Home / Financial Firm (Unknown - Insurer) / Determination 473489
Determination 473489
Partial denial of storm damage claim under exclusions for deterioration, workmanship and maintenance
Summary
The applicant's storm damage claim was partly denied under several policy exclusions. AFCA held the FSP liable for the front portico, ground floor light, pergola and dome-related water entry, with interest if cash settled, and rejected non-financial loss.
The FSP bears the onus of proving that an exclusion applies to the proximate cause, and it failed for the portico, light, pergola and dome water entry but succeeded for the remaining items.
Issues
- Claim denial primary · upheld
“the FSP is liable for the damage associated with the front portico, ground flooring light, pergola and water entry through the dome”
- Poor claim handling secondary · not upheld
“I do not accept the FSP unreasonably handled the claim”
- Inadequate claim investigation secondary · upheld
“The assessor's language as to the possible cause is equivocal”
Subjects and remedies
home or building damagenatural disasterpay claimpay interest
Text of the determination
Determination
Case No: 473489 Determination Page 1 of 9
Case number: 473489 25 June 2018
1 Overview
1.1 Dispute
The financial services provider (FSP) partially accepted the applicant’s claim for
storm damage to his property. The FSP denied various aspects on the basis they fell
within a number of policy exclusions.
The applicant disputes this as he says all of the damage was due to the storm.
1.2 Issues and key findings
What is the extent of the FSP’s liability?
The FSP’s liability is limited to the dam age associated with the front portico, ground
flooring light, pergola and water entry through the dome. This is because I accept
these were caused by the storm and do not fall within any policy exclusions.
Should the FSP pay non-financial loss?
The FSP is not required to pay non-financial loss because the evidence does not
show it unreasonably handled the claim.
1.3 Determination
This determination is partially in favour of the applicant.
The FSP is liable for the damage associated with the front portico, ground flooring
light, pergola and water entry through the dome. If the FSP chooses to cash settle
the claim, it is required to pay interest.
The FSP is not liable for any other damage or to pay non-financial loss.
Case No: 473489 Determination Page 2 of 9
2 Reasons for determination
2.1 What is the e xtent of the FSP’s liability ?
Applicant has established a valid claim
There is no dispute that a storm occurred and caused damage to the property. This is
particularly reflected by the fact the FSP agreed to accept the damages to a bedroom
and ensuite.
The FSP denied the balance of the claim relying on a number of policy exclusions.
These include:
gradual deterioration, including wear and tear, rust, corrosion, depreciation,
fading or deterioration from exposure to light
inherent defects, structural faults, faulty workmanship or faulty design
poor maintenance and failure to maintain the property in good repair.
The FSP bears the onus of establishing the application of the exclusions. This will
require the FSP to show the dominant, efficient or operative ca use (proximate cause)
of the damage falls within either of these exclusions.
The standard of proof is the balance of probabilities.
FSP relied on various reports
The FSP arranged an assessment of the property on 3 October 2016. There were
two follow up assessments carried out when the applicant raised concerns. The
assessor also arranged a roof assessment by ETS. ETS examined the roof on 7
October 2016 (report dated 17 October 2016).
The applicant provided reports from PBC and PS disputing the FSP’s positi on.
Based on these reports and the submissions provided, the following building damage
was denied by the FSP and is in dispute:
1. Front portico area
2. Ground flooring light
3. Side gate and Perspex fence
4. Pergola
5. Rear roller door/garage
6. Master bedroom and lounge room bulkhead areas
7. Powder room window
8. Balcony damaged tiles
9. Dome
Front entry portico
The FSP’s assessor says the water leaking could have been due to overflowing box
gutters and “what appears to be insufficient sealant existing”. ETS says it was a
combination of poor silicone works and large amounts of rainfall being channelled
into one downpipe.
Case No: 473489 Determination Page 3 of 9
There is no evidence to show that the one downpipe constitutes faulty workmanship.
Neither does ETS nor the FSP’s assessor say the insufficient sealant was the
proximate cause of the damage.
Given damage to one of the bedrooms was accepted on the basis of overflowing box
gutters, it is realistically possible this was the proximate cause of the front entry
portico. This was supported by PS.
Therefore, I do not accept the evidence shows the proximate cause to this area was
insufficient sealant. The FSP is to accept this damage.
Ground flooring light
This was affected by the water entry from the front entry portico.
The FSP’s assessor said this water penetrated through the cracks of the tiling to get
underneath the electrical components. The assessor also referred to “insufficient
silicone and fixing to light fitting may have also contributed”.
I am satisfied the water entry into this area is covered by the polic y for reasons set
out above.
