Home / Financial Firm (Unknown - Insurer) / Determination 484942
Determination 484942
Lounge room damage claim denied as foundation movement
Summary
The applicant claimed for lounge room cracking after a bathroom water leak, and the FSP denied the lounge damage as caused by foundation movement. AFCA found on the expert evidence that the proximate cause was seasonal soil movement and trees, not the leak, so the denial stands.
Where foundation movement is the proximate cause of loss and would have occurred without the leak, the earth movement exclusion applies.
Issues
- Claim denial primary · not upheld“the damage to the lounge room, the area in dispute, was caused by foundation movement.”
- Product terms interpretation secondary · not upheld“The FSP's policy is clear and unambiguous. Although earth movement is covered, save in certain circumstances, it is not applicable to these circumstances.”
Subjects and remedies
home or building damageno remedy
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination
Case No: 484942 Determination Page 1 of 3
Case number: 484942 15 May 2018
1 Overview
1.1 Dispute
The applicant lodged a claim with the financial services provider (FSP) for damage to
her property following a water leak in the bathroom.
The FSP accepted the claim for the leaking pipe underneath the bathroom, but
otherwise denied the claim for the balance of the damage.
This matter has been the subject of a recommendation. The recommendation was in
favour of the FSP. The applicant disputes the recommendation. A copy of the
recommendation is attached.
1.2 Issues and key findings
Is the FSP entitled to deny the balance of the applicant’s claim?
The applicant has not established a claim for the damage to the lounge room. The
FSP is entitled to deny liability with respect to this aspect of the claim.
1.3 Determination
The determination is in favour of the FSP.
The FSP is not required to make any further payments to the applicant.
Case No: 484942 Determination Page 2 of 3
2 Reasons for determination
There has been a full exchange of material between the parties and each party has
had the opportunity of addressing the issues that arise from the information
exchanged. I have attached the recommendation to this determination.
In rejecting the recommendation, the applicant maintains:
The FSP’s engineer’s report is contradictory and could not with certainty state
the tree was the cause of the damage.
The damage which occurred during the drag [drying] out period is directly
related to the damaged waste pipe leak and that flooded both inside and
outside the home.
That the FSP had entered into a binding agreement with the work agreed upon
and that the applicant had paid the excess in response to this.
This determination follows consideration of all information exchanged and is based
on what is fair i n the circumstances, having regard to the relevant legal principles,
terms of the policy, good industry practice and where applicable, prior
determinations.
2.1 Is the FSP entitled to deny the claim in relation to the lounge room?
Onus is on the FSP to establish an exclusion applies
There is no dispute that the property had water damage. The FSP has accepted the
water leak damage to the property. The FSP accepts there was a leaking pipe
underneath the bathroom but says the damage to the lounge was not caused by the
leak. The FSP says the damage was caused by earth/foundation movement which is
excluded from cover.
I agree with the findings contained in the recommendation.
All experts appointed by both parties agree, the property is built on reactive clay
soils, which shrink and expand dependent on the moisture it contains. This
movement can cause cracks in property.
I have considered the differing opinions between the experts based on consideration
of the proximate cause of damage
On balance, I find the FSP’s expert , C, more persuasive than the applicant’s expert
BE. T he contradictions of BE’s report ma de by C, have not been refuted by the
applicant. I agree with the findings in the recommendation. The damage to the
lounge, in my view, did not arise beca use of the leaking pipe. I accept that most likely
the damage arose because of earth movement.
FSP is entitled to deny the claim
I agree with the recommendation and I am satisfied the damage to the lounge room,
the area in dispute, was caused by foundatio n movement. Although earth movement
is covered in certain circumstances under the FSP’s policy, I am satisfied on the
Case No: 484942 Determination Page 3 of 3
balance of probabilities that the cause of this movement was seasonal factors
described by C in his report and not as described by BE in his report.
In view of this, I agree with the recommendation and the FSP is entitled to deny the
claim.
