Home / Financial Firm (Unknown - Insurer) / Determination 426318
Determination 426318
Home insurance claim for wall and footpath cracking denied; earthquake cause disputed and ex-gratia payment requested
Summary
The applicant claimed for cracking to his holiday home, attributing it to earthquakes around 30 July 2015, and asked for an ex-gratia payment. The FSP denied the claim under its defective workmanship and climatic exclusions. AFCA found in its favour and found no obligation to pay ex-gratia.
The expert evidence showed the wall cracking came from defective building work and normal material movement, both excluded, and not from an earthquake within 72 hours of the damage.
Subjects and remedies
home or building damagenatural disasterno remedy
Text of the determination
Determination
Case No: 426318 Determination Page 1 of 6
Case number: 426318 26 May 2016
1 Overview
1.1 Dispute
The applicant lodged a claim on 17 August 2015 for cracking to his home with his
insurer, the financial services provider (FSP).
The FSP declined the claim as it is excluded under the applicant's home insurance
policy (Policy).
The applicant has disputed this as he says the damage was due to an earthquake or
earthquakes that occurred on or around 30 July 2015. Further the applicant says that
as a loyal customer with an excellent record, the FSP should consider an ex-gratia
payment to cover the cost of repairs.
1.2 Issues and key findings
Is the FSP entitled to deny the claim?
The FSP can deny the claim because the expert evidence demonstrates on the
balance of probabilities the proximate cause of the damage is defective workmanship
and the effect of atmospheric or climatic conditions which are excluded under the
terms of the Policy.
1.3 Determination
This Determination is in favour of the FSP. The FSP is entitled to deny the claim and
is not obliged to make an ex-gratia payment to the applicant.
Case No: 426318 Determination Page 2 of 6
2 Reasons for Determination
2.1 Is the FSP entitled to deny the claim?
Policy provides cover for accidental damage
The applicant’s Policy provides cover for accidental damage. Accidental damage is
defined as:
“damage to or loss or destruction of the buildings that make up your home, or your contents and
valuable items, when it is caused by an unintentional act, or an unforeseen and uncontrol lable
incident.”
Cover for accidental damage is provided if it occurs as a result of an unintentional act
or by an unforeseen and uncontrollable act. The cracking was not caused
intentionally. The applicant has therefore established that his loss does fall within the
scope of cover provided under the Policy.
Once a prima facie claim has been established, the onus shifts to the FSP to prove
on the balance of probabilities that an exclusion applies.
Cover for accidental damage is subject to exclusions
Although the Policy provides cover for accidental damage, this cover is subject to
some exclusions. The Policy does not cover loss or damage as a result of or caused
by:
settling, shrinkage or any movement of the earth;
erosion, rust, corrosion, gradual deterioration, depreciation, wear or tear;
a defect in an item, structural defects, or faulty workmanship or design;
landslide or subsidence unless we agree to cover the incident as described
under “ l andslide or subsidence”
mildew, atmospheric or climatic conditions.
The onus is on the FSP to establish that the exclusions apply.
Applicant reports do not establish earthquake caused damage
The applicant says that the cause of the damage is the earthquake (or earthquakes)
that occurred in the vicinity of the property on or around the time that the cracking in
the walls and the footpath was first noticed.
Cover for landslide and subsidence is provided where the loss or damage occurs
within 72 hours of an earthquake or explosion.
Records show that earthquakes of magnitude 3.9 – 5.4 were detected on or around
30 July 2015 and were located offshore in the vicinity of Fraser Island.
The insured property is a holiday home. The applicant first noticed the damage on
returning to the property sometime in early August 2015. The applicant has not
therefore established that the damage occurred within 72 hours of an earthquake.
Case No: 426318 Determination Page 3 of 6
BD, who is a licenced building designer with over 20 years of experience, inspected
the property in 2011. He says a very careful inspection of the condition of the
masonry walls was conducted as the applicant was considering a second story
extension. At that time he says there was no cracking or subsidence noted.
This report does not provide any opinion about the cause of the damage or whether
the damage occurred within 72 hours of an earthquake.
The applicant also relies on a report prepared by JB who is a painter and renderer
with over 30 years of experience working in the surrounding area. He says that the
horizontal and vertical cracking in the masonry and cement sheet external walls is a
direct result of seismic activity. He says:
“I can say with no doubt of this because, I have surveyed and done reports for several
properties in the surrounding areas, from Tin Can Bay through to Bundaberg including Her vey
Bay, from units with up to 2 inches in structural movement, some of which are with engineers on
how to fix the problem ie concrete underpinning etc, done to a house such as this property
[property address]. In my professional opinion 30 years in Rendering and Painting contracting,
this is damage caused directly through movement of the ground.”(sic)
Again this report albeit identifying ground movement as a cause of damage, does not
identify that this occurred within 72 hours of the earthquake.
Information provided in FSP reports more persuasive about cause of damage
The FSP relies on two reports provided by DK who is a licenced builder.
Importantly in the supplementary report DK says:
“My investigations revealed that earthquake movement damage consistently resulted in cracks
in excess of 1 mm wide. Additionally the damage resultant of earthquake activity was typically
evident within floor/ wall tiling and plasterboard wall/ceiling lining which are vulnerable to
cracking as a result of movement.
My observations also revealed that typically earthquake movement cracks were evident higher
up the wall elevations, generally wit hin close proximity to the ceiling/cornice junctions. This is
because eart hquake movement is most amplified higher up the wall elevations.
