Determination 388520

Denial of home building water leak damage claim under erosion and landslide exclusion

FirmFinancial Firm (Unknown - Insurer)
Decided2015-06-26
ProductGeneral Insurance · Home building and contents
OutcomeFor the complainant
Amount awarded—
Non-financial loss—
Amount claimed—
SourceAFCA PDF

Summary

The applicant's home building claim for water leak damage was denied by the FSP under an erosion and landslide exclusion. AFCA decided in favour of the applicant, requiring the claim to be settled, the investigating leaks benefit paid, engineer report costs reimbursed up to $3,000, and interest on any cash settlement.

The FSP bears the onus to establish an exclusion, and on the balance of probabilities the applicant's engineer's failure mechanism, not earth movement, was more likely, so the exclusion was not established.

Issues

Subjects and remedies

pay claimpay compensationpay interest

Related

All Financial Firm (Unknown - Insurer) determinations · Find similar determinations

Text of the determination

Determination General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of Claim - Exclusion/Condition Determination Case No: 388520 Determination Page 1 of 9 Case number: 388520 17 June 2015 1 Overview 1.1 Dispute The Financial Services Provider (FSP) denied the Applicant’s claim for damage to her home building as a result of water escaping from a leaking pipe. The damage started occurring around early 2014. The FSP says the damage was concurrently caused by a water leak and ongoing atmospheric conditions and thus the Wayne Tank principle applies to defeat the claim. Alternatively, it says the policy exclusion for “ erosion and landslide ” applies. The Applicant disagrees and says the damage was due to a water leak, which is covered by the policy. She wants the FSP to pay her claim in full. 1.2 Issues and key findings Has the Applicant established an insured event caused her loss? The Applicant has established an insured event caused her loss. The available evidence establishes, on the balance of probabilities, the proximate cause of the damage was a water leak, which is covered under the insured event of “leaks”. Has the FSP established the application of an exclusion? The FSP has not established the application of an exclusion because:  the evidence is unclear as to whether there was any earth movement  SM’s evidence (the Applicant ’s e ngineer) is very persuasive and this indicates there was no earth movement involvement (per se) in the failure mechanism which caused the damage. 1.3 Determination This Determination is in favour of the Applicant.  The FSP is to settle the Applicant’s claim for damage to her property in accordance with the terms and conditions of the policy.  The FSP is to pay for the policy benefit of “investigating leaks” in accordance with the terms and conditions of the policy and subject to the Applicant giving the FSP the relevant document (eg, a tax invoice) to show her expense.  If the FSP cash settles the claim, it is to pay interest on the settlement amount in accordance with section 57 of the Insurance Contracts Act 1984 from 19 Case No: 388520 Determination Page 2 of 9 December 2014, being the date of the FSP’s final decision , to the date settlement is made.  The FSP is also to reimburse the Applicant the cost she incurred in obtaining her engineer report, subject to her providing the FSP with the relevant document (eg, a tax invoice) to show her expense and subject to the limit of $3,000 as outlined in paragraph 9.4 of the FOS Terms of Reference. Case No: 388520 Determination Page 3 of 9 2 Reasons for Determination On the balance of probabilities:  the Applicant must prove her loss was caused by an insured event  the FSP must then prove the claim is not covered or is otherwise excluded. 2.1 Has the Applicant established an insured event caused her loss? Evidence indicates the cause of damage was the water leak According to the policy details, the Applicant has cover for listed insured events for the home building (there is accidental damage – advanced cover – but only for contents). As the damage relates to the home building, the Applicant must establish one of the listed insured events caused the damage. The expert evidence (as per section 3.2 below) coincides in that the proximate cause of damage was the water leak. Neither of the parties disputes this. The policy covers the insured event of “leaks”, which is described as: “Leaks are liquids that are leaking, bursting, discharging or overflowing from certain items or devic es.” Based on the expert evidence and the policy cover, I am satisfied the Applicant has established the claimed loss was the result of the insured event of “leak s ”. The FSP must now establish the claim is not covered or is otherwise excluded. 2.2 Has the FSP established the application of an exclusion? Policy excludes earth movement no matter how it is caused The policy has a general exclusion for “erosion and landslide”, which says: “ General exclusions These general exclusions apply to all of the cover we provide under your policy. We don’t cover you under your policy for loss or damage to your home or contents or legal liability which is caused by or arise s in connection with any of the following items or events: … Erosi on and landslide  Erosion, landslide, subsidence, vibration, earth shrink age or expansion or any other earth movement no matter how it is caused (but we do cover earthquake and we cover some landslide or subsidence that happens within 72 hours of the first loss or damage to your home or contents caused by the flood or water runoff – see page 20).” Initially, the FSP relied on this exclusion and on the Wayne Tank principle (applied to two alleged, not inter dependent, proximate causes, ie, the water leak and meteorological conditions). The FS P’s engineer (IS) in its first report considered meteorological conditions were a contributory factor. However, following receipt of the report from the Applicant’s engineer (SM), IS issued a second report stating meteorological conditions were not the cause. Case No: 388520 Determination Page 4 of 9 In light of this, the FSP has said it relies only on the “erosion and landslide” exclusion. Evidence is unclear as to whether there was any earth movement Both experts have an explanation for the failure mechanism that potentially caused the damage:  IS