Home / Financial Firm (Unknown - Insurer) / Determination 477771
Determination 477771
Water leak claim declined under leaking shower base exclusion
Summary
A main bathroom leak was declined under the shower base exclusion after the FSP's experts traced it to a failed waterproof membrane. AFCA upheld the decline but ordered $270 exploratory costs, refund of the $500 excess if not already paid, and interest.
The proximate cause was membrane failure, an excluded shower base defect, but the exploratory costs benefit applies where a leak is not covered.
Issues
- Claim denial primary · not upheld“The FSP is entitled to decline the claim for water damage arising from the water leak in the main bathroom.”
- Poor communication secondary · not upheld“There was insufficient evidence to establish the FSP authorised or asked the applicant to carry out repairs before assessment.”
Subjects and remedies
pay claimpay interestrefund fees or charges
Related
All Financial Firm (Unknown - Insurer) determinations · Find similar determinations
Text of the determination
Determination
Case No: 477771 Determination Page 1 of 8
Case number: 477771 12 February 2018
1 Overview
1.1 Dispute
The applicant held a home building and contents insurance policy with the financial
services provider (FSP). On 15 March 2017, the applicant lodged a claim for water
damage to his home building, following a water leak in the main bathroom.
The FSP has declined the claim on the basis the damage was caused by a leaking
shower floor or base, which is a circumstance excluded from cover by the policy.
The applicant disputes this outcome, as he considers the cause of damage was a
cracked waste pipe. He seeks settlement of his claim in full. A recommendation has
been made in respect to this dispute which was substantially in favour of the FSP.
The FSP accepted the recommendation, whilst it was rejected by the applicant.
There has been a submission by the applicant in respect to the findings and outcome
in the recommendation, to which the FSP responded. I agree with the findings and
outcome in the recommendation for the reasons outlined below.
1.2 Issue and key findings
Is the FSP entitled to decline the claim?
The FSP is entitled to decline the claim. The FSP has established the proximate
cause of damage was a failure of the waterproof membra ne which, as part of the
shower base, is excluded from cover under the policy.
There was insufficient evidence to establish the FSP authorised or asked the
applicant to carry out repairs before assessment of the damage took place.
I am, as found in the rec ommendation, satisfied part of the applicant‟s costs falls
within the scope of the additional policy benefit of “exploratory costs where a leak is
not covered under insured event of „escape of liquid‟”. The FSP is to pay the
applicant $270 under this benefit.
1.3 Determination
This determination, as in the recommendation, is substantially in favour of the FSP.
Subject to the applicant accepting the determination:
the FSP is entitled to decline the claim for water damage to the applicant‟s
property arising from the water leak in the main bathroom
the FSP is to refund the applicant‟s $500 excess, if it has not already done so
the FSP is to pay the applicant $270 for exploratory costs, and
Case No: 477771 Determination Page 2 of 8
the FSP is to pay interest on $270 in accordance with section 57 of the
Insurance Contracts Act 1984 from 30 March 2017 to the date of settlement.
Case No: 477771 Determination Page 3 of 8
2 Reasons for Determination
2.1 Is the FSP entitled to decline the claim?
Applicant has onus to establish a claimable loss
As explained in the recommendation, the applicant is required to show, on the
balance of probabilities, he has suffered a loss caused by an event insured under the
policy. If he can establish this, the FSP is then required to show, on the balance of
probabilities, the claim is not covered or is otherwise exc luded under the policy.
The policy provides cover for listed insured events. Accordingly, the applicant‟s onus
is to establish his loss falls under the scope of cover of one of these events.
Applicant has established a claimable loss
The evidence is that the applicant lodged a claim for water damage. He has provided
an invoice and a quotation from his plumber (RW) to this effect. The documents are
brief but they indicate that there was a damaged drainage pipe.
The policy provides cover for „ escape of liquid ‟ (as set out in section 3.2 below) if the
loss or damage to the building is „ caused by liquid leaking, overflowing or bursting
from … any drain, fixed pipes, …, drainage and sewage systems‟ .
The FSP has not disputed the loss falls within the general scope of cover of this
insured event. In the absence of argument to the contrary, I am satisfied the
applicant has prima facie established a loss covered by the policy.
The FSP now has the burden of establishing the application of any exclusion or
condition in the policy which would entitle it to decline the claim.
Expert evidence establishes proximate cause of damage was membrane failure
The FSP considers the primary cause of damage was the failure of a waterproof
membrane. The applicant contends that it is a „ chicken and egg ‟ situation and
contends the primary cause of damage was a leak from a waste pipe or a
contribution from both the waste pipe and the waterproof membrane.
The FSP provided several reports (as set out in section 3.3 below). The applicant has
p rovided RW‟s quotation and invoice, and photographs.