Recommendation
Case No: 484942 Recommendation Page 1 of 10
Case number: 484942 9 October 2017
3 Overview
3.1 Dispute
The applicant lodged a claim with the financial services provider (FSP) for movement
damage to her property following an escape of liquid from the bathroom.
The FSP partially denied cover for the damages sustained to the lounge, saying the
damage was not the result of the leak. Rather the damage was caused from highly
reactive clay foundation soil causing differential foundation movements due to:
nearby trees and vegetation
seasonal changes.
The applicant disagrees and says water ingress from the leak caused its damage.
Accordingly she seek the FSP repair damages caused by the leak.
3.2 Issues and key findings
Is the FSP entitled to deny the claim?
On balance, I accept:
while various experts have provided their opinion on the cause of damage, I find
the FSP’s engineer (C) more persuasive
C ’s report says foundation movement was the proximate cause of damage to
the lounge
damage is not attributed to a single leak event (pipe leak)
the policy does not provide cover where the proximate cause is foundation
movement.
For this reason, the FSP is entitled to deny the cover for the damages sustained to
the lounge.
3.3 Recommendation
This recommendation is in favour of the FSP.
Case No: 484942 Recommendation Page 2 of 10
4 Reasons for recommendation
4.1 Is FSP entitled to partially deny the claim?
Applicants established a valid claim
It is an accepted principle of insurance law the applicant bears the onus of
establishing, on the balance of probabilities, she suffered a loss caused by a risk
covered under the policy. This is called a valid, or prima facie , claim.
The FSP accepts a water leak damaged parts of the property. Given this, I am
satisfied the applicant has established a valid claim.
The FSP says however the cause of the damage to the lounge was not the water
leak.
Accordingly, it falls to the FSP to demonstrate, on the balance of probabilities that the
disputed damage was caused by a policy exclusion.
Property has been subject to movement and cracking damage
The applicant contacted the FSP to lodge a claim on 2 August 2016 for damage
related to a leaking pipe underneath the bathroom. The FSP accepted the claim and
engaged a builder to report on the nature and extent of damage. Parties agreed to
hold repairs for a six months drying out period before finalising a scope of works and
commencing repairs.
The applicant noticed further cracks to the concrete slab and requested a re-
assessment, subsequently the FSP engaged its engineer (C) to report further. Due to
findings of C’s report, the FSP declined cover for cracks to the lounge area (zone 2).
Experts have provided differing opinions over zone 2
All experts appointed by the parties agree the property is built on reactive clay soils
which changes in moisture. However, the experts have provided differing opinions
about what caused the differential foundation movement.
C says the likely factors contributing to the differential foundation movements were:
seasonal moisture changes
drying effect of the adjacent trees.
Furthermore C concluded:
a heave has not occurred as there were no diagonal cracks in the walls.
articulation joint at the northwest corner of the lounge and floor levels taken
suggest the east end of the lounge room extension has settled.
Subsequently the applicant engaged her own engineer (BE) who reported the leaks
in the subfloor was the likely cause of the damage. BE says:
no cracks to lounge eastern wall (W3).
lounge eastern wall (W3) heaved up above concrete paving line.
olive tree did not affect the lounge or its footings.
Case No: 484942 Recommendation Page 3 of 10
BE discounts C’s observation in relation to close proximity of trees, in doing so, BE
states the trees are no threat to the foundations.
Proximate cause of damage
In order to determine whether the applicant’s claim falls within an insured event, it is
necessary to determine the proximate cause of the loss. What is the proximate cause
of the loss is the question of fact depending upon the circumstances of each case.
It is well established that a proximate cause is not necessarily the first or last or the
sole cause of the loss. It is the effective or dominant or operative cause of the loss. If
there are several causes operating contemporaneously, then each must be
examined for the qualities of predominance and efficiency as the active efficient
cause that sets a relevant train of events in motion.
Courts have said that if one cause would have resulted in the harm in any case and
the other would not have done so in the absence of the first, then the first is the
proximate cause.
