Text of the determination
Determination
Case No: 393116 Determination Page 1 of 13
Case number : 393116 10 September 2015
1 Overview
1.1 Dispute
The Applicants lodged an insurance claim with the Financial Services Provider (FSP)
for cracking damage caused by a burst pipe under their home.
The FSP denied the claim on the basis that the damage was not caused by an
insured event and that the damage was caused by earth movement, which is
excluded under the policy.
The FSP states the damage was due to seasonal movement of the founding soils,
causing ongoing and long term settlement of the footings.
1.2 Issues and key findings
Have the Applicants established an insured event under the policy?
The Applicants have established an insured event under the policy because:
The policy provides cover for damage caused by the escape of liquid from
pipes.
A water pipe was found to be leaking into the subfloor soil underneath the
staircase.
The cracking damage to the home is recent and localised to around the
staircase.
Is the FSP entitled to deny the claim?
The FSP is not entitled to deny the claim because it has not established the
proximate cause of the damage was earth movement.
1.3 Determination
This Determination is in favour of the Applicants.
The FSP must accept the claim in accordance with the terms and conditions of the
policy.
The FSP must permit adequate drying time (between 12 and 18 months from the
date of repair of the pipe) prior to preparing a scope of works on which to base
settlement of the claim.
Case No: 393116 Determination Page 2 of 13
2 Reasons for Determination
2.1 Have the Applicants established an insured event under the policy ?
The Applicants must establish an insured event
The Applicants bear the onus of establishing they have suffered loss or damage
caused by an insured event covered by the policy.
The policy provided cover for loss or damage caused by liquid leaking, overflowing or
bursting from fixed pipes.
Relevant extracts from the policy are set out in section 3.2 below.
Water pipe leaked into the subfloor soil underneath the staircase
It is not in dispute that a pipe, underneath the house and directly under the internal
staircase, leaked water. The evidence does not indicate how long the leak was
present, however:
the Applicants noticed cracks in November – December 2014
the Applicant‟s plumber located the leak on 23 December 2014
the leak was repaired on 29 December 2014
upon inspection in December 2014 and January 2015, the subfloor soil around
the stumps underneath the staircase was wet with evidence of water pooling
both the Applicants‟ and FSP‟s experts acknowledge the cracks were recent.
The FSP‟s engineer (F) indicates that there is cracking in other locations of the home
which are remote from where the leak occurred. However, these cracks are minor by
comparison and only represent a small proportion of the overall cracking damage.
The evidence, including photographs, shows that the claimed cracking damage is
predominantly in the vicinity of the staircase.
I am therefore satisfied that the Applicants have established an insured event under
the policy.
2.2 Is the FSP entitled to deny the claim?
The policy excludes loss or damage caused by ground movement
Except in limited circumstances, the policy excludes loss or damage that is caused
by or arises from ground movement.
Ground movement is described as:
erosion, vibration, subsidence, landslip, landslide, mudslide, collapse, shrinkage or any other
earth movement.
In order to deny the claim, the FSP has the onus of establishing the exclusion
applies.
Case No: 393116 Determination Page 3 of 13
F considers damage caused by settlement of footings
In its reports, F indicates that the cause of the damage is the result of ongoing and
long term settlement of the footings in the reactive clay foundation soils. It says this is
due to various factors including:
drying of the roots systems of trees close to the building
relatively low rainfall between 1997-2010
normal seasonal or climatic effects
recent low rainfall combined with high temperatures, and
poor surface drainage conditions around the perimeter of the house.
F also addressed the Applicants‟ contention that the leaking pipe was the cause of
the damage. F noted that its floor level survey of the home did not show the uplift or
heave in the vicinity of the staircase. Such heave would be expected if water leaking
from the pipe affected the soil underneath the staircase and caused the damage
claimed.
The Applicants’ experts consider the damage was caused by the leak
The Applicants‟ engineer (M) reported that:
The damage to the plaster walls and ceiling was concentrated i n one area (the
staircase which was above the leaking pipe) and did not occur in other areas.
Fresh water escaped from the defective copper pipe and caused an increase in
the moisture content of the clay founding soil in the vicinity of the staircase.
M‟s floor level survey demonstrates that the area below the staircase has
heaved an average of 2-3cm and caused distress in several locations in the
staircase.
