Partial claim decline for storm damage to limestone boundary wall
Summary
The applicant claimed under his accidental damage policy for storm damage to a limestone boundary wall, which the FSP partly declined citing faulty workmanship and design exclusions. AFCA found the FSP had not established an exclusion and that the storm was the dominant cause, so the claim must be settled under the policy.
Once the applicant shows a valid claim, the insurer must prove an exclusion applies, and the FSP's expert evidence did not establish that the design or workmanship caused the loss.
Subjects and remedies
home or building damagenatural disasterpay claim
Text of the determination
Determination
Case No: 485403 Determination Page 1 of 2
Case number: 485403 1 3 April 2018
1 Overview
1.1 Dispute
The applicant contacted the financial service provider (FSP) on 9 February 2017 to
lodge a claim under his accidental damage home insurance policy, for storm damage
to his limestone wall.
The claim was assessed but partially denied, as the FSP says the wall was damaged
by events excluded from the policy. However the FSP accepted damage to the air
conditioner, bore pump and electric gate.
The applicant maintains the damage occurred as a result of a storm, which is an
insured event.
The Case Manager provided the parties with a recommendation on the issues in
dispute. The recommendation was in favour of the applicant. A copy of the
recommendation is attached to this determination. The applicant accepted the
recommendation, but the FSP did not.
1.2 Issues and key findings
Were the findings of the recommendation correct?
The findings contained in the recommendation were correct and are adopted in this
determination. Further submissions provided after the recommendation have been
considered.
I do not consider the FSP has established, on balance, that exclusions apply or that it
is otherwise entitled to decline the claim for storm damage to the wall.
1.3 Determination
This determination is in favour of the applicant.
I agree with the case manager’s reasons for the recommendation and the
recommended outcome.
The FSP is required to settle the claim in accordance with the terms of the policy.
Case No: 485403 Determination Page 2 of 2
2 Reasons for determination
2.1 Were the findings in the recommendation correct?
I have decided this case on its merits, having regard to the relevant law, good
industry practice, codes of practice and previous FOS decisions. I have taken into
account all the material submitted by the parties, both before and after the
recommendation. I am satisfied that the documentation I have relied on has been
provided to both parties.
I am satisfied that the case manager’s recommendation contains an accurate
summary of the dispute, the issues to be determined, any applicable paragraphs of
the Terms of Reference and any relevant law.
Applicant has a valid claim and FSP has not shown exclusions apply
I am satisfied the applicant has established a valid claim under the policy, which
covers accidental damage to his property.
While the FSP has said exclusions apply which would entitle it to decline the claim, I
am not persuaded that the evidence reasonably supports that.
Specifically, the FSP has relied on the exclusion for ‘faulty workmanship, structural
defects or faulty design’.
The evidence indicates the wall was built in about 2006. The FSP’s experts have
referred to certain Australian Building Standards in suggesting the wall was not
properly designed or built, but it is not clear that those standards applied at the time
the wall was constructed. The evidence also indicates the wall did not require specific
council approval when constructed. So I am not persuaded that the damage was
caused by any fault in workmanship, structure or design.
In any case, I am satisfied that the available information taken as a whole – including
about the nature and severity of the storm, and the particulars about the fence and
property – reasonably shows, on balance, the proximate cause of the damage (that
is, the dominant, operative or effective cause) was the insured event of ‘storm’.
That means, the FSP is not entitled to decline the claim, but should settle it in
accordance with the policy terms and conditions.
Recommendation
Case No: 485403 Recommendation Page 1 of 5
Case number: 485403 18 December 2017
3 Overview
3.1 Dispute
The applicant contacted the financial service provider (FSP) on 9 February 2017, to
lodge a claim for storm damage to his limestone wall.
The claim was assessed but partially denied, as the FSP says the wall was damaged
by events excluded from the policy. However the FSP accepted damages to the air
conditioner, bore pump and electric gate.
The applicant says the damage occurred as a result of a storm, which is an insured
event.
3.2 Issues and key findings
Was the FSP entitled to decline the claim?
I am satisfied, based on the information provided, that the applicant has established
a storm caused damage to the property.
The FSP is not entitled to rely on the exclusion for non-compliance with building
requirements at the time the fence was built. This is because it has not established
the fence did not comply with the relevant standards at the time of construction, or
that the construction of the fence caused the damage to occur.
As such, the FSP has not established any exclusions apply to the claim.
3.3 Recommendation
This recommendation is in favour of the applicant.
The FSP is required to settle the claim in accordance with the policy.
Case No: 485403 Recommendation Page 2 of 5
4 Reasons for recommendation
4.1 Was the FSP entitled to decline the claim?
Applicant has established a valid claim
The applicant is being assisted by a broker in this dispute. For the purposes of this
recommendation, their submissions will be referred to as the applicant.
It is established insurance law the applicant carries the initial onus to show that the
terms and conditions of the relevant insurance policy covers the loss. This is known
as a valid, or prima facie claim.
Once the applicant establishes a valid claim, the onus then shifts to the FSP to
demonstrate the loss is not covered, either by way of one of the policy exclusions or
on some other basis.
The applicant’s policy is an accidental damage policy. The policy does not define
‘accident’, however, it is common ly accepted as being loss or damage which is
unforeseen and unintended.
Insofar as the applicant did not expect or intend damage to occur to the wall, I accept
he has established a valid claim. As such, the onus now shifts to the FSP to establish
the damage is excluded, or that it is otherwise entitled to deny the claim.
FSP excludes damage caused by certain events
The FSP says the damage was caused by factors excluded under the policy such as,
faulty workmanship, structural defects, or faulty design.