Proximate cause of the lounge damage was foundation movement
The FSP relies upon the general exclusion contained within the policy. Particularly it
says the policy does not cover loss or damage caused by or as a result of:
erosion, vibration, subsidence, landslip, landslide, mudslide, collapse, shrinkage or any
other earth movement.
However the FSP says it will cover subsidence damage to the home if it is caused by
the insured event of burst pipes, leaks and overflows.
Whilst a leak report, obtained by the FSP, identified numerous instances where the
downpipes discharged stormwater onto the ground, the discharge was not located in
close proximity to the lounge.
In the current dispute, C says floor levels contradicts BE’s theory Wall 3 heaved. I
accept C’s findings and on balance I find C more persuasive. This is particularly
because:
if moisture increased in foundation soils as a result of water ingress, the soils
would be expected to have swelled (rather than shrunk), resulting in local
heave.
floor level survey in vicinity of the leak show local heave has not occurred
there are several trees in close proximity to the property
there has been a relative settlement towards the eastern region of the house,
which is in the direction of a number of medium to large size trees.
BE have used the rule of thumb that the height of the tree is less than the
distance from the centre of the tree to the residence
The shape orientation of the lounge room cracks and the opening of the top of
the articulation joint suggests that subsidence has occurred at the east end of
the lounge, near the trees and not at the west end of the lounge near the
escape of water event.
In these circumstances, applying relevant legal principles, as foundation movement
would have occurred in the absence of the leaking pipes, then I am satisfied the
Case No: 484942 Recommendation Page 4 of 10
proximate cause of the loss was the foundation movement. The documentation
suggests the foundation movement was independent of any damage caused by the
pipe leaks.
FSP is entitled to partially deny the claim
Having considered the material provided, I am satisfied the disputed damage to the
property was caused by foundation movement. I am also satisfied the material
establishes the proximate cause of the disputed damage to the property was caused
by foundation movement.
The FSP’s po licy is clear and unambiguous. Although earth movement is covered,
save in certain circumstances, it is not applicable to these circumstances.
There may be circumstances in which it is proper to conclude that there are two
causes which are equal or at least nearly equal in their efficiency in bringing about a
harm. In the current dispute however, I am satisfied foundation movement can
properly be described as the effective cause of the loss. It is clearly the most decisive
cause. I am therefore satisfied on the balance of probabilities, the cause of
movement damage was by seasonal factors described by C as above.
Therefore, having considered the material provided and the FSP’s policy terms, I am
satisfied on the balance of probabilities, the FSP was entitled to deny the claim.
Case No: 484942 Recommendation Page 5 of 10
5 Supporting information
5.1 Key Documents
Record K ey points
Applicant ’s plumber ( V )
21 - 01 - 2017
Came out to find water leak issue. I then broke the tiles on the side
of the bath after I filled bath to then let water go.
I found the water then visible coming from outside of home with
large amount of wat er leaking under the slab into the living space.
This was due to the crack in the bath waste pipe. The water was
then travelling throughout the laundry, toilet and hall area.
Now made repairs of both waste, tested no further leaks.
FSP ’s engineer ( C )
Report 1
02 - 03 - 2017
We observed several 2 to 3 m high tree in close proximity to the
lounge room.
We observed articulation joints (AJ) in the brickwork at the
junctions bet ween the original residence and the lounge room
extension.
The AJ was 10mm wide at the top and 0 mm wide at the base.
No cracks were obs erved to the exterior brickwork.
We observed evidence of a wat er leak to the bathroom. Swelling of
the base of the vanity adjacent to the bathtub was evident.
Hairline to 0.5mm wide cracks were observed to the tiles at the
northeast and southeast corners of the bathroom.
We observed mould to the base of the south wall of bed 4 and on
the adjac ent furniture. The mould (to zone 3) was located on the
north face of the wall adjacent to the bathtub.
