund to the applicant.
Case No: 498988 Determination Page 2 of 4
2 Reasons for determination
I am satisfied that the case manager‟s reco mmendation contains an accurate
summary of the dispute, the issues to be determined, any applicable paragraphs of
the Terms of Reference and any relevant law.
In rejecting the recommendation, the applicant says:
he was unaware of any inadequate water proofing membrane prior to accepting
the policy
the policy is an accidental damage policy and he was unaware of the
application of any general exclusions to accidental damage
the recommendation relating to the refund of premium is detrimental to any
reconciliation
t he FSP‟s sales process was inappropriate.
This determination is based on what is fair in all the circumstances, having regard to
the relevant law, good industry practice, codes of practice and previous FOS
decisions. I have taken into account all the material submitted by the parties, both
before and after the recommendation. I am satisfied that the documentation I have
relied on has been provided to both parties.
2.1 Is the FSP entitled to decline the applicant’s claim ?
No dispute the applicant received the Product Disclosure Statement (PDS)
The applicant does not dispute having received the PDS from the FSP following
inception of the policy in 2010.
The applicant says he was not aware of the general exclusions applying to the policy.
I am satisfied however that the FSP has met its obligation to clearly inform the
applicant of the general nature and effect of the terms of the policy by providing the
applicant with a copy of the PDS.
Section 35 of the Insurance Contracts Act 1984 (the Act) requires that an insurer
must clearly inform an insured in writing of any relevant terms or conditions of a
policy that would be less than the minimum amount provided under a prescribed
contract.
It has been said that a fair reading of the section requires any relevant exclusion to
be in clear and unambiguous language and in a manner which a person of average
intelligence and education is likely to have little difficulty in finding and understanding
if that person reads the policy in question.
The PDS is relevantly indexed and sets out particulars of cover under the section
insured events and optional cover. The general exclusions are set out separately and
clearly state that they apply to all sections of the policy.
The applicant says he has been in the financial industry for more than 20 years. I am
satisfied that if the applicant had read the policy, he would have been made aware of
the relevant terms and conditions and in particular, made aware of the extent of any
exclusions.
Case No: 498988 Determination Page 3 of 4
Section 46 of the Insurance Contracts Act 1984 (the Act) does not assist the
applicant
I accept that the applicant may not have been aware of the lack of adequate water
proofing. He may not have been aware of the defect or structural or design fault. I
have considered in these circumstances whether section 46 of the Act provides any
assistance to the applicant.
Section 46 of the Act provides that an insurer may not rely upon a provision that has
the effect of limiting or excluding the insurer ‟ s liability by reference to the condition of
a thing at a time before the contract was entered into, if the insured was not aware of
the defect.
A policy may include provisions that exclude cover for particular events such as
inherent defects, structural faults, faulty workmanship and faulty design irrespective
of when they occur. Such exclusions do not fall within section 46 of the Act. Courts
have said that such exclusions cannot be said to be a limitation or exclusion made by
reference „ to a condition of a thing or at the time when the contract was entered into ‟ .
The applicant‟s policy does not make reference to the condition of the inherent
defect, structural faults or faulty workmanship or faulty design at the time the contract
was entered into. The provision excludes the event irrespective of when they occur.
In the circumstances, I am satisfied that section 46 of the Act does not assist the
applicant.
Damage most likely caused by inadequate water proofing membrane
I accept the reasoning contained in the recommendation. The expert reports provided
by the FSP and the applicant both identify that the damage has been caused as a
result of a lack of sufficient water proofing membrane. Both reports identify that the
timber floor joists have rotted most likely over a lengthy period due to the lack of
adequate water proofing.
The failure to adequately water proof the balcony is a defect, or structural or design
fault or faulty workmanship.
Although I accept that the damage sustained was accidental damage in that it was
unintended and unexpected, I accept that the FSP is entitled to rely upon the
exclusion contained within the terms of the policy to refuse payment of the claim.
2.2 Should the FSP refund any premiums?
The applicant has sought a refund of premiums from inception of the policy on
30 September 2010.
It is apparent from the information exchanged that since that time, the applicant has
made a number of claims on the policy and a number of these claims have been
declined for similar reasons to the current claim.
There is nothing in the information exchanged to suggest that the FSP misled the
applicant on inception of the policy as to the extent of cover. There is nothing in the
Case No: 498988 Determination Page 4 of 4
information exchanged to suggest that the FSP wo uld not have met any valid claim
under the terms of the policy.
I agree with the findings contained in the recommendation. The fact that the
applicant‟s claim was excluded under the terms of the poli cy does not invite an
entitlement to a refund of premium. I accept that the policy provided the cover as set
out in the PDS and I accept that the FSP was entitled to apply the relevant premium
throughout that time.
Recommendation
Case No: 498988 Recommendation Page 1 of 4
Case number: 498988 19 March 2018
3 Overview
3.1 Dispute
The applicant held a building and contents policy with the financial service provider
(FSP) over his principal residence. The applicant lodged a claim with the FSP on 6
March 2017 for damage to his veranda caused by a storm.
The FSP declined the applicant‟s claim, saying the cause of the damage was not the
result of a storm. Rather, the FSP says the cause of the damage was (amongst other
things) structural or design faults, which the policy excludes.
The applicant disputes the decision and seeks the FSP pay his claim in full.
3.2 Issues and key findings
Is the FSP entitled to decline the applicant’s claim?