The FSP’s assessor did not identify any cause of the tiling cracking to suggest a
policy exclusion may be engaged. Whilst he did refer to insufficient silicone and
fixing, I note:
he is not specific as to what was lacking
the photographs are unclear in this regard
his language regarding this was equivocal given he said “may have also
contributed”
Given this, I do not accept the evidence shows any of the exclusions are engaged.
The FSP is to accept the ground flooring light.
Side gate and Perspex fence
The policy contains the following specific exclusion within the insured event of
“Storm, rainwater and Flood”:
“Loss or damage … to retaining walls, gates, fences, paths and driveway;”
The applicant does not dispute receiving the policy or that these items fall within this
description.
Given this, I accept the FSP can rely on this specific exclusion for these items.
Pergola
PBC believes the damage is likely due to the storm.
The FSP’s assessor says there is bowing and a split to tim ber joist. He says it
“appears from natural movement and timber”.
This is difficult to accept. The property was only six years old at the time of the
damage. There is no evidence to suggest the property is affected by natural
Case No: 473489 Determination Page 4 of 9
movement in any other way. The assessor’s language as to the possible cause is
equivocal.
Given PBC’s evidence and the fact the damage manifested at the time of the storm, I
accept this should be covered.
Rear roller door/garage
The FSP’s assessor noted on inspection, this was working sufficiently. He could not
identify any aspect that was storm related.
The applicant has not provided any evidence to show or explain how the storm
affected this.
I do not accept the FSP is liable to accept this item.
Master bedroom and lounge room bulkhead
The FSP’s assessor and ETS said this water entry was due to a cracked render
along with poorly maintained balcony issues. They also referred to a silicon crack on
the capping.
They provided photographs that supported these findings.
PBC also identified a silicon crack on capping as being a possible water entry point.
PBC does not say the storm would have caused this crack.
PS identified possible water entry due to a cracked tile in the balcony and the side
being left by about 30mm. PS said this “could of been due to strong wind”. This
appears unlikely given the damage is so isolated.
Given all this, I do not accept the evidence shows the storm created an opening for
water to enter this area. Instead, the evidence is consistent with the entry being
associated with deterioration, workmanship or maintenance issues.
Therefore, the FSP can deny liability for this damage. This would include the carpet
affected in this area.
Powder room
The damage was a broken hinge. The FSP’s assessor identified corrosion and noted
it was designed in such a way to not be susceptible to wind damage or any sort of
impact.
The applicant has not provided any contradictory evidence.
Given the limited information, I am not satisfied the proximate cause of damage was
storm. The FSP is not liable for this item.
Balcony damaged tiles
According to the FSP’s assessor, the applicant had partially removed the tiles after
noticing one had cracked and having concerns about failed waterproofing. The FSP’s
assessor said the applicant agreed the cracked tile was likely due to
“weathering/general movement/age”.
Case No: 473489 Determination Page 5 of 9
With the cracked tile removed, I accept the FSP is unable to identify with precision
the likely cause of the cracked tile.
PS said the cracked tile could have been due to strong wind. Howeve r, as stated
previously, it is unclear how the damage could be so isolated.
Given the limited information, I am not satisfied the evidence shows the tiles were
damaged from the storm. The FSP can deny liability for this item.
Dome – resultant water damage
The FSP’s assessor believes the water entry from this point is likely due to poor
silicone work. ETS said the silicone should be removed and flashing used where
possible instead.
Photographs of the dome do show a significant amount of sealant used.
ETS does not specify where such flashing should be used and whether this would
have been sufficient to stop the water entry.
PBC says the dome has appropriate flashing and there is no issue of maintenance.
PBC believes entry is due to water being built in the roof space and overflowing
through the dome flashing.
Neither the FSP’s assessor nor ETS specifically say why the sealant work is poor or
what should have been done instead. There is one photograph that says there is a
“Close up of failing silicon”. It is not apparent from this photograph if it is failing or
was the cause of internal damage.
Further, ETS is equivocal in their conclusion as to the water entry. In the roof
inspection part of the report, ETS says “It is the amount of silicone applied to this we
suspect that the cause …”. When setting out their conclusion, ETS simply says all
the old silicone should be removed and more professional resealed.
It is unclear if the FSP’s assessor provides an independent conclusion or is
reiterating ETS’s finding. The language used in the “Cause of Damage” appears to
reiterate ETS’s opinion.
Given this, I am not satisfied this evidence shows on the balance of probabilities that
the proximate cause of water entry falls within a policy exclusion. PBC describes a
manner of entry that is consistent with other aspects that have been accepted. The
available evidence is unclear about where specifically the sealant broke down, what
works were insufficient or how these caused the water entry.