We observed a cr ack in the north wall of the lounge that extended
into the lounge ceiling. The previously repaired crack was located
at the position of the articulation joint in the brickwork. A crack up
to 6mm wide was observed to the cornice on the west wall of the
loun ge.
We observed aged cracks up to 2mm wide to the floor tiles at the
northwest corner of the lounge and along the junction between the
lounge and the dining room. No movement joint in the tiles was
present at the junction between the lounge and the origina l
residence.
Tile Joints
Australian Standard AS3958.1 - 1991 - Guide to the Installation of
Ceramic Tiles requires a movement joint in the tiled surface to
match discontinuities in the substrate, to cater for differential
ground movement.
At the junction where the lounge room slab (the extension) was
joined to the dining room slab (t he original slab) there is a
discontinuity in the substrate (t he slabs). No movement joint was
provided at this location; refer to Figure 15. Accordingly, it is our
opinion that the floor tiles do not comply with the current standards
or the standards that were in place when the extension was
constructed in the early 1990's.
Case No: 484942 Recommendation Page 6 of 10
Trees
According to Clause 82.3 of AS2870 - Australian Standard
Residential Slabs and Fo otings, planting of trees should be
avoided near the foundation of a building or neighbouring building
on reactive sites as they can cause damage due to drying of the
clay at substantial distances.
It is our opinion that the trees adjacent to the lnsured' s residence
do not comply with the above recommendation from the current
standard.
We have highlighted the lack of complianc e with the current
standards to notify the Insured and the Insurer that damage to the
residence is more likely to re - occur if the r esidence is not upgraded
to the current standards; i.e. if the drying effect of the trees is not
addressed.
Downpipes
It is our opinion that many of the downpipes discharging
stormwat er from the lnsured's roof do not comply with the above
requirements of the BCA; as the downpipes discharge water
directly onto the ground rather than to the legal point of discharge.
Cause of damage to zone 1
Based on our review of the leak det ection report, it is our opinion
that the cracks to the bathroom wall tiles and th e swelling of the
vanity base joinery was caused by escape of liquid from the
shower waste pipe and the bathroom waste pipe. The proximity of
the damage to the leaks supports our opinion.
Cause of damage to zone 2
We understand that water that escaped from the bathroom
migrated to the west end of the lounge/east end of the dining room;
however, it is our opinion that heave has not occurred at this
location. If heave had occurred, there would have been diagonal
cracks in the dining room.
The width of the se paration gap to the top of the articulation joint at
the northwest corner of the lounge in Figure 5 suggests that the
east end of the lounge room extension has settled. No evidence of
heave at the west end of the lounge/east end of the dining room
was obse rved; no diagonal cracks in the dining room were evident.
Accordingly, it is our opinion that the cracks to zone 2 occurred as
a result of settlement of the east end of the lounge room extension;
rather than heave at the west end of the lounge.
Ground mo vement occurs when one area of soil experiences a
different volumetric change relative to an adjacent area of soil. The
Albanvale area is generally composed of reactive clay soils.
Reactive clay soils expand when moisture is added, causing
heaving of found ations. Conversely, reactive clay soils shrink when
moisture is extracted, causing settlement of foundations. This is
commonly described as ground movement.
Increases in soil moisture result in heave while reductions in soil
moisture result in settlement. As settlement of the east end of the
lounge occurred as a result of a reduction in soil moisture, the
settlement is not related to escape of liquid; escape o f liquid
increases soil moisture. It is our opinion that the settlement
Case No: 484942 Recommendation Page 7 of 10
occurred as a result of seasonal moisture changes and trees. The
proximity of the trees to the east end of the lounge supports our
opinion.
Whilst leak report identified numerous inst ances where the
downpipes discharged stormwater onto the ground, the discharge
was not located in close proximity to the lounge.
The leaks to the stormwater pipes were also not located in close
proximity to the lounge.
Cause of damage to zone 3
It is our opinion that the mould to zone 3 was caused by escape of
liquid from the shower waste pipe and the bathroom waste pipe.
