Claim declined for stump and floorboard damage attributed to corrosion and gradual deterioration
Text of the determination
Determination
Case No: 477597 Determination Page 1 of 7
Case number: 477597 22 March 2018
1 Overview
1.1 Dispute
The applicant lodged a claim under her home insurance policy with the financial
services provider (FSP) after her property was inundated by stormwater in 2013. The
FSP accepted the claim and cash settled the applicant for the damage it accepted
had been caused by the storm.
However, the FSP denied cover for damage to the concrete stumps and timber
floorboards at the property. The FSP says this damage was caused by factors which
are excluded under the policy (such as wear and tear, corrosion, and gradual
deterioration).
In February 2016, the applicant notified the FSP that a broken stormwater pipe had
been discovered at her property. She considers that the damage to the stumps and
floorboards first identified in 2013 was caused by the leaking pipe.
After carrying out further investigations, the FSP maintained its previous denial, on
the basis that the relevant damage was not caused by the leaking pipe.
1.2 Issues and key findings
Is the FSP liable for the damage to the stumps and floorboards?
The available information establishes that the damage to the stumps and floorboards
was caused by corrosion and gradual deterioration as a result of exposure to high
levels of moisture in the sub-floor over an extended period of time.
The proximate cause of the moisture build-up was the features of the sub-floor and
the surrounding areas (including inadequate drainage and ventilation) .
The policy excludes cover for damage caused by corrosion and gradual deterioration
in these circumstances. Accordingly, the FSP is not liable for the damage to the
stumps and floorboards.
1.3 Determination
This determination is in favour of the FSP.
The FSP is not required to take any further action.
Case No: 477597 Determination Page 2 of 7
2 Reasons for determination
2.1 Is the FSP liable for the damage to the stumps and floorboards?
Applicant has established a prima facie claim
The applicant‟s policy provides cover for accidental damage to her home, subject to
the exclusions set out in the policy. In this context, „accidental damage‟ means
damage that is not intended or expected.
The information provided by the parties confirms there is:
severe damage to the concrete stumps supporting the single storey extension
at the west side of the property
distortion and cupping damage to the timber floorboards in the rooms above the
concrete stumps.
There is no suggestion that this damage was intended or expected. Accordingly, the
applicant has established a valid (or prima facie ) claim for accidental damage under
the policy.
In these circumstances, the FSP will only be entitled to deny the claim if it can show
that, on the balance of probabilities, it is entitled to rely on a policy exclusion.
FSP ’s liability depends on proximate cause of damage
The FSP says it is not liable for the damage to the stumps and floorboards because
the policy excludes cover for:
wear, tear, rust, corrosion, or gradual deterioration
damage directly or indirectly caused by faulty design or workmanship.
In order to deny liability, the FSP must show that the proximate cause of the damage
(that is, the dominant, effective, or operative cause) is one of the excluded factors
outlined above.
Parties disagree about source of moisture in sub-floor area
The reports provided by the parties‟ engineers confirm that the damage to the
concrete stumps was caused by excessive moisture in the sub -floor area. The
excess moisture was absorbed into the stumps, causing the internal steel
reinforcement to corrode and the concrete to crack.
However, the parties disagree about the source of the moisture affecting the sub-
floor area.
The applicant says the excessive moisture levels were caused by water leaking from
a cracked PVC stormwater pipe running along the perimeter wall (which collected
rainwater run-off from the roof). The leaking pipe was discovered and repaired by the
applicant‟s contractor (IF) in early 2016.
The FSP disputes that the excessive moisture was caused by the leaking pipe. The
FSP says the design of the sub-floor and the surrounding area allowed water to pond
under the home, creating high levels of moisture over an extended period of time.
Case No: 477597 Determination Page 3 of 7
Build-up of moisture occurred naturally over extended period of time
Having carefully reviewed the available information, the panel is satisfied that the
build-up of moisture which caused the concrete stumps to corrode occurred over time
due to the features of the property.
