Summary
The Applicants claimed for cracked brickwork and cupped flooring, attributing it to broken stormwater pipes, but the FSP denied the claim citing poor subfloor ventilation and ground movement. AFCA found the escaping water was not the proximate cause of the damage, so the denial stands.
The Applicants bore the onus of showing an insured event caused the damage, and the evidence did not establish that the stormwater leak was the proximate cause, while ground movement is excluded under the policy.
Subjects and remedies
home or building damageno remedy
Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
Claim - Exclusion/Condition
Determination
Case No: 386168 Determination Page 1 of 8
Case number : 386168 13 July 2015
1 Overview
1.1 Dispute
On 24 July 2014, the Applicants lodged a claim under a home insurance policy
held with the Financial Services Provider (FSP) for damage sustained to the
property as a result of water escaping from broken drainage pipes.
The FSP denied liability for the claim on the basis the damage was caused by
poor subfloor ventilation and long term differential movement. The leaks from the
drainage pipe had not contributed to the damage and the policy also excluded
damage caused by ground movement.
The Applicants dispute the FSP‟s denial of the claim.
1.2 Issue and key findings
Have the Applicants established the damage was caused by an insured
event?
The Applicants have not established the damage was caused by an insured event
because:
the policy provides cover for specified insured events including the escape of
liquid
whilst there is evidence of a broken pipe, the evidence does not establish that
the water escaping from the broken pipe is the proximate cause of the
damage to the building.
1.3 Determination
This Determination is in favour of the FSP.
The FSP is entitled to deny liability for the Applicants‟ claim.
Case No: 386168 Determination Page 2 of 8
2 Reasons for Determination
There has been a full exchange of material between the parties and each party
has had the opportunity of addressing the issues that arise from the material
exchanged.
This Determination follows consideration of the information exchanged and is
based on what is fair in all the circumstances having regard to the relevant legal
principles, terms of the policy, good industry practise and prior Determinations
where applicable.
2.1 Have the Applicants established the damage was caused by an
insured event
The Applicants have not established the damage was caused by an insured
event
The policy is a Home Building and Contents Policy that provides complete
replacement cover and cover for contents for various insured events. Amongst the
insured events is loss or damage arising from the escape of liquid from amongst
other things any drain, fixed pipe, roof gutters, guttering, rain water down pipes,
drainage or sewerage systems.
In these circumstances, the Applicants bear the onus to establish the damage
occurred as a result of an insured event.
Circumstances of the claim
The Applicants lodged a claim with the FSP in July 2014 after they noticed cracks
in the brickwork and cupped wooden flooring. They found water around some of
the stumps in the subfloor area.
The Applicants say an underpinning expert had initially indicated the damage
must be a result of a broken pipe because he did not find any issues with the
water supply system within the building indicating any slow leaks.
Investigations by leak detection specialist (DR) revealed there were two breaks in
the stormwater drains located on the left side of the property.
Based on the information, I accept that the Applicants have established that there
was water escaping from the broken pipe. The issue however is whether the
water discharging from the broken stormwater pipe is the cause of the damage.
Proximate cause of damage
In order to determine whether the Applicants‟ claim falls within an insured event, it
is necessary to determine the proximate cause of the loss. What is the proximate
cause of the loss is the question of fact depending upon the circumstances of
each case.
It is well established that a proximate cause is not necessarily the first or last or
the sole cause of the loss. It is the effective or dominant or operative cause of the
Case No: 386168 Determination Page 3 of 8
loss. If there are several causes operating contemporaneously, then each must
be examined for the qualities of predominance and efficiency as the active
efficient cause that sets a relevant train of events in motion.
Courts have said that if one cause would have resulted in the harm in any case
and the other would not have done so in the absence of the first, then the first is
the proximate cause.
Engineer’s Report
The FSP appointed engineer FM to assess the cause of damage to the property.
The Applicants believe the damage to the property was caused by the water
discharging from the stormwater drain. However, FM was of the view the amount
of water that may have been discharged from the drainpipe was not sufficient to
increase the foundation soil moisture to the point causing footing to heave.
Further, FM observed the assessment of floor level did not show any localised
high regions located near the points where the drain was damaged indicating the
damage did not relate to water escaping from the drain.
The Applicants reject FM‟s findings and say FM did not have local expertise to
assess their claim.
Based on the information presented by FM and the fact that the assessment was
further reviewed by a senior engineer, I am satisfied FM was suitably qualified to
assess the Applicants‟ claim.
Change in soil moisture level occurred due to changing climatic conditions
The Applicants reject FM‟s finding that the subsoil surface was generally dry to
slightly damp and free from mould/fungal growth at the northeast corner of the
subfloor space close to the manhole.
They have presented a photograph of the manhole, taken in September 2014,
showing a small pool of water around a stump. They have also presented another
photograph of the same section indicating the area had dried significantly after the
damaged drain was repaired.
The Applicants maintain these changes to the moisture levels show the broken
drain pipe was the cause of majority of damage sustained to the property.