The Applicants have also provided reports by plumber ST and builder ACW which,
while not providing any details of the mechanism by which the damage occurred,
both support the Applicants‟ position that the claimed damage was caused by the
leaking pipe.
Summaries of the reports prepared by the parties‟ experts are set out in section 3.3
below.
Re-levelling fixed any prior ground movement issues
The property is approximately 35 years old. In 1997 an upper storey extension
added. In 2006 the entire home was re-levelled. This exercise involved the addition
or replacement of around 30 concrete stumps underneath the home. The Applicants
say this work was done solely to repair cracks in the plaster walls throughout the
house.
I accept F‟s position that the re -levelling is likely to have been required to deal with
previous ground movement. However, I also accept the Applicants‟ statement that
there has not been any cracking to the house in the eight years since the re-levelling
work was undertaken. The first signs of cracking were in November – December
2014 at which time the Applicants‟ investigations as to the cause led them to detect
the leaking pipe.
Case No: 393116 Determination Page 4 of 13
This is supported by M‟s statements that the cracking was recent (which was
ultimately acknowledged by F), with no dust evident.
I therefore find that the 2006 re-levelling work was successful in stabilising the home
and mitigating the effects any ground movement experienced.
There was increased water usage prior to when the leak detected
There was much debate between the parties regarding the interpretation of the
Applicants‟ water bills prior to detection of the leak and whether the bills
demonstrated a significant increase in water use.
The most telling aspect of the February 2015 water bill (which is for the period 29
October 2014 to 30 January 2015) is the following statement in respect of average
daily usage:
Same time last year: 330 litres.
This account: 462 litres.
This supports the position that significantly more water was used during the
suspected period of the leak over the same seasonal period for the previous year.
This is consistent with the findings of M regarding the evidence of water under the
house. It also supports a finding that there was sufficient water leaking from the pipe
to affect the home.
The cracking is recent and localised
As noted above the cracking is recent and localised in the area of the staircase,
above where the leak occurred. This is despite F‟s opinion that the cracking is due to
differential settlement of the footings due to seasonal variations.
F explained that the trees and vegetation in close proximity to the home would have
a drying effect on the soils (presumably towards the outside of the house). F also
states that the damage from construction of the second storey in 1997 would take
several years to develop which is why the cracking has only developed in recent
years.
I do not consider F‟s reasoning to be persuasive. There is no evidence the cracking
developed “in recent years” as opposed to in November – December 2014 as stated
by the Applicants. If it had occurred over recent years, the cracks would not be
accepted by both F and M as “recent”.
Further, the second storey was constructed in 1997 with the relevelling occurring in
2006. This leaves eight years after the relevelling before any cracks occur and then
they occur almost exclusively above the site of the leak. Even taking into account the
limited shrubbery surrounding the home, I am not persuaded that it adequately
explains the location of the cracking.
Case No: 393116 Determination Page 5 of 13
There is no persuasive evidence that the footings caused the damage
F states that according to the drawings provided by the Applicants, the founding and
footing depths of the strip and pad footings are insufficient compared to current
building standards. However, F acknowledges the current standards may not have
been applicable at the time of construction of the home and the extension.
As no inspection of the subfloor was undertaken by F, F‟s suspicion of whether the
footings were a cause of the damage could not be confirmed. This is particularly
relevant given the relevelling work undertaken in 2006 was not apparent on the
drawings inspected by F (and as such F was unaware what, if any, changes were
made to the size or depth of the footings).
Even if I were to accept F‟s argument that the current footings of the home make it
more susceptible to foundation soil movements, given the location and timing of the
cracks, I am not persuaded that any such deficiency in the footings was the
proximate cause of the damage.
The floor levels are not persuasive in establishing the proximate cause
F states the most persuasive evidence that the leak did not cause the cracking is that
its floor level survey shows there is no localised pattern of heave in the vicinity of the
staircase. This would be would be expected from water affecting highly reactive clay
soil. F says, in contrast, that the level survey shows relative settlement in the area of
concern, with no localised movements.
By contrast M states its level survey shows heave around the stairs.
A copy F‟s and M‟s level surv ey is reproduced at section 3.4 below.