says elevated moisture levels at the time of the leak would have caused ground movement, which in turn, would have caused the majority of the damage  SM says the leak would have affected the soil’s strength and cause foundation movement, this in turn causing the reported damage. IS accepts SM’s explanation as plausible and states both likely occurred simultaneously to a greater or lesser extent, to result in the failure observed. The experts’ conclusions do not assist in clarifying which of the two failure mechanisms is more likely to have happened (or if they occurred simultaneously) and, thus, whether there was any involvement of earth movement in the causation chain. SM’s evidence is more persuasive In light of this, it would be reasonable to consider both causes contributed to the damage. However, a further review of SM’s report and IS’s second report persuades me that SM’s reported failure mechanism is the most likely to have occurred. I note:  Despite SM noting a lack of specific evidence of earth movement ( heave and settlement ), IS does not specifically address or rebut this comment in its second report .  IS accepts SM’s findings as a plausible failure mechanism .  IS appears unsure as to contributory causes (withdrawing its position regarding the meteorological conditions) and its own reported failure mechanism, conceding both his and SM’s reported failure mechanisms could have happened at the same time. The fact IS does not address SM’s concern regarding the lack of observation of earth movement makes IS’s findings less compelling. Without any further information or a rebuttal, it appears findings were made without verifying there was actual earth movement. Further, SM appears more certain of its failure mechanism than IS given IS changes its position regarding the meteorological conditions and concedes SM’s findings are plausible. Accordingly, I am satisfied, on the balance of probabilities, it is more likely the damage occurred in the way SM described, which does not involve earth movement as part of the chain of causation. Case No: 388520 Determination Page 5 of 9 FSP has not established application of exclusion The onus is on the FSP to establish the application of the exclusion on which it seeks to rely. In this instance, the evidence to hand is insufficient to establish on the balance of probabilities that the exclusion for “erosion and landslide” applies to this claim. Therefore, the FSP cannot rely on this exclusion to deny the claim. FSP is to pay additional expenses I consider the report the Applicant obtained from SM has been pivotal to the findings of this decision. Accordingly, it is fair in all circumstances for the FSP to reimburse the expenses the Applicant has incurred in obtaining this report, subject to her providing the adequate document for proof of expenses. As per paragraph 9.4 of the FOS Terms of Reference, the FSP’s contribution to the cost for the report shall not exceed $3,000. Further, the policy has an extra benefit for “investigating leaks”. As I am not satisfied the FSP has established the exclusion for “erosion and landslide” , it is liable for settlement of this extra benefit as well. Case No: 388520 Determination Page 6 of 9 3 Supporting information 3.1 FOS approach for this dispute This dispute has not been the subject of a FOS Recommendation. Due to its nature, FOS has considered it appropriate to proceed directly to Determination in line with the Operational Guidelines to the FOS Terms of Reference. There has been a full exchange of the relevant material between the parties and each party has had the opportunity to address the issues raised. While the parties have raised numerous issues in their submissions, for the purposes of this Determination, I have restricted its commentary to those issues which I consider directly relevant to the outcome only. The Applicant is represented. For the sake of brevity and clarity in this decision, both the Applicant and her representative have been referred to as “the Applicant”. 3.2 Key points on relevant expert materials/statements Record Key points FSP’s engineer (IS) Report 28 Oct 2014  There is some damage, such as hairline cracks in the northern footpath which the insured says predate the leaking water pipe.  The brickwork crack shape in the external face of southern elevation indicates there has been relative ground movement. Other observations are also consistent with the assessment of differential ground movement.  The large two storey brick veneer wall has not articulation and is thus brittle and will easily crack.  The water leak occurred in April 2013 , after a prolonged period of rainfall recorded in the area. The so i l supporting the building would have contained elevated moisture levels at the time of the leak.  As the leak occurred under the footpath and the surrounding soils had a heightened soil moisture level, it would have been nearly impossible for further additional water to drain away quickly.  Rather, the large volume of water would have migrate d throughout the supporting building soils to those with relatively lower moisture content until all soil would have had a similar moisture level.  Such conditions would result in some level of overall heaving of the supporting soils under the building. Thi s then results in an overall heaving and rising of the building.  Rain falls on the ground and drains away from the building over time. However, the water leak occurred under the footpath and likely had little opportunity to drain away from the building.  Th erefore, the heave in the building was largely due to the water leak and not the rainfall.  The leak was detected and fixed coincidentally as the rainfall over the site reduced dramatically. The perimeter ground moisture would have Case No: 388520 Determination Page 7 of 9 drained away from the bui lding.  Then, the moisture contained and trapped within the soil under the building would have subsequently migrated outwards, towards the now relatively drier soils surrounding the building.  The soil in the southeast corner of the building was “retained fi ll”, whereas the soil near the leak was “natural”. The southeast corner would have been able to drain much easier and quicker by virtue of the more granular nature of the fill material under the slab.  