As recorded in the recommendation, despite the Financial Ombudsman Service
(FOS) requesting a report on the cause of damage from the applicant, he considers
the information from RW is sufficient.
Howeve r, RW‟s documents do not identify the cause of damage. RW simply lists a
scope of works and its cost. Although RW states there is a damaged pipe, he does
not provide an opinion or identify it as the proximate cause of damage claimed by the
applicant.
It is well established at law that the proximate cause of a loss is not necessarily the
first (or the last) or the sole cause of the loss. It is the effective or dominant or
Case No: 477771 Determination Page 4 of 8
operative cause.
Where there may be two causes of damage, each cause must be assessed as to its
predominance and efficiency in order to determine what the principal cause of the
train of events that were set in motion, which resulted in the damage, was.
Courts have held that if one cause (A) would have resulted in the damage and the
other cause (B) would not have done so in the absence of the other (A), then A is the
proximate cause. Further, if there are equal causes of damage and one cause is
covered by a policy and the other is not so covered, then a claim will not be met
under the policy.
If I am satisfied, on the evidence in this matter, that the main bathroom membrane
was faulty, then that would be the proximate cause of the damage.
The r ecommendation found that the FSP‟s builder (RN), leak detection expert (AS)
and loss assessor (KS) report:
the applicant‟s photographs show long term extensive damage across the
chipboard flooring and no crack in the waste pipe
if water was escaping from the waste, it would run downwards and cause
localised damage to the chipboard floor around the waste area
as the entire chipboard floor of the recess has severe water damage, this is
more consistent with waterproof membrane failure
KS says RW advised there was a pinhole in the area where the grate within the
waste pipe sat. KS says RW agreed it was most likely a waterproof membrane
failure which caused this small gap in the grate.
The damage observed in the available images is consistent with the findings by the
FSP‟s experts. I agree that there is no visible crack of the pipe in the photograph.
There is what appears to be a pinhole. However, the evidence indicates this was
likely caused by the membrane failure.
There is no evidence to refute the findings from the FSP‟s experts that the ensuite‟s
waterproof membrane has not failed, but the evidence indicates that the main
bathroom‟s membrane had and, on balance, has caused the claimed damage.
Accordingly, I am satisfied the FSP has established the proximate cause of damage
was a leak through the waterproof membrane of the main bathroom, which is an
integral part of the shower base. Therefore, the FSP is entitled to decline the claim
under the exclusion for „ loss or damage to, or caused by, a leaking shower floor or
base ‟ .
No evidence FSP advised applicant to proceed with repairs
I agree with the findings in the recommendation. The applicant says that on the day
he lodged the claim, the FSP authorised him to engage a plumber to repair the
damage. He says he acted in good faith in order to get the repairs done and he had
no reason to believe the FSP would reject the claim.
He says the FSP‟s assessor visited six days later and at that time the work was
already in progress. He says if the FSP had sent out the assessor when RW started
the repairs, the FSP would have been able to make a „ valid evaluation ‟ .
Case No: 477771 Determination Page 5 of 8
KS says the delay in sending an assessor had been due to several bookings
following a recent Sydney hailstorm event and this was discussed with the applicant
at the time. KS also says the FSP did not advise that it would accept any cost of the
plumbing work.
On the day the claim was lodged (15 March 2017), there were two telephone
conversations. According to the audio recordings of both conversations:
the plumber was already doing works in the main bathroom when the applicant
first called to lodge the claim
the FSP did not authorise any repairs and it only requested the plumber provide
a report and a breakdown of costs of the repairs already completed.
It could be speculated that the plumber‟s works may have prejudiced the assessment
of t he damage, but I am satisfied the experts‟ findings based on the available
evidence are reasonable and clear as to the cause of damage.
The excess was paid on 15 March 2017. There is no evidence to show the FSP
represented to the applicant this meant the claim was accepted. The FSP is required
to refund the applicant the $500 excess if it has not done so.
FSP to pay applicant $270 under additional policy benefit
The recommendation correctly pointed out that the policy contains an additional
benefit (as outlined in section 3.2 below) for exploratory costs where a leak is not
covered under the insured event „ escape of liquid ‟ . I am satisfied this would be
applicable, considering my finding that the FSP is not liable for the loss as a result of
the leak.
This benefit covers „ the cost to locate the source of liquid escaping or overflowing at
the insured address ‟ .
It is not clear how much of RW‟s work would have been exclusively exploratory
works. However, based on the audio recordings, it appears the work RW carried out
on 15 March 2017 helped the applicant have an idea of the apparent cause of
damage and its extent.
In my view, it is fair in all circumstances to consider that the works RW carried out on
15 March 2017 would most likely have gone towards exploring the source of the leak.
Based on the invoice provided by RW, this would have been at a cost of $270. The
FSP is liable to pay the applicant this amount and any applicable interest.