The FSP‟s architect (MS) who inspected the property in April 2013 reported that the
earth of the entire sub-floor area was extremely moist and muddy, with water pooling
in a number of locations. MS advised that:
the ground level of the sub-floor was approximately 300 millimetres below the
surrounding external pavement and the sub-floor area was enclosed on three
sides by solid walls
these features of the sub-floor provided no opportunity for stormwater to drain
out from under the floor of the extension and allowed for limited ventilation
given the time it takes for steel to corrode and the extent of the damage
observed, it was clear that the damage had been occurring for some time.
The applicant‟ s engineer (AG), who inspected the property in late 2013, also noted
that the features of the site made the sub-floor area susceptible to inundation. AG
recommended changes to address moisture build-up, including installing an
extraction fan to improve the ventilation of the sub-floor area.
The applicant has provided extracts from reports by her building inspector (TC) in
late 2014, which refer to a possible leaking pipe at that time.
However, the photographs taken by MS and AG in 2013 suggest that they conducted
a thorough inspection of the sub-floor area, including in the vicinity of the stormwater
pipes. However, neither MS nor AG identified a leaking pipe.
Accordingly, while a leaking stormwater pipe was subsequently discovered, the panel
is not satisfied that the pipe was leaking in 2013. On that basis, the leaking pipe did
not cause or contribute to the severe damage to the stumps which was already
evident in 2013.
The engineer (SP) appointed by the FSP to reassess the claim in 2016 concluded
that the damage to the stumps was caused by the collection and retention of
moisture in the sub-floor over an extended period of time, compounded by a lack of
adequate drainage and ventilation.
SP confirmed that the damage to the stumps was severe and had occurred over a
number of years. He considered the nature and extent of the damage was not
consistent with it having been caused by the water leaking from the cracked pipe.
The available information (including the engineers‟ reports) indicates that damage
was evident to all of the sub-floor stumps, rather than being localised. This supports
MS and SP‟s findings that the damage was caused by factors affecting the entire
area.
FSP is not liable for damage to concrete stumps
For the reasons outlined above, the panel is satisfied tha t the damage to the
concrete stumps was caused by corrosion and gradual deterioration over an
extended period of time, due to the build-up of moisture in the sub-floor area.
Case No: 477597 Determination Page 4 of 7
The build-up of moisture occurred due to the features of the sub-floor and
surrounding area.
The policy excludes cover for damage caused by corrosion and gradual deterioration
in these circumstances. Accordingly, the FSP is not liable for the damage to the
concrete stumps.
In her submissions, the applicant has referred to additional damage to the property
which she considers was caused by movement of the damaged stumps.
The FSP is not liable for any additional damage as the proximate cause of the
damage was the gradual deterioration of the stumps. Further, the FSP is not liable for
any damage that occurred after the applicant‟s policy expired on 23 September 2013.
FSP is not liable for damage to timber flooring
Both the applicant‟s engineer (AG) and the FSP‟s engineer (SP) confirmed that the
damage to the timber floorboards had been caused by high levels of moisture in the
sub-floor area over an extended period of time.
As outlined above, the panel is satisfied that the build -up of moisture occurred due to
the features of the sub-floor and the surrounding area.
On this basis, the damage to the floorboards was caused by gradual deterioration
and therefore the FSP is not liable for this damage.
Case No: 477597 Determination Page 5 of 7
3 Supporting information
3.1 FOS approach to this dispute
This dispute has not been the subject of a FOS recommendation. Due to the nature
of the dispute, it has been referred directly to a panel for determination, in line with
the Operational Guidelines to the FOS Terms of Reference. The panel consists of an
Ombudsman and two representatives with consumer and insurance experience.
The panel has decided this case based on what is fair in all the circumstances,
having regard to the relevant law, good industry practice, codes of practice and
previous FOS decisions (which are not binding).
There has been a full exchange of all material information relied on for the purposes
of this determination and each party has had the opportunity to address any issues
raised by the other.
The panel has reviewed and considered a ll of the material provided by the parties.
While the parties have raised numerous issues in their submissions, for the purposes
of this determination, the panel has restricted its commentary to those issues that it
considers directly relevant to the outcome only.
