Home claim for lightning-induced power surge damage denied for insufficient evidence
Text of the determination
Determination
Case No: 457439 Determination Page 1 of 11
Case number: 457439 18 October 2017
1 Overview
1.1 Dispute
In January 2016, the applicants lodged a claim under their home insurance policy
held with the financial services provider (FSP). The claim encompassed a number of
items the applicants say were damaged as a result of a power surge caused by a
lightning strike.
The FSP denied the claim saying there was insufficient e vidence to establish the
damage claimed was a result of a power surge caused by a lightning strike.
1.2 Issues and key findings
Have the applicants established damage caused by a lightning induced power
surge?
The applicants have established damage caused by a lightning induced power surge
because:
there is no dispute that storm activity occurred on the evening in question, and
the applicants later discovered a lightning struck tree with branches resting on a
power wire
a number of electrical items and wiring appear to have failed simultaneously
there is sufficient expert evidence to establish (on balance) the majority of the
damage claimed being attributable to a lightning strike and subsequent power
surge.
What is the extent of the FSP’s liability for the claim?
For the reasons set out in Section 2 of this determination, the FSP is required to
provide indemnity to the applicants in the amount of $10,422.
Interest is not payable on this amount.
1.3 Determination
This determination is substantially in favour of the applicants.
The FSP is required to provide indemnity to the applicants in the amount $10,422
within 14 days of this determination being accepted by the applicants.
Interest is not payable on this amount.
Case No: 457439 Determination Page 2 of 11
2 Reasons for determination
2.1 Have the applicants established damage caused by a lightning
induced power surge?
No dispute a number of electrical items and wiring suffered damage
There is no dispute between the parties that a number of electrical items and wiring
suffered damage at the applicants’ property . These items, along with (where
available) the amounts claimed are listed in Section 3 of this determination.
Initial onus lay with applicants to show damage caused by a lightning induced
power surge
When lodging an insurance claim, the initial onus lay with the applicants to establish
(on balance) the loss or damage claimed resulted from an event to which the policy
responds.
In this instance, both parties agree the policy provides cover for loss or damage as a
result of a lightning strike, or a power surge caused by a lightning strike. Therefore,
the applicants need to establish (on balance) the damage claimed resulted from a
lightning induced power surge, which they say occurred on 26 December 2015.
If the applicants are able to establish this, the onus then passes to the FSP to show
why it may otherwise be entitled to deny the claim.
Available evidence establishes storm activity in the area at the relevant time
The FSP assessor confirms the local area had been affected by a tropical low
combined with a monsoon trough with embedded thunderstorms at the relevant time.
This is also supported by a local newspaper report provided by the applicants.
Power company evidence of no assistance to either party
Whilst the applicants’ power company has provided comment regarding any weather
related disturbances, this covers the period from 30 December 2015 to 1 January
2016.
However, the applicants maintain the lightning strike took place on 26 December
2015. For this reason, the power company evidence is of no assistance to either
party.
Sufficient expert evidence to establish lightning damage
For ease of reading, the expert reports provided by both parties are summarised in
Section 3 of this determination.
With regards to the experts ’ overall conclusions regarding the cause of the damage
claimed, these can be summarised as follows:
Case No: 457439 Determination Page 3 of 11
Expert Conclusion
Applicants’ electrician (EE) A lightning strike is the most likely cause of the faults due to
the timing and nature of them.
FSP ’s assessor (1 st report) The damage found appears consistent with lightning.
FSP’s electrician (PC) There was little or no evidence to support a lightning strike.
FSP ’s assessor (2 nd report) In relianc e upon PC’s report, it appears the overall damage is
unrelated to any lightning related event.
Applicants’ pressure pump
technician
The cause of this damage could be lightning strike(s) and/or
power surge.
Applicants’ electrician (KE) The damage seen is definitely lightning strike / power surge
damage.
FSP appointed independent
electrician (FE)
No signs of damage caused by a lightning strike / power s urge
were identified, but it is hard to inspect considering the time
since elapsed.
Whilst accepting the experts have differing opinions as to the cause of the damage, I
am satisfied there is sufficient expert evidence to establish (on balance) damage
being caused by a power surge caused by a lightning strike.
This is especially so considering a number of electrical items and wiring appear to
have failed simultaneously, and so consistent with some form of power surge. This
also appears to have been the FSP assessor’s initial opinion, and further supported
by EE, KE and the pump technician.
Whilst I do acknowledge the FSP suggests all electrical items plugged in would likely
be damaged if a result of a lightning induced power surge, the applicants say
unaffected appliances were protected by surge protectors.
