Claim for building cracking declined as soil settlement or pipe leak
Summary
Homeowners claimed building cracking was caused by leaking pipes, which would have been covered. The insurer declined the cracking claim as soil movement, and AFCA found the applicants had not shown on the balance of probabilities that the leaks were the proximate cause, so no amount was ordered.
Under a defined events policy the insured must first establish a prima facie claim for liquid escaping suddenly from a fixed pipe, and the preferred expert evidence did not show the leaks caused the damage.
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
Case No: 452703 Determination Page 1 of 9
Case number: 452703 22 November 2017
1 Overview
1.1 Dispute
The applicants lodged a claim with the financial services provider (FSP) for ceiling
damage and cracking to the building in 2011.
The FSP accepted the claim for ceiling damage. The FSP declined the claim for
cracking of the building because it determined the cause was shrinkage of
foundational soils over time. This falls within the policy exclusion for soil movement or
settlement.
The applicants dispute this as they say the damage was caused by leaking pipes.
1.2 Issues and key findings
Can the FSP deny the claim?
The FSP can deny the claim because:
the applicants’ policy only covers them for loss or damage caused by an insured
event
the insured event in this case is liquid escaping suddenly and unexpectedly
from a fixed pipe
the available evidence does not show the proximate cause of the cracking
damage to the applicants’ home was a leaking pipe.
1.3 Determination
This determination is in favour of the FSP.
The FSP is not liable for the applicants’ claim for cracking damage at the home.
Case No: 452703 Determination Page 2 of 9
2 Reasons for determination
2.1 Was the FSP entitled to deny the claim?
Policy provides cover for defined events subject to exclusions.
The applicants are required to show, on the balance of probabilities, they suffered a
loss caused by a risk insured against under the policy. This is known as a prima facie
claim.
If the applicants are able to establish a prima facie claim, then the onus shifts to the
FSP to show, on the balance of probabilities, it is entitled to deny the claim based on
an exclusion or policy condition.
The applicants’ policy is a defined events policy which provides cover for damage
caused by one or more of the events listed in the policy, subject to any applicable
exclusions. This includes cover for loss or damage caused by liquid escaping
suddenly and unexpectedly from a fixed pipe.
Relevant background and evidence
These relevant facts are not in dispute:
cracking occurred from 2007 or earlier
there were two fairly significant leaks found around the kitchen sink waste pipe
and near the main bathroom – testing showed a leak of 8 litres per minute and
10 litres per minute respectively
Regarding the property’s occupation from 2007 onwards, the following is relevant
and not in dispute:
the applicants resided in Brisbane from 2007
MP’s first report noted there was 34kL of water used between February 2009
and August 2011 – a typical quarterly consumption in a family home would be
between 30 to 40kL
MP’s first report also noted that in the 9 months leading to its first report dated 2
September 2011, only 4kL was recorded
the applicants’ submission to the FSP dated 12 November 2015 said the main
bathroom was not used from 2007
M P’s second report recorded the applicants’ evidence that:
- a house sitter occupied the home full time between 2007 and 2010
- home was vacant between 2010 and 2011
- home was occupied by the applicants and friends for short periods of time
During the course of this dispute, both parties have appointed experts to determine
the cause of the damage. These comprised of two engineer firms (MP and MC) and
a building surveyor.
The two engineering firms provided nine reports between them. Seven were from
firm MP and two from firm MC. The reports were completed by four authors, two from
each side. For ease of reference, I will refer to the engineering firms in this section
rather than the individual author.
Case No: 452703 Determination Page 3 of 9
I have carefully reviewed all of the experts’ reports as well as the information
provided by the parties in order to determine the proximate cause of the damage. I
prefer MP’s evidence for the following reasons.
MC does not appear to have accounted for the home’s occupancy since 2007
It is not clear MC took into cons ideration the home’s occupancy status between 2007
and 2015. In the first report, MC noted there would be significant leakages into the
soil until the pipes were repaired in 2015. MC’s second report makes a similar
comment.