The natural ground at the leak would have drained much slower due to its location and lower hydraulic conductivity. As the ground dried out, soils would have shrunk and settled, but at a differential rate, with the southeast corner being the fastest.  Therefore, it is unsurprising the location of the crack appe ars close to the cut - fill line of the site.  The external brickwork cracking, upper level cornice distortion, floor out of level and lower level cornice distortion relate to building movement (heave and settlement) as a direct result of the water leak.  The damage has been exacerbated by meteorological conditions before and after the leak and the lack of articulation in the external building fabric. Applicant’s engineer (S M ) Report 2 4 Mar 201 5  Before the crack being observed in the southeast wall, there was no prior cracking or movement. This confirms the damage has not been impacted by any lack of maintenance or pre - existing building defects.  It is likely all relate to building movement as a result of the water leak.  IS’s report clearly shows there is no cracking in the area of the stated heave or to adjacent retaining walls and building structure.  There was no cracking detected in the building adjacent to the nominated water leakage point or any cracking evident to adjacent structures (retaining walls).  T here is no vertical movement of brickwork at the crack (which is 8m west of the corner), confirming the brickwork skin cracking is the result of foundation rotation only. There is no failure of the foundation footing.  The rainfall data IS used is consisten t with previous year’s recordings and thus, not unusual.  As such, it is unusual to rely on comments that the damage has been exacerbated by meteorological conditions in one part of one structure, while not affecting any other part, nor any of the adjacent retaining structures.  If meteorological conditions were a contributing factor, cracking would have shown after the 2011/2012 summer and 2012 winter drying period.  SM does not accept the damage was exacerbated by meteorological conditions. Exacerbation by m eteorological damage is not demonstrated, merely assumed.  IS says the heave was largely due to the water leak and not the rainfall. SM does not provide any evidence to confirm observation of heave. Consequently, the relevance of IS’s comment is lost and th e comment the water leak heaved a residential is not supported.  The fact this causation was not evidenced during any previous time Case No: 388520 Determination Page 8 of 9 of wet and dry periods indicates this failure mechanism is improbable.  If localised heaving was an issue as suggested, all th ese structures would have evidence of movement and cracking.  Further, there is no evidence of heave detected.  The damage occurred following the repair of the water leak. This suggests the drying action in the soil structure supporting the foundation was a contributing factor.  Moisture content was maintained by non - meteorological sources (eg, from the water leak).  A long term water leak has been listed as another probable cause . However, there is no damage to the surrounding structures.  This is because these structures were founded on class M clays where forces generate d by the swelling and drying cycles in the support soil structure were insufficient to cause damage.  The sand backfill in the trenches to and from the downstairs bathroom, plus the fill over th e natural surface would provide a “pathway of least resistance” for water to flow from the leakage point.  The natural ground slopes in the southeast, so all the leakage water from the water supply service would have gathered in the southeast corner of the residence, permanently maintaining a wet condition and low soil strength in this region.  The fact it is a long term leak would mean the low strength condition would have been maintained in the founding soil structure until the water leak was stopped.  Over a period, the foundation movement from the low support strength would have generated tensile forces in the top of the brick wall due to the rotating footing.  These tensile forces would increase over time until cracking of the wall and lowering of the front load bearing wall occurred at the southeast corner.  This, in turn, would result in the lowering of one end of the trusses, until they were bearing on an internal wall.  The most probable cause of cracking was foundation movement resulting from a leak in th e supply service. FSP’s engineer (IS) Report 10 Apr 2015  IS is not saying the meteorological conditions are the contributory cause surrounding movement and the damage. Rather, the water leak occurred at a particular time of the year/season, which provided a disadvantaged set of surrounding circumstances.  No damage wa s detected previously and the building was likely well built and maintained.  However, this does not mean it does not move at all with varying moisture conditions, it clearly does. It means the footing system has been well built to accommodate soil movement over the life of the structure.  It is plausible the plumbing leak caused changes in moisture levels which could have resulted in building movement beyond what it was originally designed for and had experienced up to that point.  IS’s mechanism relates to changes in soil moisture content causing earth movement and subsequent foundation movement. SM’s mechanism relates to moisture causing soil degradation and carrying Case No: 388520 Determination Page 9 of 9 capacity and subsequent foundation movement.  Both IS and SM’s fai lure mechanisms are plausible and very likely both have occurred simultaneously to a greater or lesser extent, to result in the failure observed. It is not possible to determine what proportion either mechanism contributed to the damage.  The root cause of the building movement is the water leak. The meteorological conditions are not the cause.  The water leak changed the moisture levels in the supporting soils, which in turn has changed the characteristics of those soils and the building movement and damage have subsequently occurred. 3.3 Other relevant materials relied upon  Product disclosure statement with effective date 1 July 2012.  Certificate of insurance for the period 2 April 2014 to 2 April 2015.  Appendices to IS’s report dated 28 October 2014.  Various images of the building and the reported damage.  Parties’ submissions.

Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.