After careful consideration of the available material, the FSP is entitled to decline the
applicant‟s claim. This is because:
both parties‟ experts agree the cause of the loss was inadequate waterproofing
inadequate waterproofing is a structural or design fault
the policy expressly excludes loss of damage caused by this factor.
Is the FSP entitled to refund premiums?
The FSP is n ot required to refund the applicant‟s premiums as they have accepted
the risk over the insured property. The simple fact the FSP denies a claim is not a
basis for a premium refund.
3.3 Recommendation
This recommendation is in favour of the FSP.
The FSP was en titled to decline the applicant‟s claim and not required to refund the
applicant‟s premium to him.
Case No: 498988 Recommendation Page 2 of 4
4 Reasons for recommendation
4.1 Is the FSP entitled to decline the applicant’s claim?
The applicant established a valid claim
The applicant is required to show that, on the balance of probabilities, they have
suffered a loss caused by a risk insured against under the policy. This is known as a
valid ( prima facie ) claim.
If the applicant is able to establish a valid claim, then the onus shifts to the FSP. In
such a case, the FSP needs to show, on the balance of probabilities, it is entitled to:
rely on an exclusion under the policy, and/or
it is otherwise entitled to deny the claim.
The applicant‟s policy provides for accidental damage. The policy does not define
the term „accidental damage‟ but it‟s generally considered to mean an event which is
unforeseen and unintended (from the applicant‟s viewpoint).
There is no material to suggest the damage was anything but unforeseen and
unintended from the applicant ‟s viewpoint. Given this, I am satisfied the applicant
has established a valid claim.
The FSP however says the cause of the loss was a variety of factors the policy
excludes. Given the FSP seeks to deny the claim due to a policy exclusion, it bears
the onus to show the proximate cause of the damage was a policy exclusion.
Experts agree the cause of damage was inadequate waterproofing membrane
The FSP obtained a building report in March 2017 from a builder (CIBS) to determine
the cause of the damage. The report identified:
extensive structural damage to the timber frame supporting the front veranda
where advanced rot was evident
damage to the front the veranda soffit where a section of blue board had fallen
off and paint was blistering.
CIBS concluded the report by saying:
Due to the extremely advanced extent of the timber rot we believe this leakage has been
going on for several years and has been caused due to a lack of adequate waterproofing
on the tiled balcony.
The applicant also engaged a builder (TS), who inspected the damage in December
2017. TS said the cause of the damage was a combination of consistent rainwater
damage and a lack of sufficient waterproofing membrane. TS further says in his
report that the timber floor joists and flashing has rot ted over time from „weak
membrane‟.
Given the above, I accept the proximate cause of the damage was inadequate
waterproofing membrane.
Case No: 498988 Recommendation Page 3 of 4
FSP entitled to deny the claim
The policy covers loss of damage, subject to exclusions. Relevant to this dispute, the
policy clearly and unambiguously does not cover loss or damage where the cause is
a structural or design fault.
I consider inadequate waterproofing membrane of a balcony to be a structural or
design fault.
Given this, it follows the FSP is entitled to deny the claim.
The FSP also sought to deny the claim on other factors. I consider the FSP is entitled
to deny the claim for the above mentioned reason. Accordingly, there is no need for
me to further consider any of the other policy exclusions the FSP sought to rely upon.
4.2 Is the FSP entitled to refund premiums?
The FSP does not have to refund premiums to the applicant
The applicant says should the FSP decline his claim, then he should be entitled to a
full refund of premiums from the policies inception of 30 September 2010.
Simply put, the applicant is not entitled a refund of the policies because the FSP
denied his claim.
The applicant‟s claim fell out the scope of cover and the FSP was entitled to deny his
claim on this basis.
If the circumstances were different, and the applicant suffered a claimable loss, there
is no reason to believe the FSP would not honour a claim.
Given there was cover provided, the FSP is entitled to charge a premium for this
cover. The applicant is not entitled to a refund of the policies.
Case No: 498988 Recommendation Page 4 of 4
5 Supporting information
5.1 Policy wording
General exclusions
Under this policy there is no cover provided for any loss, damage or liability caused directly or
indirectly by or in any way connected with:
1. defects, structural or design faults, faulty workmanship or faulty design
…
4. wear and tear and lack of maintenance, including rust, corrosion and deterioration
(except in some instances relating to the Insured Events “Escape of liquid” and “Legal
liability” claims)
…
35. gradual loss or damage of any kind
5.2 Reports
Record Key points
FSP’s expert (CIBS)
Building Report
28 - 03 - 2017
Extensive structural damage has occurred to the timber frame
supporting the front veranda where advanced rot is evident
Damage has occurred to the front veranda soffit where a section of
blue board has fallen off
There is also damage to the soffit painting and blue board lining
along the entire front elevation where paint is blistering
Leakage is occurring where the balustrade posts penet rate the
compressed f.c. sheets causing extensive rot to the underlying
structural timbers
Due to the extremely advanced extent of the timber rot we believe
the leakage has been going on for several years and has been
caused due to a lack of adequat e waterproofing on the tiled
balcony
Applican t’s expert (TC)
Building Report
12 - 12 - 2017
Lack of sufficient waterproofing membrane has caused extensive
rotting of timber floor joists and damage to surrounding elements
Rotting of timber floor joists and flashing over time, due to storm or
rainwater dam age from weak membrane
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.