Home / Financial Firm (Unknown - Insurer) / Determination 443786
Determination 443786
Ensuite shower damage claim denied as poor installation
Summary
A homeowner claimed for shower tile and base damage that he attributed to a roof leak; the insurer denied it as poor installation. AFCA found a prima facie claim was established, the insurer had not proved faulty workmanship, and ordered the claim indemnified with statutory interest, the cost of the expert report and $250 for claims-handling delay.
Once the insured establishes a prima facie loss from an insured event, the insurer bears the onus of proving that an exclusion such as poor workmanship applies.
Subjects and remedies
home or building damagepay claimpay compensationpay interestpay non financial loss
Text of the determination
Determination
Case No: 443786 Determination Page 1 of 7
Case number: 443786 28 February 2017
1 Overview
1.1 Dispute
The applicant held a home insurance policy with the FSP. This provides cover for
loss or damage to his home caused by insured events set out in the policy, subject to
conditions and exclusions.
The applicant lodged a claim for tiles lifting in the ensuite shower recess. He believes
this was caused by a leak in the roof. The FSP denied the claim on the basis it was
due to poor installation.
1.2 Issues and key findings
Can the FSP deny the claim?
The FSP cannot deny the claim because:
the evidence shows there is a leak affecting the area – this establishes a prima
facie claim
the evidence does not show the cause of the damage was poor workma nship
Is the applicant entitled to compensation due to his claims experience?
The FSP committed an error and did not immediately appoint a builder to inspect the
damage. As this would have unduly inconvenienced the applicant, the FSP must pay
$250 in non-financial loss.
1.3 Determination
This determination is in favour of the applicant.
The FSP is required to indemnify the applicant for this claim.
The FSP is to pay interest on any amount paid to the applicant under the claim
pursuant to the statutory rate from 28 April 2016 until payment is made.
The FSP is to pay for the cost of PS’s report subject to the applicant producing an
invoice.
The FSP is to pay $250 in non-financial loss to the applicant.
Case No: 443786 Determination Page 2 of 7
2 Reasons for determination
2.1 Can the FSP deny the claim?
Applicant must establish a prima facie claim
The applicant is required to demonstrate that, on the balance of probabilities, he has
suffered a loss caused by a risk insured against under the policy.
This is known as a prima facie claim.
Once the applicant establishes a prima facie claim, the FSP is liable for the loss
unless it shows an exclusion applies. The FSP has the onus of proof in establishing
the application of the exclusion.
Evidence shows there was a leak
The applicant’s policy covers him for l oss or damage caused by an insured event.
This includes storm and escape of liquid.
The applicant says the damage was due to the roof leaking above the ensuite
shower and master bedroom.
There is no dispute the roof was leaking above these areas. Further, the evidence
shows this leak has caused damage to the flooring and wall adjacent to the ensuite.
Therefore, I accept the applicant has established a prima facie claim.
Expert PS is preferred
The FSP says this leak did not cause the damage to the shower in the ensuite. It has
relied on its experts who say the damage was caused by the poor installation of the
tiles.
The applicant has provided expert evidence challenging this.
All of the relevant expert evidence has been summarised at the back of this decisi on.
I have carefully reviewed all the available evidence. I am not satisfied the FSP has
established the cause of the damage was faulty workmanship for the following
reasons.
The evidence demonstrates there is a leak within the area affected. For instance,
there is a high level of moisture affecting the timber floor, skirting boards and timber
framed structure that backs onto the ensuite shower.
According to PS, this leak has resulted in rot to the timber flooring in both the ensuite
and master bedroom. This in turn has caused the shower base and substrate to fail
and resulted in the failed waterproofing and damage.
This explanation is plausible and consistent with the available evidence.
The FSP’s experts maintain the tiles were poorly installed and this w as the cause of
damage. They did not accept the applicant’s reasoning on the basis:
Case No: 443786 Determination Page 3 of 7
the water ingress preceded a January 2016 storm event
the deterioration occurred prior to the roof leaking
the leak had a negligible effect
There is no evidence showing when the roof first started leaking. The applicant said
this could have occurred prior to the January 2016 event. Given this, the FSP’s
experts’ conclusion that the shower was deteriorating and affected before the roof
was leaking is not substantiated.
In terms of the negligible effect of this leak, this is neither apparent nor supported by
the available evidence. For instance, PS observed the high level of moisture in the
flooring and wall adjacent to the shower. PS also believed the timber flooring of both
to be affected. The FSP’s experts have not refuted these observations or explained
why they would have had negligible effect on the shower.
Given this, I do not accept their reasoning for disagreeing with the applicant’s
position is established on the available evidence.
FSP liable for the damage
I accept the applicant has established the damage to the shower was due to the
leaking roof. I am not satisfied the FSP has established the damage was caused by
the poor installation of the tiles.
Therefore, the FSP is liable to indemnify the applicant for the shower.
The FSP is also to pay interest on any amount paid to the applicant pursuant to
section 57 of the Insurance Contracts Act 1984 (the Act). Interest is payable from 28
April 2016, being the date it denied the claim, until payment is made.
In addition, the FSP is to pay for the cost of PS’s report given this substantively
assisted the applicant. This is subject to the applicant providing an invoice of its cost.
2.2 Is the applicant entitled to compensation
FOS awards non-financial loss conservatively
The applicant has complained about the delay in settling his claim.