The FSP‟s file notes indicate the stormwater drain was fixed in early August 2014.
As noted above, the Applicant‟s photograph of the section taken in September
2014 still showed considerable amount of water in the area. It is unclear whether
the water in the area had reduced by any amount between August and
September 2014.
Considering the various findings of FM, I am satisfied the drying of the ground
was due to the changes in weather conditions and subsequent reduction in
ground water levels rather than a result of fixing the drain pipe. This is mainly
because of the changing climatic conditions in Melbourne transitioning from winter
to summer between August and March 2015.
Case No: 386168 Determination Page 4 of 8
Water discharged from the drain was not sufficient to cause heave
The breaks in the drain pipe were at levels of 200 mm to 400 mm below the
finished ground level and above the expected founding level of the perimeter strip
footing.
There is no dispute among the parties that DR did not identify any blockages to
the stormwater drain or that the soil type was moderately reactive clay.
FM was of the view most of the water through the subject drain would follow
through the path of drain (being the least resistance and downhill along the pipe),
rather than flowing parallel to a slope through relatively impermeable clay, under
reinforced concrete strip footings and into the subfloor space.
He also noted the stormwater pipes only transport water during rainfall events
which coincide with increases in natural ground water levels.
Further, the edge heave effect noted after the floor survey indicated the heave
around the perimeter of the building and a valley around the centre of the building
occurred due to the different rehydration rates around the perimeter and internal
sections of the building.
If the damage was caused by the water escaping from the drain pipe, localised
heaving would have been evident around the areas where the drain pipe had
broken.
The Applicants have not presented any further evidence to support their view the
water discharging from the stormwater drain caused damage to the property.
Based on the information exchanged, I am not satisfied that the evidence is
sufficient to establish the proximate cause of the damage to the property was
water discharging from the stormwater drain.
Whilst I accept that it is possible if the water escaping from the stormwater drain
may have contributed to some moisture under the house, I am not satisfied that
this of itself was the proximate cause of damage.
I am satisfied that most likely the movement to the property was due to ground
movement, that had been ongoing for some time and is excluded for cover under
the terms of the policy.
Subfloor ventilation did not comply with building code standards
The Applicants maintain the damage to the timber flooring was due to the
moisture trapped beneath the floor.
FM noted subfloor vents generally were not evenly spaced, not at the same level
around the full perimeter of the buildering and out of 33 vents, only 11 vents were
free from obstruction. The remaining vents were either partially or completely
obstructed internally by timber joists, bearers or excess mortar.
He also found the external finished ground was at a higher level to the subsoil
level internally.
Case No: 386168 Determination Page 5 of 8
The Applicants provided evidence from a subfloor vent specialist who visited the
property in March 2015 that the property had no issues with subfloor ventilation.
Photographs provided with the reports indicate very little ventilation.
Again, I accept that whilst there was significant space between the floor and
ground level as identified by the Applicants‟ subfloor vent specialist, nevertheless
it would appear that the vents do not meet the requirements of the Australian
Building Codes as identified by FM.
Again, I am satisfied that whilst some of the moisture may have been contributed
to by the water escaping the stormwater drainage system, I am satisfied that the
level of ground water would have varied due to the weather conditions.
In my view, the evidence is insufficient to establish that the water escaping from
the stormwater drain was the proximate cause of the moisture retention causing
the flooring to cup.
No expert evidence the flooring caused damage to the brickworks
The Applicants have also argued that the wooden flooring has expanded causing
damage to the brickwork. There is no evidence that the expansion of the flooring
caused damage to the brickworks.
FM notes the bathroom (on the left side where the drain breaks occurred) was
located on the opposite side of section with newly installed timber flooring.
Therefore, this wall could not have been pushed outwards by expanding timber
flooring.
He was also of the view the expansion in the timber flooring will generally result in
the buckling of the flooring rather than causing damage to the brick works. The
usual expansion of the wooden flooring is managed by leaving gaps for expansion
during the installation process.
The Applicants say the photograph of the red tongue supplied was in the meals
area and was consistent with the floor expansion and movement. The red-tongue
flooring had come apart at the join and that the timber beam has tilted off the joist.
This has been caused by increasing pressure of expanding floorboards, causing
the red-tongue flooring to move and separate.
FM says the meals area flooring did not show any visible red tongue in the
underside of the particleboard flooring during its visit. FM was able to identify a
similar effect in the particleboard joint which was at the kitchen/family areas.
Since there was no damage to brickwork in these areas , the FM did not consider
is relevant to the dispute at hand.
Conclusions
In the absence of expert evidence to oppose FM‟s findings, I am satisfied, on the
balance of probabilities that the gaps in the storm water pipe did not cause nor
contribute to the damage sustained to the insured property. I am satisfied that the
damage to the wooden flooring occurred as a result of the issues with subfloor
ventilation and damage to brickwork occurred as a result of differential settlement
of the footing.