Lightning struck tree discovered in March 2015 likely caused the power surge
In March 2015, the applicants discovered a lightning struck tree located
approximately 40 feet from where the main power box i s located on the applicants’
property. They say branches of the tree were discovered resting on the power line
leading to the power box.
The applicants have since provided photographs of the tree in question, and an
invoice to ‘remove lightning struck tree branches from service power wire’.
The FSP notes the discovery was made some three months after the claimed event,
and says it is therefore not possible to be certain as to when the associated lightning
strike took place.
I accept there was a period of time that passed prior to the applicants discovering the
tree. However, I also note the following:
satellite imagery of the applicants’ property identifies it to be a relatively large
rural block almost entirely covered by thick vegetation (trees)
Case No: 457439 Determination Page 4 of 11
considering the size of the block and the nature of the vegetation, I am satisfied
a fallen tree would not be easily identifiable.
Therefore, considering the lightning struck tree would not be immediately obvious
and the fact tree branches were resting on the power line, I am satisfied (on balance)
the tree being struck by lightning likely caused the power surge in question.
The applicants have established damage caused by lightning
For the reasons discussed above, I am satisfied the applicants have established
damage caused by a lightning induced power surge because:
there is no dispute of storm activity occurring on the evening in question, and
the applicants later discovering a lightning struck tree with branches resting on
a power wire
a number of electrical items and wiring appear to have failed simultaneously
there is sufficient expert evidence to establish (on balance) some of the damage
claimed being attributable to a lightning strike and associated power surge.
It therefore becomes necessary to consider the extent of the FSP’s liability for the
claim.
2.2 What is the extent of the FSP’s liability for the claim?
FSP liable for tree branch make-safe costs but not tree removal
I am satisfied the removal of the tree branches was reasonably required for make-
safe purposes, and to mitigate the risk of further damage occurring. In my view, it is
reasonable to assume the FSP would have undertaken this make-safe work itself
had the tree been discovered during initial site visits.
However, the FSP is not liable beyond this make-safe work because there is no
associated cover for this provided under the policy.
For these reasons, the FSP is liable for the tree make-safe works in the amount of
$341.
FSP liable for EE’s invoice
It is unclear whether the FSP initially requested the applicants to arrange for an
electrician to attend the property. However, it is clear this report provided both parties
with an initial understanding as to the extent of damage.
Whilst the FSP initially queried the cost of the report, the applicants note this cost
was actually less than the FSP’s own appointed expert.
For these reasons, the FSP is liable for EE’s invoice in the amount of $660.
FSP liable for underground cabling to water tank and spa
T here are some suggestions by the FSP’s experts that the underground cabling may
not have been installed in accordance with associated guidelines and regulations .
However, they have not provided any evidence to support these opinions.
Case No: 457439 Determination Page 5 of 11
The applicants maintain the cabling is in accordance with all associated guidelines
and regulations, and have provided a copy of the property’s certificate of occupancy.
The applicants have also provided a letter from the person who maintains their spa
and filtration system which confirms there have been no issues regarding the
electrical supply in the past 10 years. He also confirms attending the applicants’
property on 26 December 2015 (prior to the storm), and had used the spa on that
day.
I note there appears to be no dispute between all of the experts that the wiring has
been damaged. Indeed, considering the critical nature of the power supply, it does
not appear consistent that the applicants would not have addressed any issues
existing prior to the incident.
I am therefore satisfied there is sufficient evidence to establish (on balance) damage
being caused by a lightning induced power surge.
With regards to indemnity, I note EE quoted $1,232 to replace the underground
cabling to the water tank and spa (a total of $2,464) with an extra $1,273 quoted for
the hire of an excavator and associated trench digging.
However, I note KE have also quoted an amount of $1,232 to replace each of the
cables (a total of $2,264), but inclusive of digging.
Therefore, I am satisfied the FSP is liable for the lower cost to replace the
underground cabling to the water tank and spa in the amount of $2,264.
FSP liable for water tank pressure pump / controller / solenoid coils / pool
pump
It appears that following the power surge, the water pressure pump was not
operating, and the applicants arranged to collect a temporary replacement pump
from another of their properties.
Whilst the expert evidence is contradictory as to the functionality of the original pump,
I am not persuaded the applicants would travel the significant distance to their other
property (after discovering the local hardware store was out of stock) unless there
was an issue with the original pump.
With regards to the controller and solenoid coils , PC and the applicants’ pump
technician both accept the unit is faulty requiring a manual reset at intermittent
periods.