Both floor level surveys indicate the bath and laundry to the north of the staircase sits
higher than the staircase, and that the study, to the south of the stairs sits lower. The
hallway and living room to the east of the stairs also sit lower than the stairs. I
therefore do not accept F‟s position that there is a relative settlement (associated
with long term foundation drying/shrinkage) within the vicinity of the stairs.
While the Applicants referred to a bulge in the hallway floor, it was not evident to me
where this bulge occurred, or that either M or F considered it in their reports.
Overall, I do not consider the floor level surveys are persuasive in establishing either:
that the leak was not the proximate cause (that is, the dominant, effective or
operative cause) of the damage, or
that there was another proximate cause of the damage as suggested by F.
The FSP has not established the exclusion applies
On balance, the FSP has not established the proximate cause of the damage is earth
movement. This is because:
the re-levelling of the house in 2006 resolved prior ground movement issues
the water bill supports the position that there was a significant leak under the
stairwell
the cracking is recent and localised to the area above the leak
Case No: 393116 Determination Page 6 of 13
there is no persuasive evidence that the footings caused the damage
the floor level surveys are not persuasive in establishing a cause of the
damage.
The FSP has therefore not established that the exclusion applies.
Accordingly, the FSP is not entitled to deny the claim.
Case No: 393116 Determination Page 7 of 13
3 Supporting information
3.1 The FOS Approach
I have determined this dispute based on what is fair in all the circumstances, having
regard to the relevant law, good industry practice, codes of practice and previous
FOS decisions. I have taken into account all the material submitted by the parties.
There has been a full exchange of all documents relied on to make this
Determination and each party has had the opportunity to address any issues raised
by the other.
This dispute has been expedited to a Determination. No Recommendation was
issued.
3.2 Policy provisions
What you are covered for - Insured Events
We cover the building for loss or damage at the insured address caused by an insured event
during the period of insurance. There are some things we do not cover and thes e are shown in
the „We do not cover‟ section of the following tables on pages 16 to 25 and in the „What we do
not cover – gener al exclusions‟ on pages 35 to 40.
…
Escape of liquid
We cover
Loss or damage to the building caused by liquid leaking, overflowing or bursting from any of the
following:
…
• any drain, fixed pipes, roof gutters or guttering and rainwat er downpipes, drainag e and
sewage systems;
…
What we do not cover - general exclusions
You are not covered under any section of your policy for damage, loss, cost or legal liability that
is caused by, arises from or involves:
…
Ground movement
erosion, vibration, subsidence, landslip, landslide, mudslide, collapse, shrinkage or any other
earth movement, but we will cover landslide or subsidence that is specifically covered under the
following insured events:
• „Storm‟;
• „Flood‟ (but only if you have cover for ins ured event „Flood‟);
• „Earthquak e and Tsunami‟;
• „Explosion‟.
…
Case No: 393116 Determination Page 8 of 13
3.3 Reports referenced
Record Key points
Applicant’s
plumber ( ST )
Report
undated
Attended Applicants‟ property 23/12/2014 – water leak. There was an area
that seemed to have sunk.
Burst copper pipe located directly underneath staircas e of house
Damage to house caused by excess amount of water under the hous e
sitting around the piers – appears to have been there for a fair amount of
time prior to discovery
Leak repaired 29/12/2014 by re - running line and conn ecting to existing
drop points
(Photographs attached to report.)
FSP’s engineer
( F )
Report
30 Jan 2015
Inspection of Applicants‟ property 16/01/2015
Building 35 y/o. Extension above western section of house added 1996
Site relatively flat – poor ground s urface drainage (garden beds adjacent to
building and no adequate paving around perimeter)
Numerous cracks to plasterboard walls/ceiling – predominately in central
section of house underneath staircase. Gaps and cracks to cornices
underneat h staircase. Stud y cupboard doors catching. Plasterboard cracks
from corners of openings in living room. Cracks to hallway floor tiles
Evidence of previous re - levelling/re - packing of concrete stumps beneath
house
Floor levels – taken with Zip LevelPro - 2000‟ accurate to +/ - 2mm - varied
by up to - 58mm (datum at SW cnr in laundry.)
Pattern of relative settlement to N and NE sides of home. Not able
variations throughout.
No signs of localised movement of floor/footings around location of
reported wat er pipe leak.
