Determination 405025
Denial of external wall displacement damage caused by leaking pipe under earth movement and structural defect exclusions
Summary
The complainant's home insurer accepted internal bathroom damage from a leaking pipe but denied damage to the adjacent external wall as earth movement, faulty workmanship or structural defect. AFCA found the FSP had not established an excluded cause and ordered it to cash settle the external wall repair cost on an updated quote, with the amount not stated.
Because the leaking pipe was the prima facie accidental cause, the FSP bore the onus to prove an excluded proximate cause, and it failed to establish that the earth movement or structural defect was the dominant cause.
Issues
- Claim denial primary · upheld
“I am not satisfied that the FSP has established that the primary source of the abnormal moisture conditions was anything other than the leaking pipe.”
- Inadequate claim investigation secondary · upheld
“It appears that S did not undertake a review of the historical water usage at the property, despite having earlier recommended that this occur.”
Subjects and remedies
home or building damagepay claim
Text of the determination
Determination
Case No: 405025 Determination Page 1 of 7
Case number: 405025 7 December 2015
1 Overview
1.1 Dispute
The Applicant lodged a claim under his home insurance policy with the Financial
Services Provider (FSP) for damage to his home caused by a leaking pipe.
The FSP accepted the Applicant’s claim for the internal damage to the bathroom
resulting from the leaking pipe.
However, the FSP denied liability for damage to the external wall of the house
adjacent to the leak, on the basis this damage was not caused by the leaking pipe
but by factors which are excluded under the policy (such as faulty workmanship,
structural defects and earth movement).
1.1 Issues and key findings
Is the FSP liable for the damage to the external wall?
The available information establishes that the cause of the damage was the outward
pressure of the retaining earth on the sub-floor brick wall. However, it is not clear
whether this pressure developed naturally over time or was due to abnormal moisture
conditions.
There is conflicting information as to whether any of the various factors identified
(other than the leaking pipe in the direct vicinity of the leaking pipe) would have
significantly contributed to the swelling of the retained earth. There is also conflicting
information as to the adequacy of the sub-floor brick wall and footing system at the
time of construction.
In these circumstances, the FSP has not established that the proximate cause of the
damage to the external wall was earth movement (other than due to the leaking pipe)
and/or faulty workmanship or a structural defect. Accordingly, the FSP is not entitled
to deny the Applicant’s claim for damage to the external wall.
1.2 Determination
This Determination is in favour of the Applicant.
The FSP is to cash settle the Applicant for the cost of repairing the damage to the
external wall adjacent to the bathroom, based on an updated quotation for the repair
of this damage to be obtained from the contractor (PW) who provided the initial
quotation in February 2015.
Case No: 405025 Determination Page 2 of 7
2 Reasons for Determination
2.1 Is the FSP liable for the damage to the external wall?
Policy provides cover for accidental damage subject to exclusions
The Applicant is required to show that, on the balance of probabilities, he has
suffered a loss caused by a risk insured against under the policy. This is known as a
prima facie claim.
If the Applicant is able to establish a prima facie claim, then the onus shifts to the
FSP to show that, on the balance of probabilities, it is entitled to rely on an exclusion
under the policy to deny the claim.
The Applicant’s policy provides cover for accidental loss or damage to his property,
subject to the conditions and exclusions set out in the policy.
The FSP acknowledges there was a leaking pipe in the wall cavity adjacent to the
shower recess in the Applicant’s main bathroom. The FSP has accepted liability for
internal damage to the bathroom resulting from the leaking pipe.
On this basis, I am satisfied the Applicant has established a prima facie claim.
Accordingly, the FSP bears the onus of establishing that, on the balance of
probabilities, it is entitled to rely on a policy exclusion to deny the Applicant’s claim
for the damage to the external wall adjacent to the leaking pipe.
FSP relies on exclusions for structural defects and earth movement
The reports prepared by the FSP’s engineer (S) confirm that the external rendered
brick wall adjacent to the leaking pipe had “bulged” or displaced by approximately
6 millimetres over a distance of approximately one metre.
The FSP says it is not liable for the damage to the external wall, as this damage was
not caused by the leaking pipe but by the following factors, each of which is excluded
from cover under the policy:
a defect in an item, faulty workmanship, structural defect or faulty design; and/or
settling, shrinkage or any movement of earth.
In order to establish it is entitled to deny liability for the damage to the external wall,
the FSP must show that the proximate cause (that is, the real, effective or dominant
cause) of the damage to the wall was one of the factors listed above.
Property showed evidence of significant cracking and movement damage
It is clear from the detailed reports provided by the FSP’s engineer (S) that there was
extensive cracking and movement damage apparent to various parts of the
Applicant’s property.
