Text of the determination
Determination
General Insurance - Domestic Insurance - Home Building - FSP Decision - Denial of
Claim - Exclusion/Condition
Determination
Case No: 384164 Determination Page 1 of 8
Case number : 384164 20 April 2015
1 Overview
1.1 Dispute
The Applicant lodged a claim under her home insurance policy with the Financial
Services Provider (FSP) after she noticed her kitchen bench sinking in mid-2011.
The Applicant believed the damage was due to a leaking waste pipe under the
kitchen floor.
The FSP denied the claim on the basis that the damage was not caused by the
leaking pipe but by factors such as inadequate ventilation and poor construction
(which are not covered under the policy) and/or wear and tear, deterioration and
corrosion (which are expressly excluded under the policy).
1.2 Issues and key findings
Is the FSP liable for the damage?
The available information establishes that, on the balance of probabilities, at least
part of the claimed damage was caused by the build -up of moisture in the sub-
floor area over an extended period of time due to inadequate ventilation, as a
result of the manner in which the extension was constructed. This led to the
gradual deterioration of the timber joists and bearers. Damage caused in this
manner is not covered under the policy
However, the leaking pipe identified in November 2011 allowed further moisture to
escape into the sub-floor area, resulting in additional damage to the timber
framework (which ultimately led to the subsidence of the floor). Damage caused in
this manner is subject to cover under the policy.
How should the claim be settled?
Given the claimed damage is attributable to both the poor construction of the
extension and the leaking pipe, it is fair in all the circumstances that the Applicant
and the FSP bear the costs of repairing the damage equally.
1.3 Determination
This Determination is partly in favour of the Applicant.
The FSP is to pay the Applicant an amount equal to 50% of the costs of repairing
the claimed damage (including temporary accommodation if required), based on a
Case No: 384164 Determination Page 2 of 8
scope of works and quotation to be obtained in accordance with section 2.2
below.
The FSP is to pay the Applicant an additional amount of $2,650 as reimbursement
of costs incurred in locating the source of the water leak and obtaining her
engineer’s report.
Case No: 384164 Determination Page 3 of 8
2 Reasons for Determination
2.1 Is the FSP liable for the damage?
Application of policy depends on cause of damage
The Applicant is required to show that, on the balance of probabilities, she has
suffered a loss caused by a risk insured against under the policy. This is known
as a prima facie claim.
If the Applicant is able to establish a prima facie claim, then the onus shifts to the
FSP to show that, on the balance of probabilities, it is entitled to rely on an
exclusion under the policy or is otherwise entitled to deny the claim.
The policy provides cover for damage to the Applicant’s property caused by the
events listed in the policy (including the sudden and unexpected escape of liquid
from a fixed pipe), subject to the conditions and exclusions set out in the policy.
While the event of “escape of liquid” refers to the relevant liquid escaping
“suddenly and unexpectedly”, the policy separately makes clear that it also covers
the slow escape of liquid over an extended period of time in circumstances where
the Applicant could not reasonably be expected to have been aware of the leak.
The Applicant has provided a report from her plumber (AB) which confirms that in
November 2011 he repaired a broken waste pipe which had been leaking under
the house.
The Applicant has also provided a report from her engineer (VC) which confirms
that the timber floor frame and floorboards in the kitchen have been damaged by
exposure to moisture over an extended period of time. Based on his inspection of
the sub-floor, VC considered that the damage had been caused by the leaking
waste pipe.
The FSP acknowledges that there was a broken pipe which had been leaking
under the kitchen floor. The FSP also accepts that the damage to the kitchen floor
has been caused by deterioration of the timber bearers and joists due to
excessive moisture over an extended period of time.
However, based on the report of its engineer (DW), the FSP says that the nature
and extent of the damage is not consistent with it having been caused by a
leaking pipe.
The FSP says that the damage was caused by the build-up of moisture in the
sub-floor over an extended period of time as a result of inadequate ventilation and
poor construction techniques. Damage caused in this manner is not covered
under the policy. The FSP says that such damage also falls within the general
exclusions under the policy for damage caused by wear and tear, deterioration,
mould and rising damp.
Accordingly, it is necessary to determine the cause of the damage to the
Applicant’s kitchen floor.
Sub-floor area had inadequate ventilation
Case No: 384164 Determination Page 4 of 8
The kitchen area where the damage occurred was built as part of an extension to
the home constructed a number of years earlier. The extension was built on a
concrete slab, which was installed over an existing timber floor.
The claimed damage consists of moisture damage to the original timber joists,
bearers and floorboards located under the newer concrete slab and tiles. This
damage has resulted in gradual deterioration of the timber framework which has
ultimately caused the slab to sink, most notably at the expansion joint between
the concrete slab for the extension and the original timber flooring for the main
part of the house.