Therefore, the FSP is liable for the resultant damage caused by water entering
through the dome. This does not extend to the dome itself. This is because the
evidence does not show the dome was damaged from the storm.
Contents recently claimed are not covered
During the course of the dispute, the applicant sought cover for outdoor furniture,
artificial plants, pool cover and carpets.
Case No: 473489 Determination Page 6 of 9
I have dealt with the carpet. Regarding the artificial plants, the policy clearly says
these are not covered. Pool covers are specifically excluded from storm damage
under the policy.
For the outdoor furniture, there is insufficient evidence to show how this was caused
by the storm.
Therefore, I do not accept the FSP is liable for the contents damage.
FSP liable for front portico, ground flooring light, pergola and dome
After careful consideration of all the evidence and arguments, I accept the extent of
the FSP’s liability is limited for the damages associated with the front portico, ground
flooring light, pergola and dome.
If the FSP decides to cash settle this claim, interest is payable pursuant to section 57
of the Insurance Contracts Act 1984 (the Act). Interest begins from 3 March 2017,
being the date of the FSP’s final decision on the claim, until payment is made.
2.2 Was the applicant entitled to compensation for non-financial loss?
FOS may award compensation in certain circumstances
FOS may decide an FSP should compensate the applicant where there has been an
unusual amount of physical inconvenience, time taken to resolve a situation, or
interference wi th the applicant’s expectation of enjoyment or peace of mind.
FOS takes a conservative approach to compensation for non-financial loss. FOS
considers compensation should not be provided for the normal degree of
inconvenience experienced when a problem occ urs.
FSP not required to pay non-financial loss
The applicant’s email to FOS dated 21 August 2017 said the claims process has left
he and his family feeling very frustrated. This caused them inconvenience and stress.
The FSP’s submission dated 18 May 2017 set out a chronology of its claims
handling. The applicant has not disputed its contents.
Having reviewed this chronology, I do not accept the FSP unreasonably handled the
claim. Part of the claim was protracted as the applicant delayed lodging the claim and
asked the FSP to consider other damages during the course of its review. There
were also delays in arranging a suitable time to inspect the damage.
The applicant also raised concerns about the risk of mould. However, I note there is
no evidence to show there is mould or that this has caused health problems.
Further, whilst I have disagreed with aspects of the FSP’s decision, I do not accept
its position was unreasonably held. This is because it relied on expert reports that
indicated the policy would n ot respond to the applicant’s claim. In addition, the FSP’s
position on various items were substantiated.
Given all this, I do not accept non-financial loss is warranted.
Case No: 473489 Determination Page 7 of 9
3 Supporting information
3.1 Policy wording
Insured event Storm, rainwater and flood page 9
We do not cover loss or da mage:
To reta ining wa lls, gates, fences, paths a nd driveways
Caused by gradua l deteriorat ion from rainwater
Caused by water that has see ped or percolated into your building. Exclus ions page 26
Gradua l deteriorat ion, including wear and tear, rust, corrosion, depreciat ion,
fading or deteriorat ion from exposure to light
Inherent defects, structura l faults, faulty workmanship or faulty design
Poor maintenance and failure to ma inta in the property in good repa ir
3.2 Expert reports
Recor d Key points
FSP’s First Report & Scope
of Works (C)
Report
03 - 10 - 2016
In our opinion the da ma ges to the property have been cause d by strong winds
and ra in due to a poorly constructed and ma inta ined property and we believe
this to be cause of da mages. Re comme nd declining cla im.
The property is only six years old a nd located near the ocean, due to its
location maintenance should be an ongoing concern.
The da mage is consistent with poor workmanship and rain.
The resulta nt da mage has been caused by a combination of factors.
An inspection of the pool pergola has revealed what appears to be a poorly
installed structure and the only reason we be lieve t he timber bea m would sa g
would be due to an undersized bea m.
The balcony t iles had been re moved prior to event a nd insured has stated that
he did this beca use there was a previous leaking issue.
An inspection of the property by the roofer a lso stated:
Da mage to front entry porch has been cause d by poor silicone exposing holes
into t he ce iling spa ce be low and only one downpipe insta lled which cannot
handle a large a mount of rain a nd causing the water to backflow into property.
Master be droom/lounge room bulkhead a nd area above doors the da mage has
been ca used by rendering having cracks and allowing water to pen etrate into
property along with a poorly maintaine d ba lcony showing cracked t iles and
poor grouting.
Dome area da mage has been cause d by poor silicone work and needs
flashings insta lled instead of silicone.