Following his initial visual inspection of the property, S concluded that this damage
had been caused by earth movement resulting from the effects of abnormal moisture
conditions on the highly reactive clay soils.
Case No: 405025 Determination Page 3 of 7
S identified a number of factors which may have contributed to the abnormal
moisture conditions, including the leaking pipe in the bathroom wall cavity. He
concluded that the absence of articulation joints in the external walls had
exacerbated the cracking and movement damage.
S noted that the relatively recent renovations to the property (including rendering of
the external walls) made it difficult to determine how much of the movement was due
to the leaking pipe, as opposed to long term poor performance of the footings.
Displacement of external wall was caused by pressure of retained earth
In addition to considering the cause of the broader cracking and movement damage
to the property, the FSP undertook extensive investigations to confirm the cause of
the localised displacement (or “bulge”) in the southern wall near the leaking pipe.
Following his initial inspection, the FSP’s engineer (S) reported that the localised
displacement was consistent with a lateral failure of the brickwork below the sub-floor
level.
S identified three possible causes of the lateral failure of the brickwork, including the
long term failure of an inadequate subfloor retaining wall which was previously
hidden by rendering and/or increased pressure from the retained earth as a result of
the leaking pipe.
S advised that further investigation of the damaged brickwork was required to
determine how and why the sub-floor wall had failed. He also considered
geotechnical tests should be conducted to determine the reactivity of the soil and
identify the footing type, in order to determine the propensity for earth movement
under normal moisture conditions.
Finally, S recommended that water usage records for the property be reviewed to
determine the extent of the leak and confirm how long it had been occurring.
Subsequent testing by the FSP’s geotechnical engineer (C) confirmed that the
foundation soils at the property were highly reactive. C also considered that the site
would have been subject to abnormal moisture conditions, given the stormwater
infiltration pit near the building and the presence of the leaking pipe, which he noted
may have been faulty for an extended period of time.
Based on C’s report, S advised that the localised displacement of the southern wall
immediately adjacent to the shower recess wall cavity was consistent with having
been caused by the leaking pipe (although this had not caused the cracking and
movement damage to other areas of the building).
As the investigations carried out by its geotechnical engineer (C) had not confirmed
the footing type, the FSP arranged for S to undertake further investigations of the
footing in the area of the bulge to the external wall.
S’s investigations revealed that the 230 millimetre wide double skin brick wall below
gr ound level had suffered a complete “shear” failure of 25 millimetres in an outwards
direction away from the building, which had caused the bulge observed higher up the
wall.
Case No: 405025 Determination Page 4 of 7
S concluded that the wall had failed either under the compacted load of the fill
material or due to abnormal moisture variations which had caused the fill material to
expand and force the wall outwards. S considered this reflected the structural
inadequacy of the wall to resist long term movement of the reactive clay soils.
S concluded that the failure of the wall had occurred over an extended period of time
and prior to the recent renovations, as the render on the surface of the wall in the
area of the bulge was noticeably thinner than in other areas.
I am satisfied that the supplementary report prepared by S following his further
investigations (including the photographs contained therein) establishes that the
observed bulge in the southern wall near the bathroom wall cavity was caused by the
outward pressure of retained earth which caused the shear failure of the sub-floor
double brick wall.
However, I am not satisfied that S’s report clearly establishes the dominant or
effective cause of the earth movement which resulted in the failure of the sub-floor
brick wall.
Source of abnormal moisture conditions is unclear
As outlined above, the FSP’s engineer (S) recognised that the outward pressure of
the retaining earth on the sub-floor brick wall may have been caused by the effects of
abnormal moisture conditions.
S identified a number of factors which he considered may have contributed to the
abnormal moisture conditions in the vicinity of the wall over an extended period of
time. Such factors included:
the presence of a stormwater pit located within 3 metres of the house which
collected overland stormwater flows and subsoil drainage of retaining walls
directly upstream from the house;
sewerage drainage pipes penetrating the brick wall under the bathroom; and
the close proximity of condenser units and hot water unit overflows with no
observed drainage collection point.
However, I am not satisfied that the factors identified by S have necessarily
contributed significantly to the abnormal moisture conditions at the site.
The Applicant’s engineer (BM) has confirmed that the stormwater infiltra tion pit is
located approximately 15 metres from the area of damage to the southern wall. While
S considered the presence of the pit was reflective of previous stormwater drainage
issues affecting the property, BM says the pit collects minimal stormwater o nly.
Similarly, there is conflicting information as to the likely impact of the recent
installation of a shallow irrigation line adjacent to the brick wall, which S also
identified as likely to have contributed to the bulge.
While S referred to the sewerage pipes underneath the bathroom, there is no
evidence to suggest that any of these pipes were leaking.