However, it is clear the property was rarely used in this period given the undisputed
evidence.
MP’s reports consistently refer to this as a substantive factor in supporting the
conclusion. This is because MP expected there to be an improvement in the footing
during 2011 and 2015 as the influence of these leaks were substantively reduced in
this period of time. However, the external survey results are inconsistent with this as
the movement appears to be worsening.
Given all this, MP disagreed with the leak being the cause of damage
This is a plausible hypothesis and consistent with the available evidence.
MC does not appear to take into consideration the home’s use. Instead, MC bases
their opinion mainly on the localised heave.
In my view, MC’s failure to take into account this subs tantive factor undermines the
conclusion reached.
There appears to be evidence of settlement on the edges of the property
MC also says that if the damage was due to soil drying around the edges of the
building, it would typically show settling on the corners of the building, the northern
end of the lounge room and the south eastern end of the garage.
MC says this is not the case.
However, MP’s perimeter survey comparison results from 2011 to 2016 appears to
show this. Most corners except for the south-eastern corner shows evidence of
settlement during this period. The south eastern side of the garage settled by 20mm.
The northern end of the lounge room showed it settled by 16mm.
MC’s report dated 7 July 2016 refers to only a survey provided by another comp any.
In MC’s report dated 8 March 2017, MC says they were was only provided MP’s
report dated 22 December 2016. MP’s report of that date did not include the diagram
showing the survey comparisons conducted by MP during 2011 and 2016.
Therefore, it appears MC was not aware of MP’s comparison survey results.
MP’s evidence is preferred
Given all this, I accept MP’s reports and analysis to be more detailed and thorough
than MC. It has taken into consideration all the relevant evidence, including the
Case No: 452703 Determination Page 4 of 9
home’s occu pation during the relevant period. The conclusions it has provided are
consistent with the objective evidence, namely the external brick surveys. It has also
considered other possible causes but provided a reasonable basis as to why it
rejected them.
I ack nowledge the applicants’ argument that MC’s evidence is supported by another
expert PB. However, this is not persuasive. The substance of PB’s evidence was that
it agreed with MC’s reasoning and conclusion. It did not add any further reasoning.
Therefore, PB’s evidence would be open to the same concerns that were highlighted
with MC.
Accordingly, after careful consideration of all the information, I do not accept the
evidence shows the proximate cause of damage to the applicants’ property were the
leaks.
Therefore, I am not satisfied the applicants have shown a prima facie claim. The FSP
is entitled to deny liability for the applicants’ claim.
Case No: 452703 Determination Page 5 of 9
3 Supporting information
3.1 Summary expert reports
Record Key points
FSP’s expert (IB )
Report
02 - 09 - 2011
Inspected the residence on 29 July 2011.
Cracking noticed from 2007 and had increased in size in
some areas since last records were taken in 2009.
The level survey indicates the dwelling had settled toward the
eastern corner of the double garage – likely due to soil drying
influences from the Cypress pines along the eastern
boundary.
No samples of soils were taken but res ults from neighbouring
property suggest clays are reactive.
Pattern and location of the ceiling cracking is consistent with
the creation of a ceiling “in plane” tension force due to a
curvature change in the dwelling’s footings.
Level survey identifies a relative settlement along the eastern
elevation compared to the western elevation.
Also a relative settlement across the front (north) co mpared
to the rear.
The likely dominant mechanism for the settling is the
shrinkage of the reactive clay foundation soil. The drying of
the reactive clay soil is the likely single most dominant
influence.
FSP’s expert (SA)
Report
04 - 06 - 2015
Testing confirmed a number of leaks at property.
Leakage recorded when testing WC branc h drain however it
is noted this may have originat ed from the concealed pan
collar seal.
Leakage of 8 litres per minute recorded from kitchen sink
waste pipe.
Leakage of 10 litr es per minute recorded from section of
sewer drainage approximately 2 meters downstream of the
main bat hroom floor trap grate.
