Home / Financial Firm (Unknown - Insurer) / Determination 389164
Determination 389164
Denial of verandah collapse claim
Summary
The Applicants claimed for a collapsed verandah pillar after strong winds, and the FSP denied the claim under wear and tear and rust exclusions. AFCA found the expert evidence showed corrosion of the steel anchor caused the collapse, so the exclusions applied and the FSP may deny the claim.
Once the insurer proves on the balance of probabilities that an exclusion applies, the claim may be denied, and the builder's expert evidence established rust and wear and tear as the cause.
Subjects and remedies
natural disasterno remedy
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
claim
Determination
Case No: 389164 Determination Page 1 of 5
Case number : 389164 2 April 2015
1 Overview
1.1 Dispute
The Applicants lodged a claim for a collapsed verandah with their home insurer,
the Financial Services Provider (FSP).
The FSP declined the claim on the basis it was due to excluded factors, such as
rust or wear and tear. The Applicants state the damage was due to strong winds.
1.2 Issues and key findings
Can the FSP deny the claim?
The FSP can because:
the expert evidence from builder CRM substantiates the damage was due to
wear and tear or rust; and
damage caused by these factors are excluded under the policy.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is entitled to deny the Applicants’ claim.
Case No: 389164 Determination Page 2 of 5
2 Reasons for Determination
2.1 Can the FSP deny the claim?
The Applicants have established a prima facie claim
The policy held by the Applicants covered them for accidental damage. There is
no dispute the loss falls within this insured event.
Instead, the FSP is relying on a number of exclusions to deny the claim, inc luding
the following:
“This Policy does not cover loss … or damage …
9. caused by or arising from … wear and tear …
…
Unless We state differently in this Section We will not pay for: …
h. loss or damage which is caused indirectly or directly by: …
iii. r ust …”
In accordance with legal principles, the FSP must establish the exclusion applies
on the balance of probabilities.
I accept there were strong winds but not to the degree of 89km/hr
The Applicants have provided evidence to support their position that there were
strong winds that day. In particular, there is a diary note from the male Applicant
estimating the winds to be 70km/hr and rising.
It appears this speed was based on his own estimate given there is no reference
in his diary that he consulted a measuring device.
The Applicants have provided records from a weather station approximately 45km
away from the property to support their position about the wind speed. This
measured the peak wind as 89km/hr.
However, the FSP has also provided records from a weather station
approximately 30km away which measured the peak wind as 15km/hr.
Given this, I am not prepared to accept the measurement of a weather station
further away from the property reflects the winds experienced on the day.
However, given the Ap plicants’ diary note and the fact they have provided 10
photographs of trees and branches collapsing, I accept that strong winds of a
certain degree were experienced on the day of the loss.
CRM’s conclusions are supported by the available facts
The FSP is relying on the report of a licenced builder (CRM) following an
inspection of the damage.
CRM did not accept strong winds caused the damage. Instead, he found the
damage was due to the deterioration of the steel reinforcement bar that anchored
the pillar which collapsed. This in turn caused the extent of loss the Applicants are
now claiming for under the policy.
Case No: 389164 Determination Page 3 of 5
Having carefully read his report and considered the available evidence, I accept
CRM’s conclusion for the following reasons.
First, and of most significance, there is a photograph of the steel reinforcement
bar. This shows it is heavily corroded.
Second, according to the Applicants, the only structural damage caused by these
strong winds appears to be isolated to this one pillar. The 10 photographs
provided by the Applicants do not show any structural damage but rather fallen
branches.
I note one photograph showed possible damage to a fence. However, this
appeared to have been caused by a fallen tree branch. It does not appear this
fence was damaged by the wind itself.
Third, CRM’s conclusion was also based on his observation that the base of the
pillars were unsealed against the top of the brick wall. This allowed rainwater to
enter the pillar or wall junction underneath the pillars as well as through small
cracks in the brick wall.
This in turn caused the corrosion found and ultimately led to the loss.
The Applicant has not refuted this and CRM’s observation is plausible given there
is no dispute the steel bar is heavily corroded.
Fourth, CRM noted that given the weight of the pillar was approximately 65kg, it is
unlikely a strong wind would have such effect on this isolated part of the home but
nowhere else.
This reasoning is plausible and logical.
The Cyclone Yasi report does not contradict CRM’s conclusion
To rebut the last point, the Applicants have submitted a 127 page report of the
structural damage sustained to homes during Cyclone Yasi.
The Applicants have referred to aspects of the report which shows instances
where verandas and carports suffered damage but minimal damage to the roof
was sustained.
This, in their view, highlights the fact strong winds can result in damage isolated
to verandas.
However, I do not consider this report adds much value or contradicts CRM’s
findings for the following reasons:
it is general in nature;
it is unclear whether any of the verandas identified were analogous to the
Applicants’, which involved a pillar that weighed approximately 65kg and
contained a steel reinforcement bar; and
it is clear the winds experienced by the Applicant were not comparable to a
cyclone.
Case No: 389164 Determination Page 4 of 5
The second point I consider to be most significant as the individual attributes of
the Applicants’ veranda has been relied upon by CRM in arriving at his conclusion
and is not refuted by the Cyclone Yasi report.
CRM’s report supports the finding that the presence of rust caused the loss
The Applicants dispute the presence of rust automatically infers this was a cause
of damage given no testing was done.
However, the FSP’s position is supported by CRM. CRM is a licensed builder and
therefore qualified to provide an opinion on this issue. Further, I have accepted
his conclusions is supported by the available evidence for the reasons outlined
above.
Therefore, after careful consideration of all of the evi dence and the Applicants’
arguments, I am satisfied the FSP has established on the balance of probabilities
that the damage was caused by wear and tear or rust.
As these factors are excluded under the policy, I am satisfied the FSP is entitled
to deny the Applicants’ claim.
3 Supporting information
3.1 Expert Report
Record Key points
FSP’s expert ( CRM )
Report
12 Nov 2014
The verandah is corrugated, galvanized, painted metal
roofed structure with hardwood beams, hardwood rafters
and hardwood battens
The verandah encompasses the entire perimeter of the
structure
The collapsed section was approximately midway along
the northern elevation
The rafters and battens were still attached to the beam and
unaffected by the collapse
The base of the pillars were anchored to a n approximately
750mm high brick wall by a single approximately 10mm
wide steel reinforcement bar protruding from the base of
the pillars into the mortar joins of the wall
The base of the pillars were unsealed against the top of
the wall and rainwater was able to enter the pillar / wall
junction
The collapsed pillar had broken into two pieces
No evidence of impact to the collapsed pillar and brick wall
Observed heavy corrosion to the steel reinforcement bar
that had previously joined the two sections and a lso
anchored the pillar to the wall
None of the roof sheets to the verandah were missing
If the verandah was affected by strong winds, this would
have dislodged several of the loose roof sheets which
Case No: 389164 Determination Page 5 of 5
weigh significantly less and were not well secured
Summary
The steel reinforcement bar and anchor to the pillar has
deteriorated over time due to entry of moisture
This moisture has weakened the structural integrity of the
steel within the pillar and the anchor, causing the pillar to
break in half
Unable to attribute the damage to wind following a storm