The FSP says the failed section of the wall was not caused by the rain, but was in
fact caused by the faulty design of the construction of the wall. The FSP says as the
wall had no drainage holes for the water to escape, it acted like a dam and could not
cope with the pressure, causing it to burst.
In order to rely on the exclusions, the FSP must demonstrate, on the balance of
probabilities, that these excluded factors caused the wall to fail.
Different opinions on the cause of damage
The FSP engaged its experts B and C to inspect the wall, and to provide an opinion
on the cause of damage.
The FSP initially engaged B who attended the property on 14 February 2017. B’s
report states:
There is no areas of the fence line that have drainage holes to let rainwater through the fence
however if this fence line Hardifence this would still have no drainage holes.
[…]
Based on our inspection we believe that the cause of the damage has been due to an unusually heavy
downpour of rain during a storm event and the train water could not escape the property causing the
fence line to give way.
Case No: 485403 Recommendation Page 3 of 5
As the information from B stated there is no drainage holes, the FSP asked C to
inspect in further detail. C does not disagree with the information provided by B.
However, C’s report states :
The wall lacked the lateral load capacity as required pursuant to AS 3700 Clause 2.7, due to
inadequate foundation embedment, to resist lateral pressure resulting from damning of water behind;
The soil under the wall was saturated, losing strength, and undermining by water flowing under the
wall from the damned internal side, to the lower external side. Water flowed through the topsoil and
sand backfill and around the stormwater and electrical pipes which ran under the wall near the
northwest corner. The sections failed from vertical collapse due to the loss of ground support […].
The applicant disagrees with the FSP’s decline and says the wall showed no sign of
failure prior to the event. He raises concerns:
the storm was not an average storm, and was strong enough to do damage
the council does not require permits on a wall that is less than 2m high
the applicant cannot be aware as he purchased the property with the wall
constructed
the FSP reports by B confirm that damage is consistent with storm damage .
The FSP states the weather was not strong enough to cause damage. While not
being able to locate a weather station reading in the applicant’s area, the FSP says
the two closest weather s tations to the applicant’s town recorded rainfall of 74.2mm
with winds at 46km/h, while the other station recorded rainfall at 111mm with winds at
59km/h.
Whilst the FSP notes that neither station can accurately reflect the rainfall in the area,
it says the maximum rainfall the applicant could have experienced is 111km/h and
winds around 59km/h.
The FSP says wind speed need to be over 78km/h to cause damages, however
elected to provide no information to support its position.
FSP has not established exclusions
The FSP has not provided sufficient information to rely on the exclusion of faulty
workmanship at the time of construction. The information provided by C states as the
wall was less than 1800mm high, there is no requirement for it to be approved by the
council. The FSP has not refuted this view.
Additionally the FSP’s correspondence does not sufficiently demonstrate the climatic
conditions in the applicant’s area. Rather, the FSP’s decisions are based on locations
some 25kms from the applicant’s home.
In addition I have reviewed video footage from the applicant showing the event while
it was occurring. The video footage clearly shows the storm was not an average
storm.
I am satisfied the storm was of sufficient force to cause damage, and accept the
information from B which concludes the damage would have occurred in any event. I
note C has not refuted B’s statement that the damage would occur even if the
applicant had a Hardiwood fence.
On the balance of the information provided, I am satisfied the wall would have
sustained the damage it did, irrespective of the other concerns raised by the FSP.
Case No: 485403 Recommendation Page 4 of 5
That is, the proximate or dominant cause of damage to the fence, on balance, was
the storm.
Accordingly, I am not satisfied the FSP has established an exclusion to defeat the
claim. Therefore the FSP is required to settle the claim in accordance with the terms
and conditions of the policy.
Case No: 485403 Recommendation Page 5 of 5
5 Supporting information
5.1 Expert reports
Expert Key points
FSP’s expert (B)
Report
27 - 3 - 17
Two separate sections of limestone and colourbond infill fence has
completely collapsed.
There is no areas of the fence line that have drainage holes to let rainwater
through the fence however if this fence line was Hardifence this would still
have no dr ainage holes.
Based on our ins pection we believe that the cause of the damage has been
due to an unusually heavy downpour of rain during a storm event and the
rain water could not escape the property causing the fence line to give way.
FSP’s expert (C)
Re port
6 - 5 - 17
The inundation of the residential property exasperated pre - existing design
and construction deficiencies in the composite limestone and colourbond
sheeting boundary wall, resulting in failure of approximately 15m of the wall.
The wall would n ot have failed were it not for the pre - existing deficiencies
which included an absence of footings and vertical reinforcement to the
piers and lack of a drainage system to the west yard.
The boundary wall was never designed and or constructed to comply wi th
the reasonable requirements of AS3700 - 2011 Masonry Structures, AS4600 -
2005 Cold formed Steel Structures or manufactures requirements, and has
always been at risk of failure in design storm events, whether due to storm
water inundation or wind.
The wall lacks vertical reinforcement to creat e sufficient shear capacity and
restraint against overturning moments created by design wind loads (aside
from the loads created by the water pressure during the flood event). Overall
design wind loads are great er than the water pressure loads experienced
during the event.
The wall lacks sufficient depth to resist undermining by erosion in the event
of localized damming of water.
The soil under the wall was saturated loosing strength, and undermined by
water flowing un der the wall from the dammed internal side, to the lower
external side. Water flowed through the top soil and sand backfill and
around the storm water and electrical pipes which ran under the wall near
the northwest corner. The wall sections failed from th e vertical collapse due
to the loss of ground support; and the overturning movements exceeded the
moment capacity of the wall as calculated pursuant to AS37000 Section 7.
The council advised that the limestone boundary wall was not approved.
The Council of ficer Dale, advised that the wall was not required to be
approved on the basis that it was less than 18000mmm high and considered
a dividing fence.