Case No: 477771 Determination Page 6 of 8
3 Supporting information
3.1 FOS approach
There has been a full exchange of the relevant material between the parties and
each party has had the opportunity to address the issues raised.
All the provided material has been read and considered. The parties have raised
numerous issues in their submissions to FOS. For the purpose of this determination,
commentary is restricted to only those issues considered relevant to the outcome.
3.2 Relevant terms from product disclosure statement
Escape of liquid
We cover We do not cover
Loss or damage to the building caused by
liquid leaking, overflowing or bursting from
any of the following:
…
any drain, fixed pipes, roof gutters or
guttering and rainwater downpipes,
drainage and sewage systems;
…
baths, sinks, toilets and basins;
…
Exploratory costs
We will pay the reasonable cost of locating,
at the insured address, the source of the
escaped liquid and to repair and restore
the damage to the building caused by our
exploratory work but only if the escape of
liquid is covered under this insured event. If
the leak is not covered under this insured
event, we provide some limited cover for
exploratory costs under additional cover
„Exploratory costs where a leak is not
covered under insured event „Escape of
liquid‟‟ …
…
loss or damage to, or caused by, a
le aking shower floor or base, shower
cubicle walls, shower glass screening
or doors;
costs if you repair or renovate a
damaged area of the building before we
can inspect it and find the cause;
…
…
Exploratory costs where a leak is not covered under insured event ‘Escape of
liquid’
We cover We do not cover
We will pay the cost to locate the source of
liquid escaping or overflowing at the
insured address and to repair and restore
the damage to the building caused by our
exploratory work if the escape of liquid first
happens during the period of insurance.
The most we will pay is $1,000 for each
Loss or damage caused by flood if you do
not have cover for insured event „Flood‟.
Case No: 477771 Determination Page 7 of 8
incident.
If you make a claim under this additional
cover, no excess applies.
Note: We will not pay extra under this
additional cover to repair or rebuild
undamaged parts meaning that the section
„When we will repair or rebuild undamaged
parts‟ on page 47 does not apply
3.3 Key points on relevant expert material
Record Key points
FSP’s loss assessor
(KS)
Report
21 March 2017
It is possible the wat erproof membrane failed and caused movement
and cracking to the drain pipe.
It is possible the waste drain has been leaking for some time.
There is no resultant damage to the kitchen ceiling directly under the
[main] bathroom recess.
There is water damage to the laundry ceiling, which is directly under the
ensuite shower. There may be a possible second leak.
FSP’s leak expert
(AS)
Leak det ection report
22 March 2017
The shower tray in the ensuite was dye tested and the membrane held
the test.
The flood test to the shower screen failed. It leaked bet ween the screen
and glass. This wat er leaks onto the bathroom floor and sits behind the
toilet. However, there was no increase of water below in the laundry, so
it appears the membrane in the ensuite is working.
The water damage to the ensuite floor and laundry ceiling is believed to
be caused by the main bathroom shower leak.
No dye or flood test was done to the main bathroom as there is no floor
in the shower. Works had already been started, the waterproofing and
waste had both been removed.
The issue may have been membrane failure around the waste, as the
particleboard flooring is damaged.
FSP’s builder (RN)
Report
28 March 2017
RN can see no evidence in the applicant‟s phot ographs of any crack to
the waste that would cause the damage.
The applicant‟s photographs show long term damage to the chipboard
flooring. It appears the membrane was applied over this flooring.
Without the evidenc e of a crack to the waste pipe, the membrane has
failed some time ago and caused the chipboard flooring to rot.
If the pipe was cracked, there would have been major damage to the
kitch en ceiling and pantry, which are directly below.
There is damage to the ceiling of the laundry bulkhead. This is below
the ensuite bathroom, which passed flood and pipe pressure testing at
the time.
On site, damage to the chipboard flooring under the ensui t e was not ed.
It appears to be old and to have leaked in the past.
The damage has been the result of membrane failure.
FSP’s loss assessor
(KS)
Report
28 March 2017
If water was escaping from the waste, it would run downwards, with a
possible damaged area of chipboard floor around the waste area only.
The entire chipboard to the floor of the recess has severe water
damage. This is more consistent with a waterproof membrane failure.
KS contacted RW, who said the waste pipe was intact and no cracks
were foun d. RW advised of a gap or pinhole found in the area where
the grate within the waste pipe sat.
Case No: 477771 Determination Page 8 of 8
KS commented if the issue was wit h grate/waste pipe, one would see
water run directly downwards, not up and across the entire chipboard
floor of the recess. RW a greed on this.
RW agreed the gap in the grate may well have been brought about by
some movement due to a long term leakage as a result of the failure of
the waterproof membrane.