Applicant‟s wat er bills (4/2/14, 2/5/14, 1/8/14. 31/10/14) do not show
significant increase in water usage.
Appl noticed damage (mostly beneath staircase area) Nov/ Dec 2014.
Damage has increased since that time.
Appl‟s re - stumping contractor advised (Appl) that soil beneath home –
mostly beneath staircas e area – was very wet.
Appl‟s plumber discovered water pipe leak 12/ 12/14. Leak repaired
29/12/ 14.
Damage observed (by F) considered non - structural.
Damage does not appear recent. Re - levelling/ re - packing suggests
footi ng/floor movement and subsequent damage has been occurring for a
long time.
Site expected to have highly reactive clay foundation soils – subject to
notable volumet ric changes with change is moisture content.
Location and pattern of cracking observed typic al of damage caused by
long term differential footing movements in reactive clay soils
Caus es of changes to soil moisture content include:
o Tree root drying – trees close to building
o Relatively low rainfall 1997 - 2010
o Normal seasonal/climatic effects
o Recent low rainfall plus high temps (summer 2012/13 & 2013/14)
Case No: 393116 Determination Page 9 of 13
Record Key points
o Poor surface drainage around perimeter of home
Drawings provided by Applicants show original footings undersized by
current standards. Strip footings in highly reactive sites should be 1m
(min). Ack nowledged that requirements may not have been applicable at
time of build. However founding/footing depths are less than required and
susceptible to foundation soil movements
Drawings provided for upper floor extension – F suspect no adequat e and
sufficien t supports in subfloor to provide support for upper storey loadings.
If leaking pipe inc reased moisture content of clay foundation soil to extent
that footing movement occurred, it would have been heave. However,
relative footing settlement (long term dryi ng/shrink age) was observed in
area of concern.
Opinion – leak event did not cause or cont ribut e to observed damage.
(Photos & indicative floor level survey diagram attached)
Applicant’s
builder (ACW)
Report
22 Feb 2015
No date of inspection provided.
Floor at Applicants‟ property out of level
Movement in stumps and footings due to change in moisture content of soil
Soil too wet and ponding in places - leaking pipe found under house
Strongly thinks the leaking pipe contributed to movement of stumps an d
footing causing walls to crack.
Applicant’s
engineer (M)
Report
17 Mar 2015
Building is 35 y/o and appears well maintained
1 st floor added in 1996. In 2006, entire ground floor was re - levelled and 30
new stumps added to strengthen entire structure
Water consumption bill (Feb 2015) show increase of 121 l/d over Oct 2014
bill
Cracking noticed by Applicants in Dec 2014 and became worse in early
2015. Leaking pipe discovered in subfloor area – now repaired.
Inspection 12/03/2015 – cracking found in various locations including:
o 1 - 3mm crack found beneath timber stairs in study (1m long)
o cornice in study detached in left corner
o cornice and ceiling cracks to study‟s hallway
o 5mm wide gap (appeared fresh and recent as minimal dust found
inside) between stair landing and support wall below
o gap between staircase wall and hallways tiles
o diagonal crack to corner of opening from hallway into living room
o cracking in plaster wall and ceiling localised to staircase area.
Floor level measured throughout ground fl – sho wed floors within staircase
had heaved an average of 2cm
Stump foundations of dwelling support ed on clay soil. Adequate subfloor
ventilation installed
Founding soil is expected to be highly reactive clay.
Packers found on several stumps (2006 re - levelling )
Subfloor topsoil underneath staircase was damp – sample taken showed
clay soil was wet and saturated
Sample of subfloor soil under laundry and bathrooms areas found to be dry
and stiff.
Existing bearers/floor joists in serviceable condition
Opinion - wat er escaped from defective pipe causing increase in moisture
Case No: 393116 Determination Page 10 of 13
Record Key points
content of clay founding soil. Clay increases its volume as moisture
content increases – this has caused stumps to rise and move foundations
Expansion of clay soil consistent with heaving of floor level in staircase
area (2 - 3cm) – this has caused distress in staircase
It appeared dwelling had past seasonal floor movement – but ground fl re -
levelled and strengthened (2006). Seasonal movement after 2006 minimal
as most stumps have settled over a long period of time.