Under paragraph 9.3(b)(i) of FOS’s Terms of Reference, I can award up to $3,000 for
non-financial loss if the FSP caused the applicant to suffer an unusual degree or
extent of inconvenience, delay or interference.
FOS awards non-financial loss conservatively. This is because applicants are
expected to be moderately robust and bear the normal degree of inconvenience
experienced when a problem occurs.
The FSP must pay $250 compensation for delay in claims handling
I accept there was an unusual delay in processing the claim. In particular, the FSP
committed an error and did not immediately appoint a builder to inspect the damage.
Case No: 443786 Determination Page 4 of 7
The evidence does not show the FSP’s conduct caused any other unusual delay,
inconvenience or interference.
Given this, and FOS’s conservative approach to compensation, the FSP should pay
the applicant $250 of non-financial loss.
Case No: 443786 Determination Page 5 of 7
3 Supporting information
3.1 Expert Evidence
Re cord Key points
FSP’s expert ( RP )
Report
18 April 2016
No leaks were found to the ensuite plumbing.
Static water test to the shower base and spray test to shower
wall tiles failed
The primary cause of the water ingress appears to be a
failure of the waterproof membrane to the insitu shower
recess
Water appears to be penetrating the wall and floor tiling for an
extended period of time
Substrate to the shower rec ess is in very poor condition
FSP’s expert ( ML )
Report
12 May 2016
Shower base around the waste has been removed exposing
poor construction of the shower base
Two cracked wall tiles identified just above the base
Substrate is water damaged – this is causing rot and other
floor tiles within the shower to become loose
Carpet and flooring under it has also sustained water damage
Informed customers that main cause of shower and bedroom
issues is due to shower base construction
FSP’s expert (RP)
Report
13 May 201 6
There are ve rtical and horizontal joints on the sisilation paper
above the ensuite and master bedroom making it susceptible
to water ingress
There are several noticeable areas where the sisilation paper
has been torn and water has also been dripping into the
ceiling cavity
Roof tiles are not extended forward enough into the gutter
line – water appears to have been entering under heavy rain
conditions
A number of tiles above the ensuite and master bedroom
have broken water courses – this is also contributing to the
wat er ingress
FSP’s expert (RP)
Amended Report
13 May 201 6
Floor of the shower recess contains several dislodged tiles
A close inspection of the area where tiles have been
dislodged show waterproof membrane and tile substrate to be
in very poor condition
Tiler has not installed a mortar screed to provide required fall
before commencing tiling
An excessive layer of adhesive used – inhibited the tile
adhesive from curing correctly and avoiding tile movement
Window packers were used to restrict newly laid tiles
movement
Primary cause of damage is poor manner of installation
Damage to the shower recess has occurred over an extended
period of time
Case No: 443786 Determination Page 6 of 7
Unable to conclude whet her the leaking roof added to the
deterioration – this is moot as the primary cause was t he
manner of installation
FSP’s expert (ML)
Report
25 May 201 6
Roof inspection identified small water ingress occurring
This has resulted in damage to the base of the int ernal wall in
the master bedroom adjacent to the ensuite
Resulting damages to the sh ower are not as a result of this
ingress
Damage to shower due to poor workmanship which allowed
the shower base to deteriorate and break up
App’s expert (DS)
Letter
Undated
Water damage in the wall between main bedroom, ensuite
and ensuite shower area
Fe els the damage was caused by storm water entering the
roof above this area and down the wall cavity
This has possibly caused damage to sub floor and wall
frames – this in turn caused the plaster skirting to rot and the
carpet to det eriorate with mould on t he bedroom side
Possible rot and movement on the bathroom side may have
caused the tiles and wat erproofing to crack and deteriorate –
this in turn caused tiles on the shower floor to heave
App’s expert (PS)
Report
13 November 2016
Dwelling was subject to a makeover and refurbishment in
2004 - 2005
There was a damp “musky” smell in the master bedroom –
skirting board is distorted and appeared swollen
The MDR skirting is clearly wat er affected and the carpet is
stained and damp
Lifting the carpet reveals rotte n timber – this extends out from
the wall approximately 45cm
Water proof agent in ensuit e shower was not intact
Tile installation appeared irregular as there were plastic
packers supporting the floor tiles
Two significant items stood out – timber floorboa rds were
spongy and showing signs of wood rot and cracks were seen
in several wall tiles at the bottom of the wall
This is typical of the wall frame compressing due to moisture
related deterioration of the timber frame
Conclusions
Pooling water from the ro of has leaked int o the wall cavity
Moisture inside the wall cavity caused the timber flooring to
rot in both the master bedroom and ensuite shower
The rotting timber floor caused the shower bas e to become
spongy and the eventual substrate failure – this ca used the
tiles to crack and the waterproof membrane to be affected
No manner of installation could have withstood the timber
being constantly wet – the shower base failure was a
secondary event
Case No: 443786 Determination Page 7 of 7
FSP’s expert (PR)
Report
25 January 2016
Applicant’s property has incurred resultant damage to two
areas (master bedroom and ensuite) for two different reasons
Master bedroom suffered damage due to wat er ingress from
the roof lining
Ensuite has incurred signific ant long term water damage due
to p oor installation
Water ingress to the adjacent bedroom wall would have had
negligible effect as the shower recess already had significant
inherent damage from the poor installation
No secondary damage to the shower recess was due to the
roof leak