The reports prepared by the various contractors confirm that the manner in which
the extension was constructed did not leave any openings in the foundation
brickwork, resulting in poor ventilation of the sub-floor area. The lack of adequate
ventilation was noted by the FSP’s assessor (J), builder (AG) and engineer (DW),
as well as by the Applicant’s pest expert (A) and engineer (VC).
The FSP’s engineer (DW) concluded that the moisture damage to the original
timber flooring was due to the ongoing effects of naturally occurring ground
moisture in the poorly ventilated sub -floor area. DW noted that the stains to the
various joints and bearers appeared to be random and there was no evidence of
localised damage concentrated in the area of the leaking pipe.
While the Applicant says that DW conducted a cursory inspection only of the sub -
floor area, the Panel notes that his report includes several clear and detailed
photographs of the relevant area taken by DW during his attendance at the
property.
Having carefully reviewed these photographs (together with the additional
photographs provided by the Applicant ’ s engineer (VC)), the Panel considers that
they indicate that significant moisture damage was observed in sections of the
floor beyond the area of the leaking pipe.
The Panel notes that the Applicant’s builder (CC) had previously confirmed that
the moisture damage to the timber frame and particle board flooring was most
pronounced in the corner of the kitchen where there was less than 300 millimetres
between the timber joists and the natural ground level, allowing extremely limited
ventilation. The Applicant’s pest expert (A) also reported decay in the timber
bearers and joists located under the main bedroom toilet.
For the reasons outlined above, the Panel is not satisfied that the bulk of the
claimed damage was caused by the leaking pipe.
The Panel considers that, on the balance of probabilities, a significant portion of
the damage was caused by the build-up of moisture in the sub-floor area over an
extended period of time, due to the inadequate ventilation in the sub-floor area, as
a result of the manner in which the extension was constructed. This has resulted
in the gradual deterioration of the timber framework and contributed to the
subsidence of the kitchen floor.
Leaking pipe contributed to damage
Case No: 384164 Determination Page 5 of 8
While the Panel considers that part of the claimed damage occurred over time as
a result of inadequate ventilation, the Panel is also satisfied that the leaking pipe
identified in November 2011 contributed to the claimed damage.
The Applicant’s builder (CC) stated that when he inspected the sub -floor area in
May 2012, he found the area to be damp, indicating that water had accumulated
in the area for a prolonged period of time. CC considered this to be due to the
effects of the leaking pipe.
When CC re-inspected the sub-floor area in June 2012, he noted that the soil
appeared to be drying out, relative to his early inspection. This suggests that the
leaking pipe contributed to the moisture content of the sub-floor soil (although it is
noted that both inspections occurred after the leaking pipe had already been
fixed).
The Applicant’s engineer (VC) carried out a thorough inspection of the sub -floor
area in November 2012, during which he observed residual material on the barrier
and joint of the waste pipe (indicating a prior leak) and contaminated soil (which
he considered to be due to the effects of leaking waste).
The FSP’s engineer (DW) disputes that the volume of waste leaking from the pipe
would have been significant enough to cause the extent of deterioration to the
timber framework observed.
However, based on the available information, the Panel is satisfied that the
leaking waste pipe identified in November 2011 did contribute to the claimed
damage by allowing further moisture to escape into the sub-floor area, causing
additional damage to the timber framework which ultimately resulted in the
subsidence of the kitchen floor.
Damage is attributable to both leaking pipe and inadequate ventilation
As outlined above, the Panel is satisfied that the inadequate sub-floor ventilation
provided when the extension was constructed contributed to the build-up of
moisture in the sub-floor area and the gradual deterioration of the timber
framework over a prolonged period of time.
The Panel notes that damage of this nature typically occurs gradually over an
extended period of time and would not have been immediately apparent to the
Applicant.
To the extent that the damage was caused by naturally occurring ground moisture
and inadequate ventilation, it is not covered under the policy (which provides
cover for damage caused by the listed events only).
However, the Panel is also satisfied that the leaking pipe identified in November
2011 allowed further moisture to escape into the sub-floor area, resulting in
additional damage to the timber framework.
To the extent that the claimed damage was caused by the leaking pipe, it is
subject to cover under the policy.
Case No: 384164 Determination Page 6 of 8
For the reasons outlined above, the Panel is satisfied that both the inadequate
ventilation and the leaking pipe have materially contributed to the claimed
damage.
In the absence of sufficient information to determine the proportionate contribution
of each of these factors, the Panel considers that it is fair in all the circumstances
that the FSP and the Applicant bear the cost of repairing the claimed damage
equally.