The proximity of the damage to the leaks supports our opinion.
FSP’s leak report (A)
05 - 12 - 2016
Prior to testing insured stated that, during use of the bath, wat er
pools on the bathroom and laundry floor tiles (appendix 2,3) and
also appears to discharge in to the soil external to the south east
comer of the laundry, at the east side of the house (appendix 4)
where a large crack has star ted to appear in the internal plaster
wall and the expansion join in the external brickwork has started to
separate, indicating foundation movement.
Visual inspection was conducted to property.
At the southwest corner of the carport, at the south side of the
house, the Down pipe which picks up the entire carport space at
the south side of the house discharges on to the concrete driveway
(appendix 5). At the nort hwest corner of the house the verandah
roof which picks up the roof space external to the north side of the
house, discharges on to the soil external to the northwest comer of
the house (appendix 6). An overflow pipe has been installed to the
gutter at the northeast corner of the garage which discharges on to
the ground (appendix 7).
The roof for the garden shed in the backyard has had no guttering
or drainage installed, allowing water to discharge on to the ground
(appendix 8).
No guttering or drainage has been installed to the small roof above
the outside toilet external to the nort heast corner of the garage
(appendix 9).
CCTV camera inspection to PVC stormwater line was found to be
holding mud and wat er in a majority of sections of the line giving
the camera poor vision.
Below the down pipe external to the bedroom at the west side of
the house, a large crack was found in the PVC riser (appendix 10).
CCTV camera inspection was conducted to the sewer line.
In the shower waste pipe a large crack was identified (appendix
12).
Due to the amount of grease built up in the small branch between
the ORG ex ternal to the northeast corner of the kitchen and the
main sewer line, the camera was unable to gain clear vision
(appendix 13).
Testing was conducted to the waste pipe of the bath where water
was found to penetrate through the join of the waste pipe and b at h
(appendix 14).
Case No: 484942 Recommendation Page 8 of 10
Static test was then conducted to the bath where wat er was found
to pool below the floor tiles when viewed via thermal imaging
(appendix 15) water would then eventually escape through the
brick wall around the bath waste external to the northeast comer of
the bathroom (appendix 16) and also drip down in to the soil
external to the southeast corner of the laundry (appendix 17)
where the cracking to plaster and separating of the expansion join
can be seen.
It appears as though the majority of the int ernal damage is due to
the leak to the bath waste, based on previous report to bat hroom
by A and recent findings.
FSP ’s engineer ( C )
Report 2
16 - 06 - 2017
We reviewed the lns ured's engineers report prepared by BE dated
03/05/ 2017.
Wall W3 has lifted (heaved)
We note that BE state that W3 has lifted. Based on the floor levels,
we are of the opinion that W3 is lower than the west end of the
lounge and that W3 has settled (sunk) rather than lifting/heaving.
BE are of the opinion that the northwest corner of the lounge
lifted/heaved due to the wat er from the bathroom saturating the
ground in this area. The floor levels shown in Figure 3 contradict
this theory.
The highest floor levels are in bed B4 (+ 36mm) and at the south
end of the kitchen (+ 37mm) . The floor levels at the northwest
corner of the lounge where BE maintain heave has occurred are
approximately +15mm. If BE were correct, we would expect to see
the highest floor levels at the northwest corner of the lounge. The
highest floor levels are a t the southwest corner of the kitchen,
which is not located in close proximity to the bathroom leak.
ongoing seasonal moisture changes and trees have caused some
additional floor level variations,
ongoing disch arge from disconnected downpipes has caused
some additional floor level variations and
in 2017 the leaking pipe has locally caused some additional ground
movement in the bathroom area.
There is a high point (ridge) in the floor tiles along the junction
between the lounge and dining rooms
We agree th at locally, this is a highpoint, but globally, it is more of
a low point; compared to the levels in bed 4 and in the kitchen.
Unfortunately for BE and C, the floor levels throughout the house
vary wildly and the pattern does not neatly match any simple
hea ve/settlement theory relating to trees and leaking pipes.