Equally, I do not consider S has established any reasonable basis for discounting the
potential significance of the leaking pipe in the bathroom wall cavity as a source of
abnormal moisture conditions.
Case No: 405025 Determination Page 5 of 7
The leak in this pipe has been clearly established and is located directly adjacent to
the area where the displacement of the wall has occurred. While S referred to the
plumbing report as confirming the le ak was “minor”, a copy of this report has not
been provided.
Further, there is no information which establishes how long the leak was present. It
appears that S did not undertake a review of the historical water usage at the
property, despite having earlier recommended that this occur.
As noted by the FSP’s geotechnical engineer (C), given the location of the leak, it is
possible it could have been present for some time before it was detected.
Accordingly, even if the damage to the external wall occurred wholly or partly prior to
the renovations carried out at the property, this does not of itself establish it was not
caused by the leaking pipe.
The FSP’s consulting engineer (S) suggested that the movement of the surrounding
earth could have caused the leak in the copper hot water supply pipes. However,
given the leaking pipe was located at a height of approximately one metre up the
wall, this appears unlikely.
FSP is unable to rely on exclusion for earth movement
As outlined above, the policy contains a general exclusion for damage caused by any
form of earth movement.
However, the FSP is not entitled to rely on this exclusion in circumstances where the
proximate cause of the earth movement is an event which is otherwise subject to
cover under the policy.
As outlined above, the Applicant has established a prima facie claim for accidental
damage and therefore the FSP has the onus of establishing that, on the balance of
probabilities, the exclusion applies.
The FSP’s engineer (S) has acknowledged that the out ward pressure of the retaining
earth which caused the failure of the brick wall may have been caused by abnormal
moisture conditions.
For the reasons outlined above, I am not satisfied that the FSP has established that
the primary source of the abnormal moisture conditions was anything other than the
leaking pipe.
In these circumstances, the FSP is not entitled to rely on the exclusion for earth
movement to deny the Applicant’s claim for the displacement damage to the external
wall.
Available information does not establish structural defect
In his supplementary report, S stated that the earth fill material had been
inadequately retained due to the poor design of the brick wall when the property was
originally built.
Case No: 405025 Determination Page 6 of 7
However, the Appli cant’s engineer (BM) has noted that the version of the relevant
Australian Standards referred to in S’s r eports did not apply when the house was
constructed in 1987.
The Applicant has also provided copies of documents which confirm the footing
system for the house was designed by engineers and inspected by the local council
at the time of construction. These documents were not available to the FSP’s
engineer (S) when he prepared his reports.
S has subsequently identified potential issues as to whether the footings (as
constructed) comply with the council approved plans. However, I am not satisfied that
S has identified any specific defect in the construction of the footings, in light of the
building standards which applied at the time.
On this basis, I do not consider the FSP is entitled to rely on the exclusion for faulty
workmanship and/or structural defects to deny the Applicant’s claim for damage to
the external wall.
Wayne Tank principle does not assist the FSP
The FSP has sought to rely on an established principle of insurance law known as
the Wayne Tank principle. This principle provides that, where damage is caused by
two or more concurrent and interdependent proximate causes and one of these
causes is excluded while the others are not, the FSP may rely on the relevant
exclusion to deny the claim.
In the present case, I am not satisfied that the FSP has established that any of the
excluded factors relied upon constitute an interdependent and concurrent proximate
cause, such that the Wayne Tank principle would apply. Accordingly, this principle
does not assist the FSP.
FSP is liable for damage to external wall
For the reasons outlined above, I am not satisfied the FSP is able to rely on an
exclusion under the policy to deny the Applicant’s claim for the displacement of the
external wall adjacent to the leaking pipe.
Accordingly, the FSP is required to pay the Applicant for the cost of repairing this
damage, in accordance with the terms of the policy. For the purpose of determining
the settlement amount, the FSP is to obtain an updated quote from the contractor
(PW) who provided the initial quotation in February 2015.
Case No: 405025 Determination Page 7 of 7
3 Supporting information
3.1 FOS approach to this dispute
This Determination follows the review of a Recommendation issued on behalf of the
Financial Ombudsman Service (FOS) on 24 September 2015. The Recommendation
was rejected by the FSP.
This case has been decided on its merits, having regard to the relevant law, good
industry practice, codes of practice and previous FOS decisions.
There has been a full exchange of all material information relied on for the purposes
of this Determination and each party has had the opportunity to address any issues
raised by the other. All of the material provided by the parties has been reviewed and
considered.
While the parties have raised numerous issues in their submissions, for the purposes
of this Determination, commentary has been restricted to those issues which are
considered directly relevant to the outcome only.
During the course of this dispute, the Applicant has been assisted by his insurance
broker. For the purposes of this Determination, submissions made by the Applicant’s
broker are treated as having been made by the Applicant himself.