Fire damage claim to main fuse box denied on the basis there was no flame
Summary
The applicant's fuse box fire damage claim was declined under an exclusion for scorching or melting without flame. AFCA preferred the forensic fire investigator's evidence that the damage came from a smouldering fire and found the FSP entitled to deny the claim.
The FSP met its onus under the scorching-without-flame exclusion through the better-qualified expert evidence on the balance of probabilities.
Issues
- Claim denial primary · not upheld
“the damage to the main fuse box was caused by scorching or melting where there was no flame”
- Product terms interpretation secondary · not upheld
“this falls within the exclusion for the insured event of fire, then the FSP is entitled to deny liability”
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
Case No: 440910 Determination Page 1 of 3
Case number: 440910 11 November 2016
1 Overview
1.1 Dispute
The applicant’s claim for fire damage to the main fuse box was denied by her insurer,
the financial services provider (FSP), on the basis there was no flame.
The applicant has disputed this decision as she says there was a flame.
1.2 Issues and key findings
Can the FSP deny the claim?
The FSP can deny the claim because:
the available expert evidence demonstrates there was fire damage without a
flame
this falls within a policy exclusion for fire damage
1.3 Determination
This determination is in favour of the FSP.
The FSP is entitled to deny liability for the applicant’s claim.
Case No: 440910 Determination Page 2 of 3
2 Reasons for determination
2.1 Can the FSP deny the claim?
FSP must prove the exclusion
The applicant’s policy covers her for damage caused by fire. However, the following
exclusion applies to this insured event:
“loss or damage caused by scorching or melting when there was heat but no flame, including
scorch or burn marks cau sed by a cigar, cigarette or pipe.”
As the FSP is relying upon this exclusion to deny the claim, it has the onus of proof to
establish its application.
The standard of proof is the balance of probabilities.
Expert evidence disagree as to whether there was a flame
The applicant provided a report from the contractor (ST) who attended the site. This
report said the following:
“I found the fused mains box had caught fire and caus ed power outage issues in the property. I
cut back and reterminated the burnt cables and replaced the fused main box, two separate truck
appointments were required by the power company.” [sic]
The FSP engaged a forensic fire investigator (PG). PG was provided photographs of
the fuse box and offered the following opinion in an email dated 14 April 2016:
“There is evidence of localised heat damage, however, in my opinion, I doubt there would have
been a flame.
The presenc e of cobwebs and other dry matter in close proximity to the heat affected area
appears to indicate the heat source that caused the damage was more of a smoldering fire,
which hadn’t developed into a full fame fire.
PVC insulation of cables in the same area is intact which indicates it had not been impacted by
a flame.
If the smoldering fire had developed into a flame fire, the damage would have been significantly
greater and would have continued to develop until extinguished.
Based on the evidence shown in the supplied photographs, I formed the opinion the localised
heat damage had result ed from a smoldering fire.”
The applicant provided a second report from ST dated 31 August 2016 that said:
“Upon ins pection it would found that Origin energy technicians had inspected the property and
found a damaged overhead fused mains box (folcb).
It was advised by the power authority that the folcb was required to be replaced and certific ate
of electrical safety issued in order to have power reinstated to the property. The folcb had signs
of fire damage. The terminals were burnt and the cover had significant burn marks and was
most definite ly caused by the flames which occurred in the terminal block.”
PG’s evidence is preferred
Having carefully reviewed the available evidence, I prefer PG’s evidence for the
following reasons.
First, the FSP has provided a copy of PG’s qualifications. He has extensive training,
study and experience regarding fire. This demonstrates he has substantive
specialised knowledge in this field and is well qualified to provide an opinion as to
whether the main fuse box had a flame.
In contrast, no information has been provided about ST’s background.
Case No: 440910 Determination Page 3 of 3
Second, PG’s conclusion is supported by plausible and unrefuted observations. For
instance:
the presence of cobwebs and other dry matter in close proximity to the
smouldering fire
the PVC insulation of the cables in the same area being intact
the fact the damage would have been greater
any flame would need to be extinguished
ST’s conclusion does not address these factors. Instead, ST accepts there was a
flame based on the terminal being burnt and the cover having significant burn marks.
However, it is unclear how a flame could have caused these damages yet leave the
presence of dry matter, cobwebs and insulation intact.
FSP entitled to deny the claim
After careful consideration of the available information, I am satisfied t he evidence
establishes on the balance of probabilities that the damage to the main fuse box was
caused by scorching or melting where there was no flame.
As this falls within the exclusion for the insured event of fire, then the FSP is entitled
to deny lia bility for the applicant’s claim.