There is an established 4.3m high tree (tree T1) 4.5m to the east
of wall W3
We agree that T1 is relatively mature. BE are of the opinion that
the tree is too far away to have caused any movement of the
lounge. BE have used the rule of thumb that the height of the tree
is less than the distance from the centre of the tree to the
residence. However, this rule of thumb should be modified when
there are rows/groups of trees; as there is at the lnsured's property.
Case No: 484942 Recommendation Page 9 of 10
Neither BE nor C can conclusively prove or disprove that the trees
adjacent to the lounge have or have not contributed to the lounge
room movement.
Based on the width of the crack at the northwest corner of the
lounge, after the lounge was con structed either the west end has
lifted, the east end has sunk or a combination of both has
occurred. The floor levels shown in Figure 3 do not support the
theory that the west end has heaved as a result of the bathroom
leaking pipe.
We maintain our opini on that trees have contributed to settlement
of the east end of the lounge.
The northwest corner of the lounge lifted (heaved) due to
swelling of the underlying clay soils
We disagree, refer to item 1 response above.
We also note that BE have used the vol ume of water that escaped
to justify their opinion. The volume of water that escaped has not
been established.
BE have used the location of the bathroom leak to support their
opinion. We noted that the bathroom leak was not located in close
proximity to a ll the highpoints in the slab.
FSP ’s engineer ( C )
Report 3
16 - 06 - 2017
Neither C nor the Insured’s engineer have any doc ument ation that
confirms what the floor levels to the residence to the extension
were (prior to the escape of Liquid Event in January 2017).
Accordingly, both BE and C have had to assess the current floor
l evels and make assumptions on whether the slabs have heaved
or settled as a result of the escape of liquid events.
M took floor levels on 15/03/2017. The levels taken by M are not
consistent with BE’s theory that heave occurred at zone 2. The M
floor level s are consistent with the C theory that the east end of the
extension settled.
The shape orient ation of the lounge room cracks and the opening
of the top of the articulation joint suggests that subsidence has
occurred at the east end of the lounge, near th e trees and not at
the west end of the lounge near the escape of wat er event.
Applicant’s engineer
report (BE)
03 - 05 - 2017
During out visit we observed the following:
A separation gap in the brickwork articulation joint bet ween walls
(W1) and (W2) at the corner from outside, starting with 0.00 mm
gap at 340 mm above soil level and finishing at the underside of
eave board (approx. 2500mm high) with a 15mm gap.
A similar crack ranging from 1mm near the floor to 5mm at the
ceiling.
No cracks to lounge eastern wall (W3).
Lounge eastern wall (W3) has been heaved up above concret e
paving line.
A raised ridge line formed in the floor tiles with a 2 - 4 mm
separation gap within the tiles grout bet ween the dinning and the
lounge rooms.
The presenc e of an established 4.3 high olive tree wit h a 4.5 – 5 m
canopy and 230mm diameter trunk. The tree is situated at 4.5m
from the lounge eastern wall (W3).
Case No: 484942 Recommendation Page 10 of 10
Considering the description and the locations of the damaged
bathroom pipe and the amount of water leaking under the slab and
floating into the lounge, laundry and bathrooms and with referenc e
to all reports; in our opinion we are strongly convinced that the
corner bet ween wall 1 and wall 2 has been raised up and
developing the wall crack due to the swell of the saturated cla yey
foundation, taking int o consideration that the lounge room slab
edge edge beams are not continuous being a later extension to the
original house.
We do not think the olive tree east of the lounge eastern wall is
affecting the lounge room or its footing s due to the tree size and its
distance away from wall.
We also strongly recommend that a moisture test to be carried out
to check the moisture level in all affected walls and the wetted slab
areas and to be dried as soon as possible.
Keeping in mind a pos sible weakening of the slab reinforcement
due to water soaking which would cause possible future
developing rust within the slab reinforcement.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.