Stormwater drainage could not be successfully tested due to
blockages.
FSP’s Expert (JC)
Report
03 - 08 - 2015
Attended property on 27 July 2015.
Unable to assess changes in damage due to repairs carried
out by the applicant.
The most severe settling is experienced to the lower eastern
elevation – caused by drying of the reactive clay foundation
beneath this portion of the home.
Possib le the trees and other vegetation loc ated adjacent to
the affected elevations have extracted moisture.
This is also consistent with movement obs erved to the fence
adjacent to the lower eastern elevation.
If the identified leaks had contributed to the movement, there
would be an expected heave in the brick course levels at the
Case No: 452703 Determination Page 6 of 9
leak locations – did not observe this pattern of movement.
Do not believe the level of water likely consumed in
accordance with the occupancy to be sufficient to influence
the rea ctive clay foundation’s moisture content to the extent it
could damage the home.
Conclusion
“… the observed damage has been caused, and has
continued to worsen, by drying and concomitant settlement of
the reactive clay foundation beneath the home’s north -
e astern corner. We do not believe stormwater or leaking
pipework could have contributed to the damage.”
FSP’s Expert (JC)
Report
13 - 10 - 2015
Borehole sampling carried out – site is classified as extremely
reactive.
5 boreholes undertaken – BH5 was used as a control sample.
Suction profiles of BH1, BH2, BH3 and BH5 were relatively
similar – BH5 was the wettest of these samples at depth
indicating the site’s “natural” equilibrium is approximately
3.9pF.
BH1, BH2, BH3 were drier at dept h – samples were wetter
n ear the surface, which is normal given their time of
sampling.
The results reflect the long term drying that has occurred
around the home’s perimeter.
There is a minor difference bet ween BH1/BH3 and BH2/BH5.
BH1 was sampled near the leak in the kitchen wa ste pipe and
BH3 sampled near the leak in the bathroom waste pipe. Both
were found to have moisture further below the surface than
BH2 and BH5 – may be reflective of soil introduced to the soil
from the leaks.
However, the survey results indicate the home has continued
to settle at these locations – soil has continued to dry in these
areas despite the leaks.
Highly unlikely the limited moisture leaked through these
pipes during periods of occupancy was of a quantity
necessary to contribute to the home’s movement.
Approximate centre point of the meals room was measured to
be the highest internal point of the house – t his area of the
home’s foundation is the most remote from bot h wetting and
drying influences.
Surrounding foundation has dried at a faster ra te causing the
net settlement away from the high point towards the home’s
perimeter – this has caused distortion of the meals/family
room floor.
We do not believe the pipework has contributed to the
movement.
BH4 was sampled adjac ent to the garage’s north - east corner
where the house has undergone the greatest settlement –
whilst expecting this to be the driest, it was quite moist (even
in depth).
Moist soil conditions in this area should have resulted in
Case No: 452703 Determination Page 7 of 9
heave.
However, the surveys show the settlement aroun d the
house’s perimet er has continued to worsen since 2011 – this
is consistent with an increas e in the general drying perimeter
settlement.
Conclusion
“The movement to the home has been caused by drying and
concomitant settlement of the reactive clay foun dation
around/towards the home’s perimet er, as opined in our
Previous Report.”
FSP’s Expert (JC)
Report
24 - 12 - 2016
The applicant’s analysis is reasonable and provides a
plausible explanation for the home’s movement.
However, does not believe it was the m ec hanism which
caused the damage to the home.
If the insured’s mechanism was accept ed, we would
anticipate a recovery in the home’s movement between 2007
and 2015 as the sewer influences would have reduced – this
would res ult in a decrease in the external levels in the areas
of the leak from 2011 to 2015.
There is a decrease in levels in the area of the bathroom leak
– however the survey should be considered as a whole.
The bathroom is 40mm lower than the home’s high point
(south - east corner) – if the dominant cause was a heave in
the bathroom area, it would be the high point or at least equal
to the high point – it is not the case.