2.2 How should the claim be settled?
Extent of damage and costs of repairs is unclear
Under the terms of the Applicant’s policy, the FSP is required to settle a claim for
building damage by repairing the damage or paying the Applicant the cost of
repairing the damage (based on the most competitive quote received).
The Applicant has provided a quote for $64,185 from her builder (H) for the
necessary repairs to the kitchen, including the replacement of the concrete slab
and floor tiles, repairs to the plasterboard and the replacement of damaged
appliances.
The FSP disputes the extent of the damage to t he Applicant’s kitchen caused by
the moisture-affected timber flooring. Among other matters, the FSP disputes that
40% of the kitchen flooring requires replacement.
The Panel notes that the quote provided by the Applicant appears to include
repairs to the joinery in the laundry, in circumstances where it is not clear that this
damage is related to the current claim. There is also insufficient information
available to determine the extent to which appliances in the kitchen and/or laundry
need to be replaced.
In the circumstances, the Panel considers that the FSP should be required to
engage an appropriately qualified expert (who has not been involved in the claim
to date) to prepare a scope of works for the repair of the damage to the
Applicant’s property ca used by the deterioration of the moisture-affected timber
framework under the kitchen.
Following receipt of the scope of works, the FSP is to obtain quotations from two
suitably qualified builders (who are willing to conduct the repairs directly on behalf
of the Applicant) for the cost of carrying out the repairs set out in the scope of
works, together with an estimate of the likely timeframe for completion of the
works and confirmation as to whether temporary accommodation will be required
(and, if so, for how long). The Applicant may nominate one of the builders to
provide a quotation.
The FSP is to cash settle the Applicant for 50% of the sum of the more
competitive quotation and the reasonable costs of temporary accommodation, to
the extent required whi le the repairs are carried out.
Reimbursement of professional costs
Case No: 384164 Determination Page 7 of 8
The Applicant seeks reimbursement of costs incurred by her in engaging
contractors to identify the cause of the damage.
The policy provides that the FSP will pay for the reasonable costs of locating the
source of a water leak. The FSP has previously agreed to reimburse the Applicant
for $1,000 of costs incurred by the Applicant in locating the leaking pipe, subject
to providing copies of relevant receipts.
The Applicant engaged the services of various contractors (including a pest
expert, a plumber and a builder) in order to identify the leaking pipe. Based on the
information provided by the Applicant (including relevant receipts), the Panel is
satisfied that she incurred costs of at least $1,000 in doing so.
The Applicant also seeks reimbursement for fees of $1,650 paid to her engineer
(VC) for the preparation of this report.
Under paragraph 9.4 of the FOS Terms of Reference, FOS may require a
financial services provider to contribute to legal or other professional costs
incurred by an applicant in the course of their dispute.
The Panel accepts that it was necessary for the Applicant to engage an engineer,
in order to be able to effectively dispute the FSP’s denial of her claim, which wa s
based primarily on the findings of its own engineer (DW).
The Panel is satisfied that VC’s report has been of assistance in establishing that
part of the claimed damage was caused by the leaking pipe.
In these circumstances, the Panel considers that the FSP should be required to
reimburse the Applicant for the costs of $1,650 incurred in obtaining VC’s report.
Case No: 384164 Determination Page 8 of 8
3 Supporting information
3.1 FOS approach to this dispute
This dispute has not been the subject of a FOS Recommendation. Due to the
nature of the dispute, it has been referred directly to a Panel for Determination, in
line with the Operational Guidelines to the FOS Terms of Reference. The Panel
consists of an Ombudsman and two representatives with consumer and insurance
experience.
The Panel has decided this case on its merits, having regard to the relevant law,
good industry practice, codes of practice and previous Financial Ombudsman
Service (FOS) decisions.
There has been a full exchange of all material information relied on for the
purposes of this Determination and each party has had the opportunity to address
any issues raised by the other.
The Panel has reviewed and considered all of the material provided by the
parties. While the parties have raised numerous issues in their submissions, for
the purposes of this Determination, the Panel has restricted its commentary to
those issues that it considers directly relevant to the outcome only.
3.2 Terms of policy
Su bject Terms
Insured event –
escape of liquid
Liquid escaping suddenly and unexpectedly from a :
water main, drain, fixed pipe …
Escape of liquid –
specific exclusions
No
Damage or loss resulting from:
liquid escaping slowly over a period of time where you could
reasonably be expected to be aware of this condition …
Ge neral exclusions You are not cover ed under any section of the policy for
damage … caused by or arising from or involving:
wear and tear, rust, deterioration or corrosion,
structural … or other failure or breakdown,
mould, wet or dry rot, rising damp or dampness …