Case No: 386168 Determination Page 6 of 8
3 Supporting information
3.1 Product Disclosure Statement
“ Escape of liquid
We cover
Loss or damage to the building caused by liquid leaking, overflowing or bursting from any of
the following:
• refrigerators, freezers, dishwashers and washing machines;
• any drain, fixed pipes, roof gutters or guttering and rainwat er downpipes, drainage and
sewage systems;
…
What we do not cover - general exclusions (cont’d)
You are not covered under any section of your policy for damage, loss, cost or legal liability
that is caused by, arises from or involves:
…
Ground movement
erosion, vibration, subsidence, landslip, landslide, mudslide, collapse, shrinkage or any
other eart h movement, but we will cover landslide or subsidence that is specifically covered
under the following insured events:
• „Storm‟;
• „Flood‟ (but only if you have cover for ins ured event „Flood‟);
• „Earthquak e and Tsunami‟;
• „Explosion‟.”
3.2 Claim lodgement by Applicant
“ I noticed that there was a crack in the brick work
and also there was water around our stumps, we
have had someone out to have a look and he has
stuck a camera down, and found that there is holes
in our drainage pipes. Our wooden flooring has also
cupped from the moist.”
3.3 DF’ s report dated 28/7/2014
“ CCTV camera inspection of storm water drains was completed 24 July 2014.
CCTV camera inspection of the storm water drains down both sides of the house was
completed to Legal Point of Discharge.
The left hand storm water drain has 1 x break behind the garage approximately 200mm
deep under dirt and 1 x break at rear left corner of the house 400mm deep under dirt.
One of the breaks is adjacent to the problem area at the rear left corner of the hous e.
The right hand storm water is clear of any breaks.”
3.4 Loss assessor’s report dated 1/8/2014
“ Cause of Damage Bursting, Leaking , Overflowing.
Stormwater pipe to rear of garage has broken and appears to have run
under the house with the natural slope of the block.
Hous e is approx late 80s early 90s.
Single storey brick veneer with a tiled roof.
Hous e is generally in very good condition.
Resultant Damage Brick work has cracked to the left hand side of the house to the en suite
& lounge room walls.
Vertical cracking to the stepped o ut en suite and horizontal cracking
Case No: 386168 Determination Page 7 of 8
along the damp course below the lounge window.
Cracking to the rear wall below the bedroom window.
There appears to be movement of approx 50mm between the brick work
and the edging below indicating that heaving has occurred.
The man hole access is close to this area where the concrete stump has
been dug around with water evident.
Right hand side of the house /south elevation.
Horiz ontal cracking along the damp course under the meals window
towards the rear decking.
Internal movement to the corner of the window frame.
Sliding rear door to decking out of alignment x approx 8mm.
Internal door to toilet binding on door jamb to strike side.
Hardwood timber floorboards on chipboard sub floor have heaved &
buckled through out the living areas.
Note New kitchen has been installed on top of flooring.”
3.5 Loss assessor’s report dated 5/09/2014
“ The gaps in the storm water pipe running parallel to the northern
external wall did not cause , nor contribute to, the observed
damage to the subject structure.
Poor ventilation caused observed damage to the timber floor
covering in the Study, Front entry, Living, Dining, Family, Kitchen
and meals areas.
Long term differential footing movement due to foundation soil
moisture content variations as outlined in Paragraph 4.15 caused
the observed damage to the external brickwork, the Kitchen
cabinets and the Meals area window frame.”
3.6 FM ’s report dated
5.0 Conclusion
5.1 Based on the res ults of this investigation, [FM] provides the following opinions:
• The gaps in the storm water pipe running parallel to the northern external wall
did not cause, nor contribute to, the observed damage to the subject structure.
• Poor subfloor ventilation caused observed damage to the timber floor covering in
the Study, Front Entry, Living, Dining, Family, Kitchen and Meals areas.
• Long term differential footing movement due to foundation soil moisture content
variations as outlined in Paragraph 4.15 above caused the observed damage to
t he external brickwork, the Kitchen cabinets and the Meals Area window frame.”
3.7 Applicants’ subfloor vent specialist’ s report dated 11/03/2015
“ Underfloor
• Inspection revealed an open floor space under the affected areas
• Floor clearance is approx 1.25m at easterly end of the house
• We checked for humidity levels and no adverse readings were observed
• Soil was dry with a layer of dust on the surface.
After viewing the property at [Insured Risk Address] in October 2014 and again in
November 2014, it is my professional opinion that this property did not exhibit any signs of
poor subfloor ventilation or related noticeable moisture issues.”
Case No: 386168 Determination Page 8 of 8
3.8 Timeline of events
Date Event
22/7/2014 Date of loss .
24/7/2014 Date claim was reported to the FSP .
28/7/2014 Leak detection test and report .
1/08/2014 Loss assessor‟s findings .
7/08/2014 Broken pipes were repaired .
19/08/2014 FM attends the insured property .
1/09/2014 FM ‟s report was issued .
11/03/2015 Applicant‟s subfloor vent specialist‟s report .
Coded fields were extracted from the text by a language model and may contain errors. The published PDF is the authoritative record.