Limited change to the kitchen area – therefore, there is no
evidence the home is recovering from a heave in the kitchen
ar ea.
If the home was recovering from a heave along an east - west
axis linking the two leaks, the levels of the lower - eastern and
northern elevations would converge to the levels of the
remainder of the house – the opposite has occurred.
The more objective ev idenc e indicates settlement of the
home’s northern, western and lower - eastern elevations is the
dominant cause of the home’s distortion.
FSP’s Expert (JC)
Report
14 - 06 - 2016
Additional borehole sampling indicates no influence from the
leaks to the foundat ion and moisture content.
The distortion of the home’s footings has continued to worsen
(or, at best, remained relatively constant between July 2015
and March 2016).
If the leaks had caused the damage, we would expect an
improvement in the footing’s distor tion as the leak’s influence
on the foundation dissipated – no evidence of this occurring.
Applicants’ Expert
(RP)
Report
07 - 07 - 2016
Level survey carried out show a significant high area around
the kitchen, meals area and family room.
Peak of the heave ap pears to be around the north - eastern
side of the meals area.
There appears to be a high section around Bedroom 2 and
the main bathroom.
Case No: 452703 Determination Page 8 of 9
The applicant provided a different floor level survey recorded
by others – this shows a similar contour profile.
Sewer and stormwater investigator noted leaks at the kitchen
sink waste pipe and waste pipe north - west of the main
bathroom – these leaks are very high and reportedly fixed
prior to their inspection.
The predominant cause was the significant ingress of water
int o the reactive soils, particularly in the kitchen and meals
area – this would have been caused by the kitchen waste
water pipe.
The similar leakage adjacent to the main bathroom would
also appear to be responsible for the smaller amount of
swelling around bedroom 2 and the main bathroom – this has
not been as serious.
Applicants’ Expert
(GR)
Report
31 - 08 - 2016
Conc urs with RP’s opinion.
FSP Expert (JC)
Report
22 - 12 - 2016
Disagrees with applicants’ experts’ conclusion as to cause of
damage.
Water would hav e only leak ed when pipes were being used –
as home was sparsely occupied from 2010 - 2015 there would
have been little potential for water use.
If a leak was the factor which started the cracks in 2007 then
the unoccupied period would have allowed the home t o return
to its original footing – this did not happen as the movement
appears to have worsened.
Maintains position the cracking is due to the drying influences
around the home.
Applicants’ Expert
(TM)
Report
08 - 03 - 2017
Have reviewed JC’s report dated 22/12/16 – have not
reviewed previous engineer reports
The moisture ingress most likely continued since 2007 until it
was repaired until 2015.
This resulted in localised slab heave around the leak.
The pattern of the heave is typical of slab heave due to a
localised pipe leak.
If it was due to soil drying around the edges of the building, it
would more typically show
- the corner of building settling
- the northern end of the lounge room settling
- the south eastern end of the garage settling
This is not the case .
The slab heave is also very severe – this is not typical for a
situation where the soil around the edges is drying and the
footing is a concrete raft slab.
The owners have noted a closing of cracks around doors etc,
in the area of slab heave since the re pair of the pipework. It
has been almost 2 years since the pipework was repaired –
this is to be expected given the nature of the soil.
Case No: 452703 Determination Page 9 of 9
Conclusion
“… it is concluded that the slab heave in the kitchen/meals
and adjacent family room … is due to moisture ingress from
the proven sewer leak in the kitchen waste pipe.”
FSP’s expert (JC)
Report
05 - 04 - 2017
Home’s highest point is the south - eastern corner – this is
some distance from either of the leaks – would not be the
case if the movement was in the form of localised heave.
Previous gap referred to by the applicants was not pointed
out or identified in their inspection – does not assist either
way.
This is be cause Adelaide ex perienced above average rainfall
over the past 12 months – the settled parts of the home may
have begun to return to their original levels after being
somewhat rehydrated from this.
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.