3.2 Relevant expert reports
CL, loss adjusters, report dated 7 March 2013
CL inspected the home on behalf of the FSP on 7 February 2013. The report says:
“water appears to have been pooling under the dwelling for quite some time as the
stumps have been affected that are now crumbling.”
MS, architect, report dated 30 April 2013
MS inspected the home on behalf of the FSP on 26 April 2013. The report includes
photographs showing severely cracked concrete stumps. MS said the cause of the
damage was: “th e internal steel reinforcement is rusting, causing the concrete cover
to crack and explode, and in numerous locations fall off.”
MS said the stumps were on ground that was “extremely moist and muddy… with
pools of water in a number of locations”. MS said the “primary cause” of the corrosion
was that the area had no drainage and limited ventilation. MS concluded that the
corrosion “has been occurring for some time, certainly longer than the relatively
recent January 2013… rain event”.
AG, engineer, report dated 12 December 2013
AG inspected the home on behalf of the applicant in early 2013 and again in October
2013. The report concludes:
The corrosion of reinforcement in older concrete columns under houses is not uncommon and
generally proceeds very slowly unless there is significant moisture present. The inundation
event [of January 2013] and extremely long presence of ample ground moisture creates (with
oxygen) an environment for rapid corrosion of steel. Therefore while corrosion may have been
previously present, it has been greatly accelerated by the moist condition.
Case No: 477597 Determination Page 6 of 7
AG also notes cupping of floorboards, which indicates “long term moist conditions”
under the floor.
TC, building inspector, excerpts from reports
The applicant has provided excerpts from reports by TC, who inspected the insured
building on 31 October 2014.
TC says the stumps show “extensive concrete cancer”, which occurs when steel
reinforcements rust and crack the concrete. TC also notes “[s]igns of past water
pooling” and “[w]ater leaks at some poly pipe connections”.
SP, plumber, report dated 10 November 2015
SP inspected the home on behalf of the applicant SP says:
…lot of water damage to tiles and concret e stumps under house as a result of water flooding
through property from the front and water gets trapped under house, which is causing the
reinforcing metal to rust and makes the concrete post to explode and crack…
IF, mechanical tradesman, undated letter
The applicant says IF discovered and repaired a leaking pipe in 2016. IF says:
It was evident that water had accumulated under the dwelling and the area around the pylons
had become waterlogged for some time…
It was possible that a certain amount of water could enter under the hous e during heavy
downpours, but the amount of water present a fter light showers look ed out of place. Light to
heavy showers would not produce the amount of water accumulated under the house.
…I located a… PVC pipe… open and damaged.
…
This was the source of the accumulated water under the hous e that had caused the decay of
the stumps/pylons, as every time it rained, half the water falling on the roof ended up under the
house.
CL supplementary report dated 17 March 2016
CL‟s supplementary report says:
[The applicant] has informed our Office that a friend had recently accessed the subfloor area
and discovered a broken PVC storm water pipe.
…
[The applicant] is of the opinion that the previously declined aspect of this claim, being the
deterioration of concrete piers, may be attribut able to the escape of liquid from the brok en
stormwat er pipe…
Unfortunately, we were unable to view the allegedly damaged pipe, as this had been disposed
of prior to our ins pection.
SP, engineers, report dated 27 April 2016
SP inspected the home on behalf of the FSP on 12 April 2016. The report says:
[The applicant] stated that as a result of the subfloor… being flooded by a broken stormwater
pipe during [the storm of January 2013]… the concret e stumps… suffered moisture damage…
SP concludes as follows:
…the movement to the timber flooring… i s the result of constant moisture in the subfloor caused
by poor ventilation and lack of drainage…
I am of the opinion that the deterioration to the concrete stumps in the subfloor is a result of
constant moisture being present in the subfloor. This moist ure has been absorbed by the
concrete stumps and caused the steel reinforcement to corrode. I am also of the opinion that
the corrosion of the reinforcement has taken place over a long period of time, pre-dating [the
storm of January 2013].
Case No: 477597 Determination Page 7 of 7