Ensuite could not locate a cause of water da ma ge.
The building has bee n maintained in poor condit ion.
FSP’s Second Report &
Scope of Works - Reinspect
Insured has other areas of t he home which was inspected and reported to
date however this re inspect ion report is for bedroom 4 only as per request
Case No: 473489 Determination Page 8 of 9
(C)
Report
Undated
which a ppears to be consistent with overflowing gutters.
Reinspect ion to the property for Bedroom 4. Insured advised that the
cornice/wa ll stains is a result from the sa me event /first cla im however missed
on first inspect ion by attending As sessor.
Reinspect ion was take n place for be droom 4 where water stains to cornice
appears. The cornice is decorative and what appears to be plaster glass
decorative. Our inspection ide ntified water stains to the ce iling cornice a nd wall
housing the sta ined cornice.
Inspection to the roof ident ified box gutter above the be droom which appears
to have overflown from severe rain ca using water to overflow due to volume.
The box gutter was found to be clean/clear during inspection a nd no clear
faults appearing.
Th e building has bee n maintained in poor condit ion.
FSP’s Third Report &
Scope of Works - Reinspect
(C)
Report
Undated
The building has bee n maintained in poor condit ion. The resultant da mage has
been ca used by a combinat ion of factors.
Lounge room - Water da mage d sta ins to ce iling - beside skylight dome - We
ident ified some poor / insufficient silicone surrounding most of external
skylight dome and external pane ling appears to be detaching due to
insufficient fixings appear .
Roof inspection found no storm cre ated openings - as the wa ll is common to
lounge bulkhea d da mage the wall of lounge is common to bed 1 therefore
ridge capping above affected wa ll areas where like ly water has entered
through capping during heavy rains a nd silicone crack to ridge capping po int
The pool fencing Perspex has been screwe d to the metal fencing pane ls a nd
these have bee n da maged due to strong winds alt hough this is not a
recomme nded method of pool safety fencing.
T he da mage d clothes line is missing a pin/bolt considered as wear a n d tear
ma intena nce. Further, t he gara ge rolle r door a ppears to require genera l
servicing a nd in our vie w not a result from the storm event.
The balcony t iles had been re moved prior to event a nd insured has stated that
he did this beca use there was a previo us leaking issue a nd cracked t ile from
move ment a ppears to have occurred.
A n inspection by the roofer we appointed has stated the be low:
1. Da mage to front entry porch has been cause d by poor silicone exposing
holes into the ceiling space be low and only one downpipe installed
which cannot handle a large a mount of rain and ca using t he water to
backflow into property .
2. Master be droom/lounge room bulkhead a nd area above doors the
da mage has been caused by re ndering having cracks and a llowing water
to penetrate in to property a long with a poorly ma inta ined balcony
showing cracked tiles and poor grout ing .
3. Dome area da mage has been cause d by poor silicone work and needs
flashings insta lled instead of silicone .
4. Ensuite could not locate a cause of water da ma ge
In our op inion the da ma ges to the property have been cause d by strong winds
and ra in due to a poorly constructed and ma inta ined property and we believe
this to be cause of da mages. The property is only six years old a nd located
near the ocean, due to its location maintena nce should be an ongoing concern.
Most da mages to the home a ppear to be consistent with poor workma nship
and lack of maintenance
Case No: 473489 Determination Page 9 of 9
Applicants Report (PBC)
Report:
16 - 05 - 2016
Roof inspection notice silicon cra ck on capping which shows over flow of fl ood
water interring in to the house.
Master be droom - Tw o w all w ater damage affected and carpet w ater damage
affected require replacement family room first floor: w ater stains mark,
speaker rust and ceiling bulkhead damage, c learly shows w ater damage
evid ence .
Sky light Dome area - Crack gyprock and water stains on ce iling Inspect ion of
Dome area from roof space. There is no issue of ma intena nce, the dome has
appropriate flashing but it see ms over silicon to prevent any further leakage
but where the water has e nter that would be from a mount of f lood water built
in roof spa ce that has caused over flow through flashing of dome.
B edroom 4 - over flow from gutter has caused water da ma ge cornices a nd
water stain on 2 x wa lls, No any ot her maintenance concern foun d.
Outdoor pergola - see ms internal da ma ge of t imber and has got a bow - front
elevation sagging, it is due to the sto rm whe re timber has been da ma ged but
not claps a nd been secure d by prop.
Where the house located in higher sect ion of Mindarie there is stro ng wind
specia lly being storm da ma ge it clearly shows above da ma ges has bee n
caused by the storm da ma ge .