With regards to the pool pump, there does not appear to have been any specific
examination of the original unit beyond being identified as non-operational at the time
PC attended the property.
That said, it again appears inconsistent that the applicants would replace the pump if
it remained operational. I note the applicants have not claimed for the spa pumps
which they say remained operational once the temporary power supply source had
been set up by the applicants.
Case No: 457439 Determination Page 6 of 11
Therefore, when taken as a whole and the fact all items appeared to display faults
simultaneously, I am satisfied the claimed damage was (on balance) a result of the
lightning induced power surge.
Therefore, the FSP is liable for the associated costs for these items in the amount of
$4,038 ($1058 / $1,518 / $640 / $822).
FSP liable for heavy duty leads
It appears the applicants had no option but to arrange for a temporary power source
in light of the damaged underground wiring, and which the claim for the heavy duty
leads relates to.
Therefore, in my view it is fair in all the circumstances the FSP indemnify the
applicants for this cost in the amount of $100.
FSP liable for air conditioner replacement cost
The applicant’s confirm t heir claim relating to the air conditioning units is limited to
the replacement of the unit in the lounge / living room.
The available evidence suggests this unit was possibly repairable by way of replacing
the unit’s PC board. However, due to the time now elapsed it becomes impossible to
determine with any level of certainty what this repair cost would have been.
However, regarding the option of repairing or replacing the unit it appears the
applicants relied upon EE’s advice on this point, that being to replace the unit due to:
the age of the unit and so any repairs undertaken could not be guaranteed
the fact there may have been other unidentified damage.
I also note the applicants live in an area of Australia with relatively high temperatures
and humidity during the summer season. Therefore, in my view it was not
unreasonable for the applicants to proceed with the associated works. This is
especially so considering the FSP appointed assessor and electrician did not attend
the applicants’ property for anoth er approximate two week period.
For the same reason, it appears inconsistent the applicants would not have
addressed any pre-existing issue with the unit prior to the incident.
For these reasons when the evidence is taken as a whole, I am satisfied the air
conditioning unit in question was (on balance) damaged as a result of the lightning
induced power surge. I am also satisfied that it is fair in all the circumstances that the
FSP provide indemnity in line with the replacement cost of $3,019 (as opposed to the
indeterminable repair cost), but taking this in to account when considering interest as
discussed below.
FSP not liable for stove
The applicants say that following the incident, the stove takes an extended period of
time to heat up.
Whilst KE makes reference to the stove having surge damage and ‘not working 100
percent’ when he attended the property in August 2016, the FSP’s assesso r could
Case No: 457439 Determination Page 7 of 11
not identify any fault when attending the property in February 2016. The applicants
say that having worked in the electrical industry in the past, they know the issue is
related to the incident.
The issue facing the applicants is the lack of persuasive evidence to demonstrate the
exact nature of the issue and more importantly, how a power surge could cause the
issue.
For these reasons, I am not satisfied there is sufficient evidence to establish (to the
extent required) any issue with the stove is a result of the power surge in question,
and so the FSP has no liability for this aspect of the claim.
FSP not liable for hot water system
Similarly to the stove, the applicants say that following the incident, the hot water
system takes an extended period of time to heat up.
However, there is again no persuasive independent evidence to establish (on
balance) any such issue is related to the incident.
For this reason, I am not satisfied there is sufficient evidence to establish (to the
extent required) the issue with the hot water system is a result of the power surge in
question, and so the FSP has no liability for this aspect of the claim.
FSP not liable for television
In their most recent submission to FOS, the applicants suggest their television has
not been used since September 2016, and experienced problems with it prior to this
point in time.
It appears this issue was not initially raised when the applicants’ lodged their dispute
with FOS in October 2016. Further, the applicants confirm the television was
protected by way of a surge protector along with other household items unaffected by
the incident.
The issue facing the applicants is once again the lack of expert evidence as to the
actual cause of the issue now seen. Further, there appears to have been an
extended period of time from the incident occurring and the issue now raised.
For these reasons, I am not satisfied there is sufficient evidence to establish (to the
extent required) the issue with the television is a result of the power surge in
question, and so the FSP has no liability for this aspect of the claim.
Interest is not payable on total payment amount
When the amounts of the items the FSP is deemed liable for are totalled up, this
gives a figure of $10,422.
The FSP is not required to pay interest on this amount considering the applicants
have been awarded the full replacement cost of the air conditioner as opposed to the
potentially lower (but now indeterminable) repair cost.
