Home / Financial Firm (Unknown - Insurer) / Determination 401475
Determination 401475
Claim denied for foyer ceiling collapse attributed to storm
Summary
The applicants claimed for a foyer ceiling that collapsed after a December storm, and the FSP denied the claim on the basis of faulty installation. AFCA found the defective installation was the proximate cause, that the storm water entry was insufficient to cause the collapse, and that the FSP is not liable.
Where the dominant proximate cause is an excluded defect, the insurer may deny the claim even if an insured peril acted concurrently, under the Wayne Tank principle.
Subjects and remedies
home or building damagenatural disasterno remedy
Text of the determination
Determination
Case No: 401475 Determination Page 1 of 6
Case number: 401475 31 March 2016
1 Overview
1.1 Dispute
The applicants lodged a claim under their home insurance policy with the financial
services provider (FSP) after the ceiling in their foyer collapsed in late December
2014. The applicants believe the damage was caused by the effects of a storm which
occurred approximately two weeks earlier.
The FSP denied the claim on the basis that the damage was not caused by the storm
or by any other event insured against under the policy. The FSP says the damage
was caused by the faulty installation of the ceiling.
1.2 Issues and key findings
Is the FSP liable for the damage to the applicants’ ceiling ?
The proximate cause of the damage to the ceiling was the defective manner in which
it was installed. Damage caused in this manner is excluded under the policy.
Even if the storm did result in damage to the roof (which has not been clearly
established), the volume of rainwater which entered as a result would not have been
sufficient to cause the ceiling to collapse.
The FSP would be entitled to deny the claim even if the storm and the faulty
installation acted together to cause the collapse. At law, an insurer is entitled to deny
a claim where a loss is caused by two interdependent and concurrent causes, only
one of which is excluded.
1.3 Determination
This determination is in favour of the FSP.
The FSP is not liable for the applicants’ claim .
Case No: 401475 Determination Page 2 of 6
2 Reasons for determination
2.1 Is the FSP liable for the damage to the a pplicants’ ceiling ?
Policy provides cover for storm damage subject to exclusions
The applicants are required to show that, on the balance of probabilities, they have
suffered a loss caused by a risk insured against under the policy. This is known as a
prima facie claim.
If the applicants are able to establish a prima facie claim, then the onus shifts to the
FSP to show that, on the balance of probabilities, it is entitled to rely on an exclusion
under the policy or is otherwise entitled to deny the claim.
The applicants’ policy provides cover for loss or damage caused by the events listed
in the policy (including storm), subject to the conditions and exclusions set out in the
policy.
The policy contains a general exclusion for damage caused by or arising from faulty
design or workmanship.
The photographs provided by the parties confirm that part of the mezzanine ceiling in
the applicants’ foyer collapsed on 22 De cember 2014. The remaining section of the
ceiling was removed by the FSP’s contractors as par t of make safe works.
The FSP will only be liable for the damage to the applicants’ ceiling if the proximate
cause of the damage (that is, the real, effective or dominant cause) was one of the
events insured against under the policy.
The applicants say the collapse of the ceiling occurred due to the effects of a storm
on 6 December 2014. Based on reports from their consultants, they believe water
entered the ceiling cavity during the storm, saturating the insulation and causing the
ceiling to detach from the timber framework as a result of the additional loads placed
upon it.
The FSP disputes that the collapse of the ceiling on 22 December 2014 was caused
by the storm experienced two weeks earlier. Based on reports provided by its
structural engineer (CC), the FSP says the collapse was due to defects in the
manner in which the ceiling was originally installed.
Accordingly, in order to determine whether the FSP is liable for the applicant’s claim,
it is necessary to determine the proximate cause of the damage.
As noted above, during the course of this dispute, the parties have appointed several
consultants to determine the cause of the damage. I have carefully reviewed the
reports prepared by the various consultants (together with the other information
provided) in order to determine the proximate cause of the damage.
Experts disagree about relative effects of water entry and installation issues
Both the FSP’s engineer (CC) and the applicants’ engineer (SS) have confirmed that
there are signs of water entry at the applicants’ property. Both engineers also agree
Case No: 401475 Determination Page 3 of 6
that the ceilings at the property were not installed in accordance with applicable
building requirements.
However, the two engineers disagree as to the extent to which each of these issues
contributed to the collapse of the foyer ceiling.
The FSP’s engineer (CC) says the collapse occurred due to a failure of the fixings
which were not installed in compliance with the applicable Australian Standards and
manufacturer’s recommendations. In particular, CC advised that:
the spacing of the screw fixings (at up to 600mm) exceeded the maximum
allowable spacing of 450mm;
the spacing of the glue adhesive points (at up to 400mm) exceeded the
maximum allowable spacing of 250mm; and
the glue appeared to be an inferior product and had been sparsely applied.
CC concluded that these issues would have predisposed the ceiling to premature
failure.
While CC acknowledged there was evidence of water entry in various areas of the
applicants’ property, he c onsidered that minimal (if any) rainwater would have
entered the ceiling cavity during the storm on 6 December 2014. Accordingly, CC
concluded that the collapse was not caused by the storm.
For his part, the applica nts’ engineer (SS) acknowledged that the ceiling showed
signs of poor workmanship, including excessive spacing of the screw fixings and glue
adhesive points.
However, SS considered that the major factor contributing to the collapse was the
rainwater which entered the ceiling cavity during the storm.