Damage to plaster walls/ceiling concentrated in one area (staircase above
burst pipe. No cracking in other areas.
Opinion - damage to staircase area is result of burst pipe.
Recommend subfloor dried out (generally 12 months) before repair work
undertaken. Floor levels to be measured after drying to ensure no more
stump movement.
(Photos and floor level/damage location diagrams attached)
FSP engineer (F)
Supplement ary
report
26 Mar 2015
F has reviewed reports by ACW and ST, wat er bill Feb 2015, and
comments from Applicant.
Re: Appl‟s statement that F did not inspect subfloor space – attending
engineer inspect via external hatch at SW cnr of house, general conditions
of ground and stumps assessed
Purpose of that inspect was to determine cause of damage – F visually
inspected site and damage and took floor level survey – entry to subfloor
not considered necessary for this purpose. Footing movement cannot be
determined by inspection of subfl oor area. Floor level survey considered to
be suitable for determining caus e.
Re: Appl‟s concern that no dry - out period provided in initial report – F
would normally recommend a 12 - 18 month drying period aft er the repair of
a leak event. (A Scope of work w ould only be provided if claim accepted).
F cannot confirm age of damage to home – but report conclusions (re:
cracks result of ongoing/long term footing settlement and not heave) are
not invalidat ed.
Water bill for Feb 2015 (not available until recently) does not show
significant increase in usage for 3 months during which water leak
occurred – appears within normal range for property:
o Ave daily usage 2014 approx. - 405 l/d
o Ave daily usage for Feb 2015 – 462 l/d
o Ave daily usage in Jan 2013 – 480 l/d
o F op ines that volume of wat er escaping from pipe (prior to
discovery/repair) would not have been a significantly large
o Amount of water escaping has not caused/contributed to observed
footing movement and damage to home.
Reports by ACW and ST state leaking wat er contributed to damage, but do
not explain soil behaviour in presence of leaking water, or how mechanism
of failure is linked with leak.
Restumping/relevelling (11 years after upper floor extension) does not
imply that adequate supports for u pper storey have been provided.
Restumping most likely to address overall building movements – rather
than providing localised supports for upper extension.
Findings of earlier report unchanged.
Case No: 393116 Determination Page 11 of 13
Record Key points
FSP expert (F)
Supplement ary
report
7 Apr 2015
F has reviewed report by M.
F opined that floor levels by F and M cannot be interpreted as localised
heave in vicinity of leak
o Floor levels recorded by M show general pattern of settlement towards
NE side of house – differential footing movement of up to 70mm. S imilar
contour pattern found in F‟s recorded levels, with differential footing
movement of up to 58mm. Variation in level recorded by M and F
(noting differing dat um point used)
o Unclear how M has concluded upward movement/heave around
staircase area. Neit her M nor F floor level surveys show a localised
pattern of heave in immediate vicinity around staircase.
o M and F floor levels around staircase are lower than levels of SW corner
of laundry
Reactive clay soils are of relatively high plasticity and low per meability
which resist water flow to significant depths and volumes. Majority of
(escaped) water would remain within upper – relatively permeable soil
level
Unclear what depth of soil was checked by M for saturation – can only be
confirmed by geotec h inves tigation
Absence of discernable pattern of heave around staircase shows leak has
not adversely affected foundation soils under footings.
Re - leveling and re - packing of home:
o does not strengthen structure as M suggests (this can only be achieved
by deepening the footings – no evidenc e that this occurred)
o does not affect seasonal movement of site, as M suggests, in any way.
(Address of adverse site conditions – eg drainage – is required for this)
Agree majority of cracking is within staircase area, bu t there are
plasterboard cracks elsewhere eg: living room, bedroom 1.
o Occurrence of more damage around staircase reinforces F‟s theory that
no adequate/sufficient supports in subfloor to support additional load of
upper floor extension. Re - stumping does no t necessarily imply adequate
supports for upper extension
Movement of building is not recent – evidenced by re - levelling
Unclear exact timeframe for damage occurrence, but sudden appearance
of cracks does not show that burst water pipe under staircase has
caused/contributed to damage
Photos of cracking in home attached
Case No: 393116 Determination Page 12 of 13
3.4 Level surveys
F’s level survey
Case No: 393116 Determination Page 13 of 13
M’s level survey