Case No: 457439 Determination Page 8 of 11
Case No: 457439 Determination Page 9 of 11
3 Supporting information
3.1 Items claimed
Item / cost incurred Amount (incl GST)
1 x air conditioner (living room) $3,019
Underground cable to water tank pump $1,232
Water tank pump and fittings $1,058
Water tank controller (incl reprograming) $1,518
Underground cable to spa pump $1,232
Pool pump $822
Solenoid coils $640
Hot water system $Unk nown
Television $998
Trenc h digging (underground cables) and hire machine $1,273
Removal of tree branches from power line $341
Removal of tree debris $440
Electrician (EE) site visit, inspection and call out $660
Stove $Unk nown
Heavy duty leads $100
3.2 Expert reports
Applicants’ electrician (EE) 18 January 2016
Initial site inspection has found that there is no power to the pressure pump, spa
pump and living room air conditioning unit.
It is recommended the air conditioning units be replaced because the PC
boards have been damaged and there is likely other (then) unidentified
damage.
Due to the unknown damage of the wiring to spa and pressure pump, it is
recommended the undergrounds and outlets be replaced in full.
A lightning strike is the most likely cause of the faults due to the timing and
nature of them.
FSP’s assessor 1 February 2016
The living room air conditioner has been replaced due to a damaged control
board. There was no quote to repair the control board as the unit was out of
warranty, and any repairs unable to be guaranteed.
Case No: 457439 Determination Page 10 of 11
The kitchen air conditioner had been repaired by way of a fuse replacement and
the addition of plumbing items.
The applicants believe the electric range was no longer heating as fast as it
used to, but it appeared to be functioning correctly.
The applicants had replaced the bore pressure pump with one from another
property. The original pump was not available for inspection.
The irrigation controller reported by the applicants as being faulty could be
turned on, but requires inspection by an electrician.
The underground power lines to the spa and water tank were reported as
damaged by the applicants, with the associated pumps being powered by an
alternative power source.
The quote provided by EE appears high and includes replacement of a
functioning air conditioner and unrelated plumbing items.
The area had been affected by a tropical low combined with a monsoon trough
with embedded thunderstorms during the relevant period.
The damage found appears consistent with lightning.
FSP’s electrician (PC) 5 February 2016
There was little or no evidence to support a lightning strike. No specific damage
usually caused by a lightning strike was found on any switchboards, appliances
or cabling that could be visually inspected.
Various small faults were found around the property, but it was indeterminable
with the non-invasive inspection techniques used to determine if they were
caused by a lightning strike.
The underground cabling leading to a press ure pump had a fault, although the
pump itself was found to be working after off-site testing (although a loading test
could not be performed).
An irrigation controller was found to be non-functional and the screen unable to
be read. The unit had power, but no burn marks of blown components were
found. The front cover was unable to be removed for an inspection behind the
screen.
There was no power supply to the pool pump’s power point. The reason for the
lack of power could not be identified due to the installation method and location
of the cable. A further detailed inspection would be required to accurately
determine the fault.
FSP assessor 15 February 2016
PC’s report advises there is little or no evidence in support of the claim of a
lightning strike, either directly or indirectly.
The original air conditioning unit in the living room was over five years old and
no consideration given to repairs by EE. EE also believes the kitchen unit will
fail over time, but without objective evidence to support this belief.
It is understood the underground wiring found to have faults was installed by the
applicants.
It appears the overall damage is related to underground faults resulting from
installation and line placement and unrelated to any lightning related event.
Case No: 457439 Determination Page 11 of 11
Applicant’s pressure pump technician April 20 2016
The pressure pump control module is faulty, requiring pump to be manually
reset on an intermittent occasion.
The cause of this damage could be lightning strike(s) and/or power surge.
Applicant’s electricia n (KE) 8 August 2016
A lightning strike close to the bore pump and main power supply is very obvious
with fallen and damaged trees.
There is a black flash mark on the wall at a GPO.
The stove is not operating correctly.
The surge protector for the television is fused.
The outside water station is fused with a burnt out transformer and wiring
points.
The bore pump is not operating correctly.
There is no power to the water tank or spa pumps which are now being
powered by an alternative power source. The pumps are likely damaged by way
of conduit fusion.
The damage seen is definitely is lightning strike / surge damage.
Independent electrician (FE) 27 February 2017
No signs of damage caused by a lightning strike / power surge were identified,
but it is hard to inspect considering the time since elapsed.
The issues appear to have been caused by ants / moisture / general wear and
tear.
The two underground circuits to the spa and pressure pump could possibly
have been damaged by lightning, but it is near impossible to say at this point. It
could also be issues with the original installation and water ingress. Both
circuits’ cable cores are shorted out.