However, at the time of my inspection I did not detect any significant cracking (i.e. in excess of 1
mm), the plasterboard wall/ ceiling linings, plasterboard cornice, internal floor titling or to the
external floor titling common to the NE side of the residence which is shaded by a pergola roof. ”
Further, the objective reporting of the time, size and location of earthquakes in the
relevant period do not support a finding that the property was likely to be effected.
The property is outside of the estimated damage radius. Whilst the earthquake may
have been felt in the area of the property, the property falls outside of the impact
zone in relation to damage.
I am more persuaded by these reports because:
the writer is a qualified builder and building consultant
the reports provide a detailed analysis of the location and extent of cracking
they refer to the relevant building codes
they provide information about the size, location and timing of the earthquakes
and tremors and relate this information to the visible damage.
Proximate cause of damage to masonry walls is defective building work
The property was renovated between 2011 and 2013. The renovation included an
extension and rendering to the entire external walls.
T he FSP’ s expert says that the location of the walls and defective building work has
caused the damage to the masonry walls. He says that the failure to install
Case No: 426318 Determination Page 4 of 6
articulation joints in accordance with the relevant building regulations (Building Code
of Australia 2008) has caused the cracking.
This view is based on the following observations:
the cracking appears on the south east (SE) and north west (NW) walls which
are exposed to direct sunlight
the cracks are located below or in close proximity to windows
vertical articulation joints were not installed
the relevant building code requires vertical articulation joints of no less than 10
mm be provided where a wall contains openings more than 900 x 900 mm
the NW and SE walls consist of openings in excess of 900 x 900 mm
the cracks are indicative of damage caused by normal building material
movement
the failure to install the vertical articulated joints combined with exposure to
direct sunlight has contributed to the cracking
the failure to install vertical articulation joints is considered to be defective
building work.
On the balance of probabilities the proximate cause cracking to the masonry walls is
a defect in an item, a structural defect, or faulty workmanship or design. As such this
damage is excluded under the Policy and the FSP is entitled to deny this part of the
claim.
Damage to cement sheet wall caused by normal building material movement
Vertical control joints have been installed in the cement sheet wall in accordance with
acceptable industry practice. The cracking i n this wall is vertical and approximately
.25mm wide.
On the balance of probabilities this cracking is a result of normal building material
movement caused by changes in temperature and moisture levels.
Under the Policy damage caused by atmospheric or climatic conditions is excluded.
Further, damage caused by erosion, rust, corrosion, gradual deterioration,
depreciation, wear or tear is also excluded.
As the proximate cause of the damage is related to the normal expansion and
contraction of building material it falls within the exclusion and is therefore not
covered under the Policy.
Damage to footpath caused by defective workmanship
In the absence of any contrary opinion in relation to the footpath I accept the FSP’s
report that the failure to properly compact the sub-base under the footpath has
allowed the aggregate material to self-compact over an extended period of time
resulting in subsidence.
The FSP has established that on the balance of probabilities that the damage to the
footpath has been caused by defective workmanship. The FSP is entitled to deny the
claim for damage to the footpath.
Case No: 426318 Determination Page 5 of 6
FSP is entitled to base its claim decision on the Policy terms and conditions
The FSP has not disputed that:
the claim has been made in good faith;
the applicant has been insured with the FSP for 16 years;
the applicant has a limited claims history;
the applicant has paid premiums to the FSP over the period of insurance.
The applicant says that given the above the FSP should give the applicant the benefit
of the doubt and pay the claim or make an ex-gratia payment to the applicant.
The FSP has responsibility to all of its stakeholders to assess each claim on its
merits and to consistently apply the terms and conditions of its policies to each claim.
In this case the FSP has met its contractual obligations to the applicant. The claim
has been considered and declined in accordance with the Policy. The FSP has met
its onus of establishing that the proximate cause of the damage is excluded under
the Policy. In all of the circumstances the FSP is entitled to base its claim decision on
the Policy and therefore is not obligated to make any payment to the applicant for this
claim.
Case No: 426318 Determination Page 6 of 6
3 Supporting information
3.1 Expert reports
Summary of information provided in reports
Report Key points
FSP’s report (RG)
Assessment
10 September 2015
Recommend appointment of building cons ultant as doubt
whet her loss occurred as a result of insured event
(earthquake).
FSP’s expert (DK )
Caus ation Report
12 October 2015
Masonry walls – walls in direct sunlight. Failure to install
vertical articulation joints has contributed to cracking.
Cement sheet walls – normal building material movement.
Footpath – subsidence due to defective building work.
Applicant’ s expert
(BD )
Condition Report
10 November 2015
Referenc e to 2011 inspection done prior to
extension/renovation.
No evidence of cracking or subsidence in 2011.
FSP’s expert (DK)
Supplement ary report
26 November 2015
Masonry walls – normal building material movement.
Cement sheet walls – normal building material movement.
Subject property was in excess of 100km from the estimated
damage radius of the highest magnitude earthquak e within
the relevant period.
Damage not consistent with earthquake damage as size and
location of cracking does not indi cate damage caused by
earthquake.
Applicant’s expert (JB )
Structural repor t
13 February 2016
Cracking to external walls of the building is a direct damage
due to seismic movement from constant tremors.
In professional opinion 30 years in rendering and pai nting
contracting this damage is caused directly through movement
of the ground.