Home / Financial Firm (Unknown - Insurer) / Determination 440910

Determination 440910

Fire damage claim to main fuse box denied on the basis there was no flame

FirmFinancial Firm (Unknown - Insurer)
Decided2016-11-11
ProductGeneral Insurance · Home building and contents
OutcomeFor the firm
Amount awarded—
Non-financial loss—
Amount claimed—
SourceAFCA PDF

Summary

The applicant's fuse box fire damage claim was declined under an exclusion for scorching or melting without flame. AFCA preferred the forensic fire investigator's evidence that the damage came from a smouldering fire and found the FSP entitled to deny the claim.

The FSP met its onus under the scorching-without-flame exclusion through the better-qualified expert evidence on the balance of probabilities.

Issues

Subjects and remedies

home or building damageno remedy

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Determination Case No: 440910 Determination Page 1 of 3 Case number: 440910 11 November 2016 1 Overview 1.1 Dispute The applicant’s claim for fire damage to the main fuse box was denied by her insurer, the financial services provider (FSP), on the basis there was no flame. The applicant has disputed this decision as she says there was a flame. 1.2 Issues and key findings Can the FSP deny the claim? The FSP can deny the claim because:  the available expert evidence demonstrates there was fire damage without a flame  this falls within a policy exclusion for fire damage 1.3 Determination This determination is in favour of the FSP. The FSP is entitled to deny liability for the applicant’s claim. Case No: 440910 Determination Page 2 of 3 2 Reasons for determination 2.1 Can the FSP deny the claim? FSP must prove the exclusion The applicant’s policy covers her for damage caused by fire. However, the following exclusion applies to this insured event: “loss or damage caused by scorching or melting when there was heat but no flame, including scorch or burn marks cau sed by a cigar, cigarette or pipe.” As the FSP is relying upon this exclusion to deny the claim, it has the onus of proof to establish its application. The standard of proof is the balance of probabilities. Expert evidence disagree as to whether there was a flame The applicant provided a report from the contractor (ST) who attended the site. This report said the following: “I found the fused mains box had caught fire and caus ed power outage issues in the property. I cut back and reterminated the burnt cables and replaced the fused main box, two separate truck appointments were required by the power company.” [sic] The FSP engaged a forensic fire investigator (PG). PG was provided photographs of the fuse box and offered the following opinion in an email dated 14 April 2016: “There is evidence of localised heat damage, however, in my opinion, I doubt there would have been a flame. The presenc e of cobwebs and other dry matter in close proximity to the heat affected area appears to indicate the heat source that caused the damage was more of a smoldering fire, which hadn’t developed into a full fame fire. PVC insulation of cables in the same area is intact which indicates it had not been impacted by a flame. If the smoldering fire had developed into a flame fire, the damage would have been significantly greater and would have continued to develop until extinguished. Based on the evidence shown in the supplied photographs, I formed the opinion the localised heat damage had result ed from a smoldering fire.” The applicant provided a second report from ST dated 31 August 2016 that said: “Upon ins pection it would found that Origin energy technicians had inspected the property and found a damaged overhead fused mains box (folcb). It was advised by the power authority that the folcb was required to be replaced and certific ate of electrical safety issued in order to have power reinstated to the property. The folcb had signs of fire damage. The terminals were burnt and the cover had significant burn marks and was most definite ly caused by the flames which occurred in the terminal block.” PG’s evidence is preferred Having carefully reviewed the available evidence, I prefer PG’s evidence for the following reasons. First, the FSP has provided a copy of PG’s qualifications. He has extensive training, study and experience regarding fire. This demonstrates he has substantive specialised knowledge in this field and is well qualified to provide an opinion as to whether the main fuse box had a flame. In contrast, no information has been provided about ST’s background. Case No: 440910 Determination Page 3 of 3 Second, PG’s conclusion is supported by plausible and unrefuted observations. For instance:  the presence of cobwebs and other dry matter in close proximity to the smouldering fire  the PVC insulation of the cables in the same area being intact  the fact the damage would have been greater  any flame would need to be extinguished ST’s conclusion does not address these factors. Instead, ST accepts there was a flame based on the terminal being burnt and the cover having significant burn marks. However, it is unclear how a flame could have caused these damages yet leave the presence of dry matter, cobwebs and insulation intact. FSP entitled to deny the claim After careful consideration of the available information, I am satisfied t he evidence establishes on the balance of probabilities that the damage to the main fuse box was caused by scorching or melting where there was no flame. As this falls within the exclusion for the insured event of fire, then the FSP is entitled to deny lia bility for the applicant’s claim.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.