In his report, SS advised that:
the high winds experienced during the storm disturbed the solar matting above
the foyer area, causing it to bunch up;
the tangled solar matting blocked the flow of rainwater along the roof, causing
water to back up and enter the ceiling cavity through broken roof tiles under the
matting; and
the water saturated the ceiling insulation and plasterboard, causing it to bow
and buckle and imposing stress on the glue and fixings, which ultimately
resulted in the collapse of the ceiling two weeks later.
SS considered that, even if the ceiling had been installed correctly, it would not have
been able to withstand the loads imposed by the significant volumes of rainwater
which entered the ceiling cavity and saturated the insulation material during the
storm.
Ceiling installation issues were evident throughout the property
The FSP has provided a number of detailed colour photograp hs taken by the
contractors appointed to inspect the property shortly after the applicants lodged their
claim.
Case No: 401475 Determination Page 4 of 6
It is evident from these photographs that, at the time of the storm in December 2014,
the ceilings throughout the property were showing signs of damage and premature
failure, due to the manner in which they had been installed.
The photographs show that the plasterboard ceilings in a number of rooms at the
property were bowed and distorted. While the ceilings in the garage and the internal
pool area were most severely affected, similar issues were also evident in a number
of the other rooms.
The close- up photographs taken by the FSP’s contractors confirm that the screws
affixing the ceilings in a number of rooms had started to “pop”, indicating that the
ceilings were beginning to detach from the timber rafters above.
The FSP’s engineer (CC) advised that the damage to the ceiling in the garage was
so severe that it was at risk of imminent collapse. Photographs confirm that a section
of the plaster in the garage had fully detached from the timber roof frame.
The reports prepared by the applicants’ engineer (SS) did not refer to the b owing and
distortion damage to the ceilings in various parts of the property, as this damage did
not form part of the applicants’ claim.
Nevertheless, the issues with the ceilings which are generally evident throughout the
property are relevant in determining the extent to which the identified installation
defects are likely to have caused or contributed to the collapse of the foyer ceiling in
December 2014.
The applicants have referred to specific issues (such as localised leaks a nd
condensation from the pool heater) which they say caused the issues with the
ceilings in the other rooms of the property.
However, I am not satisfied that the issues identified by the applicants satisfactorily
explain all of the pre-existing issues with the ceilings, given the nature and extent to
which these issues are evident throughout the property (including on both levels).
Accordingly, I am satisfied that the installation issues identified by the FSP’s engineer
(CC) have had a significant effect o n the condition of the ceilings.
Available information does not establish significant water entry
The roofing specialist (AB) appointed by the FSP to inspect the applicants’ roof in
January 2015 did not identify any damage to the terra cotta roof tiles immediately
above the foyer area which might have been caused by the storm.
However, AB noted there was evidence of minor water entry through fractured
roofing tiles in the valley system.
After experiencing ongoing water entry issues, the applicants arranged for the tiles to
be repaired in or around September 2015. The applicants’ engineer (SS) has advised
that two broken roof tiles were identified directly under the solar matting.
The cause of the damage to the roof tiles is not clear. While AB considered the
damage was consistent with having been caused by foot traffic on the roof, the
applicants’ engineer (SS) concluded it was more likely to have been caused by the
Case No: 401475 Determination Page 5 of 6
storm in December 2014 (based on the applicants’ advice that no one had been on
the roof for a number of years).
However, even if the damage to the roof tiles was caused by the storm, I am not
satisfied that the volumes of rainwater which entered the ceiling cavity as a result
would have been sufficient to cause the collapse of the ceiling.
The applicants say the plaster which littered the foyer following the collapse of the
ceiling was waterlogged and mouldy. However, there is no independent information
to confirm the condition of the plaster at this time.
Had substantial volumes of water entered during the storm, the timber roof frame
would be expected to show significant evidence of water staining. However, the
numerous detailed photographs of the inside of the roof cavity taken by the FSP’s
contractors in January 2015 show very little evidence of water staining.
In these circumstances, I am not satisfied that collapse of the ceiling on 22
December 2014 was caused by the effects of the storm which occurred two weeks
earlier.
FSP is not liable for damage to ceiling
For the reasons outlined above, I am satisfied that the proximate cause of the
damage to the applicants’ ceiling was the defective manner in which the ceiling was
designed and constructed. Damage caused in this manner is excluded under the
policy.
Even if I were to accept that rainwater which entered the roof cavity during the storm
operated interdependently and concurrently with the defective installation of the
ceiling to cause the collapse, the FSP would still be entitled to deny the claim.
Where a loss is caused by two proximate causes operating interdependently and
concurrently and one is excluded while the other is not, the exclusion clause
operates to allow the insurer to deny the claim in its entirety. This is an established
principle of insurance law known as the Wayne Tank principle.
Case No: 401475 Determination Page 6 of 6
3 Supporting information
3.1 FOS approach to this dispute
FOS has considered it appropriate to expedite this dispute in accordance with the
Operational Guidelines to the FOS Terms of Reference, due to the nature of the
dispute. Accordingly, this dispute has not been the subject of a FOS
Recommendation and has proceeded directly to Determination.
There has been a full exchange of all material information relied on for the purposes
of this Determination and each party has had the opportunity to address any issues
raised by the other. All of the material provided by the parties has been reviewed and
considered for the purposes of this Determination.
This dispute has been decided on its merits, having regard to the relevant law, good
industry practice, codes of practice and previous Financial Ombudsman Service
(FOS) decisions.
While the parties have raised numerous issues in their submissions, for the purposes
of this Determination, commentary has been restricted to those issues considered
directly relevant to the outcome only.